INTERBUS
105752_en_03
PHOENIX CONTACT
49 / 56
A 3
INTERBUS
Both Inline input terminals and Inline output terminals are connected to the ILC 131 ETH
using INTERBUS.
A 4
Network interface
1 x Ethernet 10/100Base-T(X)
Owing to the configuration of the Inline controllers as master and slave (see
), the default IP addresses are automatically assigned to the Inline control
-
lers during the first startup of the multiplexer system. These addresses are required for ac
-
cessing the web interface. The following table indicates the default IP addresses for both
the master and slave:
0 mA ... 20 mA
1 x IB IL AI 2/SF
↔
1 x IB IL AO 1/SF
0 mA ... 20 mA
1 x IB IL AI 2/SF
↔
2 x IB IL AO 1/SF
4 mA ... 20 mA
1 x IB IL AI 2/SF
↔
1 x IB IL AO 1/SF
4 mA ... 20 mA
1 x IB IL AI 2/SF
↔
2 x IB IL AO 1/SF
±10 V
1 x IB IL AI 2/SF
↔
1 x IB IL AO 2/U/BP
The onboard terminals of the Inline controller are only used for configuration purposes,
they are not available as I/O terminals.
Number of I/O points
max. 4096
Number of bus segments
max. 63
Transmission speed
500 kbps
Only use Inline terminals with a uniform transmission speed in the entire connected Inline
system (local bus and remote bus).
Speed
10 Mbps (10Base-T), 100 Mbit (100Base-TX), half
duplex, full duplex, auto negotiation.
Connection technology
CAT5 twisted pair cable
Twisted pair cable with a conductor cross section of
0.14 mm
2
to 0.22 mm
2
8-pos. RJ45 female connector
Table A
-
7
Permissible complementary arrangement of analog terminals
Analog range
Modules to be used