Configuration and startup
3886_en_A
PHOENIX CONTACT
33
3.9.3
Serial logs
The “Serial Logs” page provides a log of received and transmitted messages on the serial
port. Up to 128 bytes per message and up to 128 messages are logged. This is intended to
help with debugging serial connectivity problems, determining the proper start and end of
transmission bytes, and diagnosing device problems. Click the “Reset Log” button at any
time to clear the log. This page displays the serial messages transmitted and received
during normal operation.
To view serial log statistics:
1.
Click the “Diagnostics” tab.
2.
Click the “Serial Log” tab.
Figure 3-16
“Serial Log” page
The log format is as follows:
Pkt(N):
ddd:hh:mm:ss.mss Rx/Tx>(data)
ddd
: days since last system restart
hh
: hours since last system restart
mm
: minutes since last system restart
ss
: seconds since last system restart
mss:
milliseconds since last system restart
(
data
): Data packet received. For PROFINET IO data, all data bytes are shown in
hexadecimal (xxh) format. For Raw/ASCII and PROFINET/ASCII data, ASCII
characters are displayed as characters. Non-ASCII data is displayed in hexadecimal
(xxh) format