background image

INSTALLATION

CAUTION:

 Disconnect all electrical power to the cooler 

before attempting to install, open, or service your cooler. 
More than one disconnect will be required to de-energize 
the equipment for servicing. If the cooler is 
thermostatically controlled, the thermostat may not be 
used as the power supply disconnect, as it may reset and 
start the unit unexpectedly.

Even while routinely inspecting or servicing the inside, the cooler can 
be accidentally started. Keep all personnel away from the cooler and 
electrical supply when you are working on it. Before servicing or 
cleaning unit, switch power off at the service disconnects and lock the 
disconnecting means to prevent power from being switched on 
accidentally. When the service disconnects cannot be locked, 
securely fasten a prominent warning device, such as a tag, to the 
service disconnect or panel.

Electric Power Supply Requirements

CAUTION: 

All electrical installations must comply with 

local and national building & safety codes; all work must 
be performed by qualified personnel only.

NOTE 

- References in this manual to: National Electric Code 

(N.E.C.), local or national codes means that those items must 
comply with applicable installation codes as specified by the building 
code authority having jurisdiction at the installation location. It is the 
installer's duty to comply with all requirements.

IMPORTANT:

This UL Classified Evaporative Air Cooler requires the use of 
two separate electrical power supply circuits to the unit: 

1. Blower (fan) motor: 

!

Single phase - 115, 208, 230 Volt AC / 60 Hz

!

3 phase - 200, 208, 230, 460 Volt AC / 60 Hz

2.

Circulating pump: (depending on model, more than one pump 

per unit may be required, see catalog information)

!

Single phase - 115 or 230 Volt AC / 60 Hz. The pump power 

supply circuit must be a GFCI protected circuit.

Make sure that the circulating pump and (where used) a single 
voltage blower motor (i.e.; 115V, 230V) are connected to the voltage 
and frequency (Hz) stamped on each component's specification 
plate. Make sure that a multiple voltage blower motor (i.e., 115/208-
230V) has been properly connected internally to match the available 
power supply voltage, per the connection diagram on the motor's 
specification plate.

NOTE: Improper motor voltage connections will void 
motor warranties.

The motor Hp / full load current, voltage, phase, number of motor 
speeds and the length of wire from the power supply to the motor are 
all factors in determining the gauge of wire used in the circuit.

Safety Disconnect Switches

Each unit must have safety disconnect switches (motor circuit and 
pump circuit) compatible with the installation location and installed in 
accordance with the National Electric Code (N.E.C.), Article 430 
and/or local codes.  Each disconnect switch shall be a U.L. Listed 
disconnect which breaks all ungrounded conductors that can carry 
current to the unit.

Over-current (short circuit) Protection

Each unit must have over-current protection equipment intended to 
protect all ungrounded pump and motor branch-circuit conductors, 
motor control apparatus, pumps and motors against overcurrent due 
to short circuits or ground faults. They shall have minimum enclosure 
classifications compatible with the installation location and installed 
in accordance with N.E.C., Articles 240 and 430. These devices shall 
be U.L. Listed short circuit protection devices, sized and installed in 
accordance with specifications as stated in N.E.C., Article 430.

Overload Protection

All pumps and single-phase motors available from Phoenix 
Manufacturing, Inc. for use in Industrial/Commercial coolers have 
integral thermal running and locked rotor overload protection as 
required by the N.E.C. 
All 3-phase motors require installation of properly sized and mounted 
thermal running / locked rotor overload protection. 
Branch circuit protection should be properly sized and installed by a 
competent electrician in accordance with local and national code 
requirements. 

Motor Start Switch / Motor Starter

All motor applications require the use of Start/Stop switches 
and/or motor starters of the proper current capacity.

In applications where a switch is deemed adequate to start the motor, 
as defined by N.E.C., Article 430, the branch circuit shall be sized in 
accordance with N.E.C., Articles 210 and 430. The enclosure for the 
switch and its installation location shall comply with N.E.C. 
requirements for the installation of the switch. 
A motor starter with integral thermal (running and locked rotor) 
overload protection is used to start/stop 3-phase motors. Motor 
starter shall be sized in accordance with specifications stated in the 
N.E.C., Article 430. Starters mounted to the unit shall have a 
minimum NEMA 3R (raintight/rainproof) enclosure rating. Starters 
mounted remote to the unit shall have a minimum enclosure 
classification compatible with the location and installed in 
accordance with N.E.C., Article 430.

Pump Power Supply Circuit

The pump supply circuit shall be a GFCI protected circuit with 
overcurrent (short circuit) protection of 15 AMP and have a minimum 
of #14 AWG copper wire to the pump receptacles in the junction box 
assembly. Conduit to the junction box shall be rain-tight or liquid-
tight, flexible metal conduit with a separate ground wire, installed per 
N.E.C., Article 351.

Electrical Ground

For maximum safety, make sure cooler cabinet, blower motor and 
pump(s) are properly grounded to a suitable ground connection as 
required by all local and national codes.

 

Motor Installation

!

Mount blower motor to the motor mount using the four carriage 
bolts and nuts provided in the parts bag. Tighten nuts enough to 
hold motor in place until belt(s) have been installed, aligned 
and properly tensioned. 

!

Connect motor to electrical power supply, as required, making 
sure motor is wired for proper rotation (some single phase and 
all 3 phase motors are bi-directional). See arrow on blower 
housing.

!

Adjust motor sheave for expected blower RPM requirement 
(refer to cooler design/capacity selection tables and RPM 
information  available in the catalog

!

Insert motor sheave onto the motor shaft, align by vertically 
centering motor pulley inline with blower pulley, tighten 
setscrew to 95 in-lbs.

!

Install belt(s) from motor sheave to the blower pulley and adjust 
belt tension (see “Belt Adjustment”).

!

Rotate blower wheel by hand to see that it moves freely without 
rubbing against housing.

!

After motor and belt(s) are installed, complete the motor 
mounting process by insuring all screws, nuts and bolts are 
tightened down properly.

 UL Classified  Industrial / Commercial Evaporative Cooler Use and Care Manual  3

Summary of Contents for D8801

Page 1: ...tives or treatments in this cooler will void the warranty Your warranty does not cover shipping damage Report all shipping damage at once to dealer or carrier making the delivery For future reference...

Page 2: ...coolers are used to cool large areas such as factories auditoriums or supermarkets divide the area and strategically locate units of proper capacity in each area Install coolers in a location where on...

Page 3: ...with the installation location and installed in accordance with N E C Articles 240 and 430 These devices shall be U L Listed short circuit protection devices sized and installed in accordance with spe...

Page 4: ...and alignment is important proper setup reduces power consumption and prolongs life of belt and motor When installing or adjusting belt loosen the motor adjustment bolts and adjust to proper tension...

Page 5: ...ts Check torque on setscrews and cabinet hardware Motor and Blower Pulley set screws 95 in lbs Blower Wheel set screws 1 per side 150 in lbs Cabinet hardware 25 in lbs GENERAL INSPECTION Initial Start...

Page 6: ...otor blower assembly Check belt condition and replace it if frays or cracks appear Check alignment of blower pulley with motor pulley Cleaning Water Pump Hose CAUTION Disconnect all electrical power t...

Page 7: ...sition pump as shown for your specific model make sure pump sits flat on bottom Bend bracket as required to conform to the mounting surface Using slotted holes in bracket as a guide mark and drill two...

Page 8: ...xcessive humidity inside Musty or unpleasant odor POSSIBLE CAUSE 1 No electrical power to unit A Fuse blown B Circuit breaker tripped 2 Belt loose or broken 3 Motor overloaded and or frozen bearings A...

Reviews: