QUINT4-PS/1AC/24DC/10
107100_en_01
PHOENIX CONTACT
5 / 50
4
Technical data
Input data
Unless otherwise stated, all data applies for 25°C
ambient temperature, 230
V
AC input voltage, and nominal
output current (I
N
).
Input voltage range
100 V AC ... 240 V AC -15
% ... +10
%
110 V DC ... 250 V DC -18
% ... +40
%
Electric strength, max.
300 V AC 60 s
Frequency range (f
N
)
50 Hz ... 60 Hz -10 % ... +10 %
Frequency (f
R
) for railway power supply systems
16.7 Hz (acc. to EN 50163)
Railway power supply systems can be operated at 16.7 Hz. Use conditions and technical data on request.
Current draw typ.
3.4 A (100 V AC)
2.8 A (120 V AC)
1.5 A (230 V AC)
1.5 A (240 V AC)
3 A (110 V DC)
1.3 A (250 V DC)
The specified values for current consumption apply for operation in the static boost
(P
N
x
125%).
Discharge current to PE
typical
< 3.5 mA
0.7 mA (264 V AC, 60 Hz)
Mains buffering
≥
35 ms (120 V AC)
≥
35 ms (230 V
AC)
Switch-on time
< 1 s
Typical response time from SLEEP MODE
300 ms
Protective circuit
Transient surge protection Varistor, gas-filled surge arrester
Switch-on current surge limitation typical after 1 ms
18 A
Inrush surge current I
2
t
< 0.7 A
2
s
Input fuse slow-blow, internal
8 A
During the first few microseconds, the current flow into the filter capacitors is excluded.
The SCCR value (short-circuit current rating) of the power supply unit corresponds to the SCCR value of the
backup fuse (see input protection table).
The external backup fuse must be approved for the (AC) supply voltage used and the voltage level.