Process, parameter, and diagnostic data
109745_en_01
PHOENIX CONTACT
49 / 66
7.2.2.2
Local programming lock (index 0002
hex
)
This index can be used to read and write the local programming lock. The read or write com
-
mand must be issued to the slot that corresponds to the module position in the system. The
subslot is always “1”.
7.2.2.3
Channel outputs (index 0003
hex
)
This index can be used to switch the channels of a module on and off. The read or write
command must be issued to the slot that corresponds to the module position in the system.
The subslot is always “1”.
Table 7
-
15
Local nominal current programming lock
Byte
offset
Data
type
Data
Access Default setting
0
Byte
0 = channel 1 lock inactive
r/w
0
1 = channel 1 lock active
2 = no change
1
0 = channel 2 lock inactive
1 = channel 2 lock active
2 = no change
2
0 = channel 3 lock inactive
1 = channel 3 lock active
2 = no change
3
0 = channel 4 lock inactive
1 = channel 4 lock active
2 = no change
Table 7
-
16
Channel outputs
Byte
offset
Data
type
Data
Access Default setting
0
Byte
0 = switch off channel 1
r/w
0
1 = switch on channel 1
2 = no change
1
0 = switch off channel 2
1 = switch on channel 2
2 = no change
2
0 = switch off channel 3
1 = switch on channel 3
2 = no change
4
0 = switch off channel 4
1 = switch on channel 4
2 = no change
Summary of Contents for 1110984
Page 1: ...User manual CAPAROC System and installation...
Page 20: ...CAPAROC system 20 66 PHOENIX CONTACT 109745_en_01...
Page 22: ...CAPAROC system 22 66 PHOENIX CONTACT 109745_en_01...
Page 28: ...CAPAROC system 28 66 PHOENIX CONTACT 109745_en_01...
Page 52: ...CAPAROC system 52 66 PHOENIX CONTACT 109745_en_01...
Page 54: ...CAPAROC system 54 66 PHOENIX CONTACT 109745_en_01 Figure 8 1 PC WORX FIRMWARE UPDATER...
Page 67: ......