Phoenix D385 Owner'S Manual Download Page 3

3

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

Process Air Filter Replacement

4021475    16” x 20” x 2” MERV 11 Filter (Standard)
4024969    16” x 20” x 2” MERV 6 Filter (Optional)
4022164    16” x 20” x 2” MERV 14 Filter (Optional)

Reactivation Air Filter Replacement

4026860    12” x 12” x 1” MERV 7 Filter (Standard)
4026315    12” x 12” x 1” MERV 8 Filter (Optional)

3 Operation

3.1 How the Phoenix D385 works

Your Phoenix D385 has two separate air streams that run 

through it – Process (Fig. 1) and Reactivation (Fig. 2).

Note: Check for airflow at all inlets and outlets. DO NOT run 
unit if no airflow is detected.

Process Air Stream:

  

P1 – 

385 CFM of air enters (12”flex) the top of the machine 

and...

P2 – ...

water vapor from incoming air is deposited on the 

desiccant wheel.

P3 –

 385 CFM of dry air exits (10” lay flat) the machine.

Reactivation Air Stream:

R1 –

 75 CFM of air enters (6”flex) the lower-side of the 

machine and...

R2 –

 passes over the heater coils.

R3 –

 Water vapor is picked up from the desiccant wheel by 

the hot air and...

R4 –

 ...75 CFM of wet air exits (6”flex) the machine.

3.2 Avoiding Secondary Damages

The D385 is a powerful tool capable of removing a great deal 

of water from most environments. Care must be taken to 

avoid secondary damages of over-drying and or unexpected 

condensation.
Your Phoenix D385 removes vapor water from the incoming 

process air stream (Fig. 1) and transfers it to the outgoing 

reactivation air stream (Fig. 2). The reactivation exhaust air is 

hot and wet. 

Take care to prevent the reactivation exhaust air stream 
from causing secondary damage due to condensation. 

If the reactivation exhaust air stream cools below its 

dewpoint liquid water will condense inside the duct work 

creating puddles. If the reactivation exhaust air stream is not 

exhausted completely from the structure it can also cause 

secondary water damage.
Your Phoenix D385 does not produce liquid water internal 

to the machine. There is no condensate pump and no drain 

hose.
The D385 desiccant dehumidifier will continue to remove 

water from already dry, cold air. It is possible to over-dry 

objects and or structures.

Care must be taken to avoid secondary damages due to 
over-drying.

3.3 Electrical Requirements

When used on a water loss work site, ground fault circuit 

interrupter (GFCI) outlets are required.
Your Phoenix D385 requires a total of 24 amps, 115VAC. In 

order to run at all, this machine must be plugged into two 

separate circuits each with a minimum of 12 amps dedicated 

capacity available. 
The D385 has two separate power cords, each cord must be 

plugged into its own 15 amp circuit. If both cords are plugged 

into the same 15 amp circuit this circuit will trip when the 

unit is turned on.
Another situation to avoid is that one or both of the circuits 

which the D385 is using can be tripped by other appliances 

drawing power from either circuit. This can happen well 

after a job site has been set-up as in the case with a freezer 

compressor turning on.
Care must be taken to insure that the D385 always has 

sufficient power available to run without tripping breakers or 

blowing fuses.
If your location requires the use of an extension cord, use 

safe techniques in selection and connection. Such cords 

must be grounded and rated for carrying 12 amps: 14 gauge 

minimum for one extension less than 25ft in length or 12 

gauge for one extension less than 50ft in length.

Figure 1: Desiccant process air stream.

Figure 2: Desiccant reactivation air stream.

P1

P2

P3

R1

R3

R2

Summary of Contents for D385

Page 1: ...ly or horizontally the D385 will fit inside most crawlspaces Having the D385 securely inside rather than outside the crawlspace access deters the possibility of tampering with the dehumidifier or the set up The 385 CFM of process air will provide 3 ACH on an affected area up to 7000 cubic feet The Phoenix D385 is easy to transport and set up The D385 will fit on your truck in the areas already des...

Page 2: ...4022537 10 Lay Flat Duct 500 4024935 10 Lay Flat Duct 250 4024440 Kestrel 3000 Multi Function Air Meter Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix D385 dehumidifier Table of Contents Introduction 1 1 Safety Precautions 2 2 Specifications 2 3 Operation 3 3 1 How The ...

Page 3: ...int liquid water will condense inside the duct work creating puddles If the reactivation exhaust air stream is not exhausted completely from the structure it can also cause secondary water damage Your Phoenix D385 does not produce liquid water internal to the machine There is no condensate pump and no drain hose The D385 desiccant dehumidifier will continue to remove water from already dry cold ai...

Page 4: ...CTIVATION OUTLET Must always be ducted out of the affected area NEUTRAL PRESSURE The reactivation inlet and outlet are ducted from outside the drying area This can be beneficial if the air outside the drying chamber is very damp REACTIVATION OUTLET Must always be ducted out of the affected area REACTIVATION INLET Duct in from outside the affected area POSITIVE PRESSURE The process inlet is ducted ...

Page 5: ... 12 x12 x1 filter is located in the bottom of your D385 To change the reactivation air filter lay the D385 down in a horizontal position The filter access slot is located on the bottom of the machine Fig 4 Open retainment clip remove old filter and replace with fresh filter The stock filter supplied carries a MERV 7 filtration efficiency rating This filtration prevents plugging the heater or loadi...

Page 6: ...not fixed to driveshaft Tighten or replace set screw 4 Rotor is obstructed from rotating Check bearings and confirm rotor turns freely 5 Defective gear motor Rotor motor and heater operating blower s not operating 1 Defective blower or blower capacitor 6 Wiring Diagram PROCESS BLOWER GRN 25 BLK 11 WHT 24 CORD 1 CORD 2 WHT WHT BLK BLK BLK BRN BLU 27 BLU BLU RED RED WHT 9 BLK 8 BLU 7 ORG 6 BLU BLK G...

Page 7: ...ATION AIR 6 4037807 HEATER CORE PHX D385 7 4029266 TOP COVER DESICCANT 385 8 4026898 THERMAL OVERLOAD CUT OUT SWITCH PROCESS AIR 9 4035235 11 CAPACITOR RUN 8 MFD DRY REACTIVATION AIR 10 1970010 CONTROL RELAY SPST 110VAC COIL 25AMP CONTACTS 11 4026773 MOTOR DESICCANT WHEEL 12 4026795 BELT DRIVE PHOENIX DESICCANT 13 4026772 WHEEL DESICCANT 14 4021475 FILTER AIR 16 X 20 X 2 PROCESS AIR 15 4026194 SWI...

Page 8: ...horized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC reasonable control Limitations and Exclusions If any Phoenix D385 Dehumidifier part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that t...

Reviews: