GW PL ETH/…BUS
PHOENIX CONTACT
3433_en_C
4.2.4
Protocol settings
Click the “Protocol Settings” tab to view and configure the protocols available for
communication between the GW PL ETH/…BUS and the host system.
Figure 4-7
“Protocol Settings” page
4.2.4.1
HART IP configuration
HART IP is a connection option that facilitates host-level systems to access and integrate
measurement and device diagnostics information from HART-enabled field devices using
the existing plant networking infrastructure.
The GW PL ... modules will act as a gateway between a HART IP-enabled host station, such
as a HART Server, PDM, PACTware, HCF OPC Server, etc., and a HART device.
When adding the GW PL ETH/…BUS to a HART IP-enabled host system, use the following
configuration:
4.2.4.2
Modbus configuration
When the GW PL ETH/…BUS is used in conjunction with any GW PL HART… expansion
modules, the process variables of a HART device can be accessed. Additionally, digital
inputs and outputs can be monitored and controlled with GW PL DIO4-BUS modules.
Activate Modbus
Navigate to the “Protocol Settings” page in the web-based manager (see
Check the “Modbus TCP” box to activate the Modbus registers on TCP port 502. The
system automatically requests several HART parameters from the field devices and
populates the correct Modbus registers.
Click the “Apply changes” button to save changes.
Modbus and PROFINET cannot be active at the same time.
Network
1
1
TCP is recommended
TCP/UDP
Port
5094
Poll address
0
IP address
Physical LAN port address
The polling address of any HART devices must be set to
0
.
Summary of Contents for GW PL DIO4-BUS
Page 1: ...User manual UM EN GW PL ETH BUS GW PL ETH BUS...
Page 16: ...GW PL ETH BUS 14 46 PHOENIX CONTACT 3433_en_C...
Page 40: ...GW PL ETH BUS 38 46 PHOENIX CONTACT 3433_en_C...
Page 44: ...GW PL ETH BUS 42 46 PHOENIX CONTACT 3433_en_C...
Page 46: ...GW PL ETH BUS 44 46 PHOENIX CONTACT 3433_en_C...