background image

5

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

Hot, high pressure refrigerant gas is routed from the 
compressor to the condenser coil. The refrigerant is cooled 
and condensed by giving up its heat to the air that is about 
to be discharged from the unit. The refrigerant liquid then 
passes through a filter/drier and capillary tubing which 
cause the refrigerant pressure and temperature to drop. It 
next enters the evaporator coil where it absorbs heat from 
the incoming air and evaporates.
The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the 
accumulator after leaving the evaporator coil. The 
accumulator prevents any liquid refrigerant from reaching 
the compressor. The compressor evacuates the cool 
refrigerant gas from the accumulator and compresses it to 
a high pressure and temperature to repeat the process.

5.2 Troubleshooting

No dehumidification, neither hour meter display nor 
compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet
2.   Defective control board
3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor 
compressor run with POWER button ON.

1.   Defective control board
2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but 
compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on
2.   Defrost thermistor defective or loose

3.   Loose connection in compressor circuit
4.   Defective compressor overload
5.   Defective compressor
6.   Defective relay
7.   Upper housing is not sealed to lower housing

No dehumidification, air mover runs but compressor does 
not.

1.   Bad connection in compressor circuit
2.   Safety float switch closed, check pump reservoir
3.   Defective compressor capacitor
4.   Defective compressor overload
5.   Defective compressor
6.   Defective control board

Air mover does not run. Compressor runs briefly but cycles 
on and off.

1.   Loose connection in blower circuit
2.   Obstruction prevents impeller rotation
3.   Defective air mover

Unit removes some water but not as much as expected.

1.   Air temperature and/or humidity have dropped
2.   Humidity meter and/or thermometer used are out of 

calibration

3.   Unit has entered defrost cycle
4.   Air filter dirty
5.   Defective defrost thermistor
6.   Low refrigerant charge
7.   Air leak such as loose cover
8.   Defective compressor
9.   Restrictive exhaust or inlet ducting

Unit runs but does not pump water.

1.   Hose kinked or plugged
2.   Pump motor defective
3.   Pump check valve plugged
4.   Bad connection in pump circuit
5.   Hose disconnected internally
6.   Defective control board (pump phase)

Unit pumps water automatically but not when PURGE 
button is pushed.

1.   Bad connection in PURGE button circuit
2.   Defective control board

Figure 5: Refrigeration system

Summary of Contents for R200

Page 1: ...obstructions Telescoping Handle A heavy duty retractable handle for ease of transport and reduces space for storage and stacking Recessed 12 Wheels Allows greater maneuverability on the job site and efficient storage Rolls over obstacles with ease Pleated Media Air Filter A 12 x12 x1 MERV 11 filter is standard Stacking Nesting Reduces space for ease of stacking and storage Specifications subject t...

Page 2: ... Five years 1st year 100 of Parts and Labor 2nd 5th year 100 of sealed refrigeration system parts Dimensions Unit Shipping Width 20 21 Height 33 5 35 25 Depth 20 21 Weight 105 lbs 115 lbs Patent 7 246 503 7 281 389 7 540 166 3 Operation Place dehumidifier inside structure place condensate hose into a drain or a large water tight container and turn on To decrease drying times make sure all windows ...

Page 3: ... plastic exhaust tabs If the R200 is located in the unaffected area the intake can be ducted with 12 flex duct see accessories in section 6 Attach the flex duct to the top cover by hooking the spiral wire under the four tabs Tape the duct to the top cover for a complete seal 3 5 Defrost Cycle If the low side refrigerant temperature drops below the defrost set point due to excessive frost formation...

Page 4: ... IMPORTANT DO NOT operate the unit without the filter or with a less effective filter as the heat exchanger and coils inside the unit could become clogged and require disassembly to clean 4 2 Storage There are two issues to consider when the Phoenix R200 is stored between uses and both pertain to the water trapped in the unit damage caused by freezing or biological growth The effect of the trapped...

Page 5: ...WER button ON 1 Defective control board 2 Loose connection in internal wiring Some dehumidification air mover runs continuously but compressor only runs sporadically 1 Unit is in defrost cycle DEFROST light on 2 Defrost thermistor defective or loose 3 Loose connection in compressor circuit 4 Defective compressor overload 5 Defective compressor 6 Defective relay 7 Upper housing is not sealed to low...

Page 6: ...7 Reassemble thermistor and dehumidifier using the above procedure in reverse Figure 8 Picture of the float safety switch 5 5 Condensate Pump The internal condensate pump removes water that collects in the reservoir To replace the condensate pump 1 Unplug the unit 2 Remove the front housing 3 Unplug the pump wires from the wire harness 4 Remove the condensate hose and the one screw attaching the p...

Page 7: ...BLK 3 YEL 7 E1 E3 E2 E5 E4 BLK 5 BRN 6 BLK 12 BLU 18 BLK 4 WHT S R C 4026354 C Figure 9 Wiring diagram 7 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 6 Options Accessories 4024750 Intake Flex Duct 12 x 25 Metallize Polyester 4024935 Lay Flat Duct 10 Round x 250 Roll To order contact Therma Stor LLC at 1 800 533 7533 7 Wiring Diagram ...

Page 8: ...26986 13 Cord 1 4032315 14 Control Board 1 4026763 15 Capacitor Compressor 45 μF 1 4033032 05 16 Capacitor Impeller 15 μF 1 4033031 07 17 Thermistor 1 4031279 18 Handle lever 1 4026350 Description Qty Part No Compressor 1 4029190 Evaporator Coil 1 4026985 Condenser Coil 1 4026983 Accumulator 1 4028297 Condensate Pump 1 4034582 01 Description Qty Part No Float Safety Switch 1 4034374 Impeller Air M...

Page 9: ...The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitation and Exclusions If any Phoenix R200 Dehumidifier part is repaired...

Reviews: