Description of the Inline controller
6959_en_07
PHOENIX CONTACT
29
Removal
When removing the Inline controller from the DIN rail, proceed as shown in Figure 2-15:
•
Disconnect the power to the station.
•
Remove all the connectors from the Inline controller.
•
If Inline terminals are installed next to the Inline controller (see Figure 2-14):
Figure 2-14
Connectors to be removed if terminals are installed next to the Inline
controller
•
Insert a tool in the base latches of the Inline controller and pull gently upwards
(Figure 2-15, detail B). Pull out the Inline controller from the DIN rail (Detail C1, C2).
Unlike other Inline terminals, the Inline controller is removed by tilting it away from the DIN
rail. This requires the Inline terminal to the right to be removed prior to removing the Inline
controller. The right connector of the Inline controller must also be removed.
Remove the third and fourth connectors to access the right base latch.
It is therefore recommended that all connectors be removed prior to removing the Inline
controller.
•
Lever up the connectors by pressing on the back connector shaft latching
NOTE: Damage to extended double signal connectors due to excessive
bending
If the extended double signal connectors (long connectors) are bent back too far, the front
snap-on mechanism may break.
•
Do not bend the double signal connectors (long connectors) back too far.
•
Remove the connectors (Figure 2-15, detail A2).
•
Remove the following connectors:
–
All connectors of the terminal that is directly connected (A1 to A4)
–
The adjacent connector of the following terminal (B1)
•
Remove the directly adjacent Inline terminal (A).
Observe the information provided in the aforementioned user manuals.
6959B017
1
PLC
RUN
FAIL
RUN / PROG
MRESET
STP
INLINE CONTROL
ILC 350 ETH
Ord.No.: 27 37 203
IL
RDY / RUN
BSA
FAIL
PF
PRG
ETH
LNK
ACT
100
10/100
RESET
1
2
1
2
3
4
1
2
3
4
1
2
US
UM
UL
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I3
I4
I1
I2
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
Q2
Q3
Q4
E
Q1
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I9
I10
I11
I12
1
2
1
2
3
4
1
2
3
4
5
6
5
6
1
2
I5
I6
I7
I8
ILC 350 ETH
A
B
A1... A4
B1
Summary of Contents for ILC 330 Series
Page 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Page 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Page 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Page 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Page 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...