5.3. Motor Overload Protection
Functions relevant for safety are realized by the hybrid motor starter without any external influences.
Special switching techniques are not required.
The wiring of the load current circuit should be implemented as in the above listed examples. In contrast,
the module current supply, however, can be connected directly to the voltage source without a safety re-
lay PSR. This applies for the control.
5.4. Motor with brake
If a motor with brake (connection in the motor terminal board) is connected, the 400 V AC brake must be
connected to the 2/T1 and 6/T3 connections. A 230 V AC brake must be connected to the 4/T2 connection
and the star point of the motor.
Please note the following:
The motor current monitoring must be increased by the value of the
brake (nominal current of the brake). Configure the relevant setting on the hybrid motor starter
(refer to point 4.3, page 18)!
5.5. Auxiliary relay connection
Auxiliary relay (e.g. PLC RSC 230UC/21, order no.: 2966207) for activating external brakes or
acknowledgements to the PLC must be connected to the "4T2" and "N" connection of the system.
6. Technical data
Type
Order No.
ELR W3-24DC/500AC-2I
2297031
ELR W3-24DC/500AC-9I
2297057
ELR W3-230AC/500AC-2I
2297044
ELR W3-230AC/500AC-9I
2297060
Input data
ELR W3-24DC/...
ELR W3-230AC/...
Rated control supply voltage U
s
acc. to IEC 60947-1 / UL 508
24 V DC
230 V AC (50/60 Hz)
Control supply voltage range
19.2 ... 30 V DC
(32 V DC, max. 1 min.)
85 ... 253 V AC
Control supply voltage
Switching level "Safe off"
< 5 V DC
< 5 V AC
Rated control supply current
as per IEC 60947-1
≤
40 mA
≤
4 mA
Control input L, R:
Switching level "Low"
-3...9.6 V DC
< 44 V AC
Switching level "Safe off"
< 0.5 V DC
< 5 V AC
Switching level "High"
19.2...30 V DC
85...253 V AC
Input current
≤
5 mA
≤
7 mA
Output data
Load side
ELR...-2I
ELR...-9I
Circuit principle
Safety output module with bypass,
three-phase disconnection
Rated operating voltage U
e
acc. to IEC 60947-1
500 V AC;
500 V AC;
Operating voltage range
acc. to IEC 60947-1
acc. to UL 508
42 ... 550 V AC
42 ... 500 V AC
42 ... 550 V AC
42 ... 500 V AC
Load current at 20°C (see 8.2. Derating curve)
0.18...2.4 A
0.18(1.2) ... 9.0 A
Load current at 20°C without safety function and
asymmetry recognition (see 8.2. Derating curve)
0...2.4 A
0 ... 9.0 A
Rated operating current I
e
acc. to IEC 60947-1
AC-51
acc. to IEC 60947-4-3
AC-53a
acc. to IEC 60947-4-3
acc. to UL 508
2.4 A
2.4 A
2.4 A
9 A
6.5 A
6.5 A
Nominal switching capacity
acc. to UL 508
Full Load (power factor = 0.4)
Full Load (power factor = 0.8)
0.9 kW (1.2 HP)
1.7 kW (2.2 HP)
2.3 kW (3.0 HP)
4.6 kW (6.1 HP)