PHOENIX CONTACT page 8  of  9

Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40

5.9. Remote Shutdown 

("Remote", Fig. 12)

The device has a UPS remote shutdown function for 

speci

fi

c shutdown.  

Remote shutdown must be deactivated for the device 
to switch to buffer mode in the event of a supply voltage 
failure.  

 

Remote Shutdown Off

•  The "Remote shutdown R1" and "Remote 

shutdown R2" terminal points are short circuited 
(e.g., with a plug-in bridge) OR
The "Remote shutdown R2" terminal point is 
supplied with a 24 V DC voltage

•  The QUINT-DC-UPS switches to buffer mode in the 

event of a supply voltage failure

Remote Shutdown On

•  The "Remote shutdown R1" and "Remote 

shutdown R2" terminal points are not connected

•  All LEDs are off
•  The QUINT-DC-UPS does not switch to buffer mode 

in the event of a supply voltage failure, instead the 
device is shut down. When the supply voltage is 
reapplied, the battery module is charged and the 
device remains off until remote shutdown is 
deactivated.

•  Connected loads are supplied as long as the supply 

voltage is present

6. Setting Options on the Device 

(Fig. 13)

6.1. Buffer Time Setting

Buffer mode can be exited after a prede

fi

ned time 

has elapsed or by external
shutdown (see 6.9).
If the device is to be shut down after a speci

fi

c time

has elapsed, the time can be set via the 
selector switch 

§

 on the front of the device.

When the supply voltage is reapplied, the device
can switch to buffer mode again.

6.2. Battery Module Setting

Before startup, the capacity of the battery module 

used must be set on the device via the selector switch 

$

. When replacing the battery, the selector switch 

must be set to "Service" (see also 6.7).

V   40 

A

Output

+     

 –

Bat.-Mode
Bat.-Charge

Alar

m

Power In OK

Bat.-Mode

Bat.-Charge

Batter

y

rm

Power In

OK

+      –

10

15

5

3

2

1

0,5

20

30

t

max

[min]

Service

3,4

12

7,2

Bat.-Select

[Ah]

$

$

$

$

§

§

§

§

Figure 13

3  14

DC

OK

+  +  

13  14

DC

OK

+  + 

13  14

DC

OK

+  + 

V 0,2A

11

   21

12   13  2

11
Alarm

Bat

.-Mode

Cha

rge

QUI
Ord

e

Inp

u

Op

e

Out

p

AP

P

U

Alarm

Bat.-Mode

Bat.-Cha

rge

3   1

4 DC

OK

+  +  –

Alarm

31  R1  R2

2  23  32  33

21
 Bat.-
Mode

31
 Bat.-
Charge

R1     R2
Remote

OFF

ON

8

8

8

8

Figure 12

Summary of Contents for QUINT-DC-UPS/24DC/40

Page 1: ...g is thus required for maximum system availability Three floating PDT contacts and three LEDs are provided for function monitoring which indicate all the operating states clearly So that relay signali...

Page 2: ...harge current Battery presence check time interval Battery quality test time interval Memory Medium Nominal voltage Nominal capacity Charge current QUINT DC UPS 24DC 40 DC UPS Module U u F Type Order...

Page 3: ...cations Signaling Power In OK Alarm Battery Mode Battery Charge Approvals Standards Electrical equipment of machines Electrical safety of IT equipment Industrial control equipment Shipbuilding Electro...

Page 4: ...ully The QUINT DC UPS is a built in device Installation and startup must only be carried out by qualified personnel The relevant country specific regulations e g VDE DIN must also be observed Before s...

Page 5: ...4 DC OK 24V 0 2A 11 21 12 13 2 11 Alarm Bat M ode Bat C harg e QUIN T D C U PS 24DC 20 Ord er No 28 66 23 9 Input Opera tional Voltage Output 24VDC 22A 22 5 3 0VDC 24VDC 20A APPROVALS Read in sta llat...

Page 6: ...onnected For reliable and safe to touch connections Strip 10 mm 0 39 in from the input and output side connector ends and 7 mm 0 28 in from the signal connector ends To maintain UL approvals use coppe...

Page 7: ...24DC type battery modules The following battery modules are recommended QUINT BAT 24DC 3 4AH Order No 2866349 QUINT BAT 24DC 7 2AH Order No 2866352 QUINT BAT 24DC 12AH Order No 2866365 When using QUIN...

Page 8: ...ce remains off until remote shutdown is deactivated Connected loads are supplied as long as the supply voltage is present 6 Setting Options on the Device Fig 13 6 1 Buffer Time Setting Buffer mode can...

Page 9: ...idling proof 7 2 Signaling Three floating PDT contacts and three indicators are provided for function monitoring xx xx Contact closed 1x Alarm 2x Battery Mode 3x Battery Charge x1 group contact x2 N C...

Reviews: