Be aware that all positive connections of CMLsolid 30 controller are common and therefore have  

the same electrical potential. If any grounding is required, always do this on the positive wire.  

The charge controller casing can be grounded by means of an existent dedicated grounding 

post.

REMARK:  

If the device is used in a vehicle which has the battery negative on the chassis, loads 

connected to the regulator must not have an electric connection to the car body. Otherwise the Low 

Voltage Disconnect function and the electronic fuse function of the controller are short circuited.

REMARK:  

Mind   the   recommendations   of   your   battery   manufacturer.   We   strongly   recommend 

connecting a fuse directly to the battery to protect any short circuit at the battery wiring. The fuse 

must correspond to the nominal current of the charge controller: 45 A.

 

Starting up the controller

Self Test

As soon as the controller is supplied with power either from the battery, it starts a self test routine. 

Then the display changes to normal operation.

System Voltage

The controller adjusts itself automatically to 12 V or 24 V system voltage. As soon as the voltage at the  

time of start-up exceeds 18.0 V, the controller assumes a 24 V system.  

If the battery voltage is not 

within the normal operation range at start-up, a status display according  to the section ERROR  

DESCRIPTION occurs.

 

Battery Type

The controller is preset to operate with lead-acid batteries with solid electrolyte (GEL type or AGM 

type). If you intend to use a lead-acid battery with liquid electrolyte, you can adjust the charging  

24

EN

Summary of Contents for CMLsolid 30

Page 1: ...Phocos CMLsolid 30 Solar charge controller Bedienungsanleitung User Manual Manual del usuario Manuel de l utilisateur Manual de Usu rio CID 181815512...

Page 2: ...CONTENTS Bedienungsanleitung User Manual Manual de Instrucciones Guide de l utilisateur Manual do Usu rio 1 19 20 37 38 56 57 75 76 95 96 113...

Page 3: ...kustisches Signal bei Ladezustands nderung Tiefentladeschutz ladezustands oder spannungsgesteuert Ausgang zum ferngesteuerten Ein Ausschalten des Wechselrichters USB Standardanschluss f r das Laden vo...

Page 4: ...und Installationshinweise Bei der Installation oder beim Arbeiten an der PV Anlage bitte immer zuerst die PV Solarmodule vom Laderegler trennen um eventuelle Sch den am Laderegler zu vermeiden Bitte b...

Page 5: ...Batterieladung zu erzielen Der Laderegler erkennt selbstst ndig die Batteriespannung und stellt sich automatisch auf 12 V oder 24 V Betrieb ein Der Laderegler besitzt eine Reihe von Schutz und Anzeige...

Page 6: ...Um spannungsfrei zu arbeiten schlie en Sie bitte die Kabel zuerst an den Regler dann an die Batterie und zuletzt an die PV Module an F r die Last gilt bitte zuerst die Kabel an die Last anschlie en d...

Page 7: ...5 Erdungsklemme Anschluss zum fernsteuern eines Wechselrichters USB Anschluss DE Sicherung...

Page 8: ...nnung versorgt wird f hrt er einen Selbsttest durch Erst dann wechselt die Anzeige in den Normalbetrieb um Systemspannung Der Laderegler stellt sich selbstst ndig auf 12 V oder 24 V Systemspannung ein...

Page 9: ...atlich immer wieder vollst ndig geladen wird Andernfalls wird die Bleibatterie dauerhaft gesch digt Die Vollladung kann vom Laderegler nur dann durchgef hrt werden wenn nicht gleichzeitig zu viel Ener...

Page 10: ...durch den Laderegler signalisiert Ladungsanzeige Solaranlage liefert Strom Solaranlage liefert keinen Strom Gr ne LED leuchtet Gr ne LED leuchtet nicht Ladezustandsanzeige 75 25 75 25 10 3 LEDs AN 2 L...

Page 11: ...lisiert Die Lastabschaltung erfolgt ca 1 Minute nach einer Serie von 25 Signalt nen Lastzustandsanzeige Der Laderegler schaltet bei Tiefentladung und bei berlastung Lastkurzschluss den Lastausgang ab...

Page 12: ...fix geeignet falls Verbraucher direkt an die Batterie angeschlossen sind und der Laderegler nicht den gesamten Laststrom erfassen kann Werkseitig ist der Modus 1 voreingestellt Die Einstellung des Mod...

Page 13: ...Alarm Aus Spannungsgesteuert Fl ssigs ure Batterie Werks einstellung Alarm An Ladezustandsgesteuert GEL VRLA Batterie Schutzfunktionen An den PV Anschl ssen An den Batterie Anschl ssen An den Last Ans...

Page 14: ...muss durch eine Sicherung gesch tzt werden oder sie kann im Falle eines Kurzschlusses dauerhaft besch digt werden 4 200 Nennstrom Abschaltung nach 3 Sekunden Verz gerung WARNUNG Die Kombination versch...

Page 15: ...ichter Zur Steuerung der Phocos Wechselrichter Serie SI 350 SI 700 oder SI 1500 durch die Tiefentladeschutz Funktion LVD des Ladereglers ist eine 6p4c Modularbuchse vorhanden Der Wechselrichter wird b...

Page 16: ...r CMLsolid 30 die Stromaufnahme des Wechselrichters nicht messen kann Fehlerbeschreibung Fehler LED Anzeige Ursache Fehlerbehebung Verbraucher haben keine Energie Batterie ist tiefentladen Rote LED an...

Page 17: ...ochohmig Bitte berpr fen Sie die Batteriezuleitungen Sicherungen und die Batterie Batterie ist nach kurzer Zeit wieder entladen Batterie hat Kapazit t verloren Rote LED leuchtet Batterie austauschen B...

Page 18: ...estrom 30 A Max Laststrom 30 A Spannung Erhaltungsladung 13 8 27 6 V 25 C Spannung Hauptladung 14 4 28 8 V 25 C 0 5 Std t glich Boost Ladung 14 4 28 8 V 25 C 2 Std Aktivierung Batteriespannung 12 3 24...

Page 19: ...ung 50 V Max Batteriespannung 50 V Temperaturkompensation Ladespannung 4 2 mV K per cell Ruhestromaufnahme 10 mA Erdung Positiv Erdung Umgebungstemperatur 40 bis 50 C Max H he 4 000 m NN Batterietyp B...

Page 20: ...Siehe Graph der Ladezustandssteuerung Sicherer Betriebsbereich 18 CMLsolid 30 Sicherer Betriebsbereich Nennlaststrom DE...

Page 21: ...es Batterieherstellers missachtet werden Der Hersteller haftet nicht wenn Reparaturen oder Kundendienst von nicht autorisierten Personen durchgef hrt wurden bei unsachgem sser Gebrauch falscher Instal...

Page 22: ...changes Low voltage disconnect regulated by state of charge or voltage Remote output terminal to switch on off an Inverter Mobile charger for external devices using USB standard connector Max 16 mm2 c...

Page 23: ...the charge controller first to prevent any damages to the charge controller Please verify that all cable wire connections are tightly fastened to the connectors binding posts in order to avoid any bad...

Page 24: ...e Controller and battery must be installed in the same room The controller warms up during operation and should therefore be installed on a non flammable surface only Connect the controller by followi...

Page 25: ...23 Grounding Post Remote Terminal for inverter USB connector EN...

Page 26: ...tly to the battery to protect any short circuit at the battery wiring The fuse must correspond to the nominal current of the charge controller 45 A Starting up the controller Self Test As soon as the...

Page 27: ...with a dry tissue It is important that the battery gets fully charged frequently at least monthly Otherwise the battery will be permanently damaged A battery can only be fully charged if not too much...

Page 28: ...y signaled acoustically Charge display Solar array supplies electricity Solar array does not supply electricity Green LED on Green LED off State of charge display 75 25 75 25 10 3 Yellow LEDs on 2 Yel...

Page 29: ...s are disconnected approx 1 minute after a series of 25 tones Load status display In case of deep discharge or overload short circuit of load the load output is switched off This is indicated by Norma...

Page 30: ...tery protection 2 Voltage controlled Disconnect at 11 0 V 22 0 V fixed setting Appropriate if bypass loads draw current directly from the battery The controller is preset to Mode 1 from the factory Ch...

Page 31: ...trolled Flooded battery Factory setting Alarm on State of charge controlled GEL VRLA battery Safety Features PV terminals Battery terminals Load terminals Reverse polarity Protected Warning Red LED on...

Page 32: ...error conditions may cause damage to the controller Always remove the fault condition before you continue with connecting the controller Auxiliary terminals USB connector USB connector for delivering...

Page 33: ...31 EN...

Page 34: ...use the CMLsolid 30 can t measure the current drawn by the inverter under these setting Error Description Error Display Reason Remedy Loads are not supplied Battery is low Red LED on Load will reconne...

Page 35: ...gh resistance Check battery wires fuses and battery Battery is empty after a short time Battery shows low capacity Red LED on Change battery Battery is not being charged during the day Solar array fau...

Page 36: ...x load current 30 A Float charge 13 8 27 6 V 25 C Main charge 14 4 28 8 V 25 C 0 5 h daily Boost charge 14 4 28 8 V 25 C 2 h Activation battery voltage 12 3 24 6 V Equalization 14 8 29 6 V 25 C 2 h Ac...

Page 37: ...perature compensation Charge voltage 4 2 mV K per cell Self consumption idle 10 mA Grounding Positive grounding Ambient temperature 40 to 50 C Max altitude 4 000 m above sea level Battery type Lead ac...

Page 38: ...Please see graph of SOA Safe Operating Area 36 EN...

Page 39: ...ations of the battery manufacturer are neglected The manufacturer shall not be liable if there has been service or repair carried out by any unauthorized person unusual use wrong installation or bad s...

Page 40: ...taje de la bateria Terminal remoto de salida para el encendido apagado del inversor Cargador m vil para equipos externos mediante conector USB est ndar Terminales m x 16 mm2 Protecci n electr nica com...

Page 41: ...r de carga para evitar da os en el controlador de carga Verifique que todas las conexiones de los cables est n bien ancladas a los conectores puertos de conexi n para evitar la existencia de cables su...

Page 42: ...ador y la bater a deben instalarse en la misma habitaci n El controlador se calienta durante su funcionamiento y por lo tanto ha de instalarse nicamente sobre una superficie no inflamable Para evitar...

Page 43: ...41 Terminal de control remoto del inversor Conector USB Posici n de toma de tierra ES Fusible...

Page 44: ...nes de Desconexi n por Bajo Voltaje y de fusible electr nico OBSERVACI N Siga las recomendaciones del fabricante de su bater a Recomendamos encarecidamente conectar un fusible directamente a la bater...

Page 45: ...evisi n Retire el polvo con un pa o seco Es importante que la bater a se cargue completamente con frecuencia al menos una vez al mes De otro modo la bater a estar permanentemente da ada Una bater a so...

Page 46: ...Visualizaci n de la carga El m dulo solar suministra electricidad El m dulo solar no suministra electricidad LED verde encendido LED verde apagado 44 Visualizaci n del estado de la carga Visualizaci n...

Page 47: ...llo parpadea El porcentaje indica la relaci n entre la energ a disponible de una bater a cargada completamente y el m nimo indicado con Desconexi n por Bajo Voltaje Se ales ac sticas El descenso del e...

Page 48: ...ador tiene 2 modos diferentes para proteger la bater a de una descarga profunda 1 Estado de la carga controlado Desconecta de 11 4 V 22 8 V a corriente de carga nominal hasta 11 9 V 23 8 V a falta de...

Page 49: ...P situados en el lateral izquierdo del controlador Interruptor DIP BUZ LVD GEL Funci n Se al de alarma ac stica Funci n de desconexi n por bajo voltaje Tipo de bater a Ajuste activado Alarma activada...

Page 50: ...ma de 15 5 31 0 V Subvoltaje Se apaga Sobrecalentamiento Reduce la corriente de carga si se produce un sobrecalentamiento y desconecta el consumo si la temperatura es demasiado alta 1 El controlador s...

Page 51: ...l consumo negativo Terminal de control remoto del inversor Disponible un conector modular 6p4c tipo RJ para controlar cualquier inversor de la serie SI de inversores Phocos SI 350 SI 700 o SI 1500 en...

Page 52: ...50 ES...

Page 53: ...atura LED rojo parpadea Desconectar todos los consumos Eliminar cortocircuito El controlador activar autom ticamente el consumo despu s de m x 1 minuto El voltaje de la bater a es demasiado alto 15 5...

Page 54: ...encendido Cambie la bater a La bater a no se carga durante el d a M dulo solar defectuoso o polaridad equivocada LED verde apagado Corrija la conexi n defectuosa polaridad inversa Bater a con polarid...

Page 55: ...sumo m x 30 A Carga de flotaci n 13 8 27 6 V 25 C Carga principal 14 4 28 8 V 25 C 0 5 h diariamente Carga r pida 14 4 28 8 V 25 C 2 h Activaci n voltaje bater a 12 3 24 6 V Ecualizaci n 14 8 29 6 V 2...

Page 56: ...n de temperatura Voltage carga 4 2 mV K por c lula Autoconsumo idle 10 mA Toma de tierra Positive aterrisado Temperatura ambiente 40 a 50 C Altitud m x 4 000 m sobre el nivel del mar Tipo de bater a P...

Page 57: ...V ase gr fica de SOA Safe Operating Area 55 Corriente consumo nominal ES...

Page 58: ...an las recomendaciones del fabricante de la bater a El fabricante no se hace responsable si se han llevado a cabo reparaciones a cargo de personal no autorizado o por un uso inusual una mala instalaci...

Page 59: ...ge soit par la tension Conecteurs de contr le distance pour la mise en marche arr t de l onduleur Chargeur portable pour les p riph riques externes quip s d un port USB standard Bornes de raccordement...

Page 60: ...es panneaux photovolta ques du r gulateur de charge afin d viter tout endommagement du r gulateur Veuillez galement v rifier que tous les raccordements de c bles et de fils sont suffisamment serr s au...

Page 61: ...il directs En aucun cas il ne doit tre install dans un endroit humide tel qu une salle de bain Le r gulateur mesure la temp rature ambiante afin d adapter la tension de charge La batterie et le r gula...

Page 62: ...me potentiel lectrique Si une mise terre est requise elle doit toujours tre effectu e sur les fils positifs Une borne de mise la terre pr vue cet effet permet de relier le bo tier du r gulateur de cha...

Page 63: ...61 Borne de mise la terre Borne de contr le distance de l onduleur Port USB FR Fusible...

Page 64: ...de batterie Le r gulateur est pr r gl pour fonctionner avec des batteries au plomb comportant des lectrolytes solides de type GEL ou AGM Si vous avez l intention d utiliser une batterie au plomb avec...

Page 65: ...tionnement normal Le r gulateur de charge est quip de 5 LED et d un dispositif d alerte sonore Affichage de la charge En fonctionnement normal le r gulateur de charge indique le niveau de charge de la...

Page 66: ...s d lectricit LED verte allum e LED verte teinte Affichage de l tat de charge 75 25 75 25 10 3 LED jaunes allum es 2 LED jaunes allum es 1 LED jaune allum e 1 LED jaune clignote Les pourcentages corre...

Page 67: ...te apr s une s rie de 25 signaux sonores Affichage du niveau de charge En cas de d charge profonde ou de surcharge court circuit de la charge la sortie de la charge est automatiquement d connect e Cec...

Page 68: ...en la batterie 2 Tension r gul e d connexion 11 5 V 23 0 V param tres pr r gl s Ce mode est appropri si des charges d riv es consomment directement du courant de la batterie Le r gulateur est pr r gl...

Page 69: ...ion v rifi e Batterie ouverte Param trage d usine Alarme allum e tat de charge v rifi GEL batterie VRLA Dispositifs de s curit Bornes des panneaux solaires Bornes de batterie Bornes des charges Polari...

Page 70: ...que contre les surintensit s limit e 400 A 3 La batterie doit tre prot g e par un fusible pour ne pas tre d finitivement endommag e en cas de court circuit 4 200 du courant nominal d connexion au bout...

Page 71: ...urant AVERTISSEMENT Ne branchez pas le dispositif de rechargement sur d autres bornes Le contact n gatif du port USB est connect la borne n gative de la charge Bornes de contr le distance de l onduleu...

Page 72: ...bles reli s un protocole modbus ou un t l phone connexion 1 1 Branchez l onduleur directement sur la batterie Dans ce cas la fonction SOC ne peut pas tre utilis e car le r gulateur CMLsolid 30 ne peut...

Page 73: ...la batterie les fusibles et la batterie La batterie se d charge apr s une br ve p riode La capacit de la batterie est faible LED rouge allum e Changer la batterie La batterie ne se recharge pas au co...

Page 74: ...Courant de charge maximum 30 A Charge de maintien 13 8 27 6 V 25 C Charge principale 14 4 28 8 V 25 C 0 5 h par jour Charge forc e 14 4 V 28 8 V 25 C 2h Activation tension de la batterie 12 3 V 24 6 V...

Page 75: ...la temp rature tension de charge 4 2 mV K par cellule Autoconsommation au ralenti 10 mA Mise la terre Mise la terre positive Temp rature ambiante 40 50 C Altitude maximale 4000 m au dessus du niveau d...

Page 76: ...Veuillez consulter le graphique de l aire de s curit SOA 74 Courant nominele charge FR...

Page 77: ...n ont pas t respect es Le fabricant ne peut tre tenu pour responsable si des op rations de maintenance ou de r paration ont t effectu es par des personnes non autoris es des utilisations inhabituelle...

Page 78: ...o por baixa tens o LVD controlada por estado de carga ou por tens o Terminal de sa da remoto para ativar desativar um inversor Controlador de carga para dispositivos eletr nicos port teis utilizando c...

Page 79: ...o Antes de instalar ou colocar o sistema fotovoltaico em funcionamento desconecte os pain is FV solares do controlador a fim de prevenir qualquer dano ao controlador de carga Verifique se todos os con...

Page 80: ...gado da luz do sol Nunca instale o controlador em recintos midos como banheiros por exemplo O controlador mede a temperatura ambiente para determinar a tens o de carga da bateria Tanto o controlador c...

Page 81: ...ste fim O gabinete do controlador de charga podera ser aterrado atwaves de um terminal dedicado disponivel para esta fun o OBSERVA ES Caso o controlador de carga seja utilizado em ve culo cujo polo ne...

Page 82: ...80 Terminal para aterramento Terminal Contato para controle de inversores Conector USB PO Fus vel...

Page 83: ...obilizado GEL ou AGM Caso seja desejado utilizar baterias de chumbo cida com eletr lito l quido as caracter sticas de carga poder o ser ajustadas vide Configura es Neste caso o processo de carga ser a...

Page 84: ...r ac stico Gera o Durante opera o normal o controlador mostra o estado de carga da bateria e da energia recebida dos pain is solares Qualquer altera o no estado de carga SOC para uma condi o cr tica s...

Page 85: ...10 3 LEDs amarelos ligados 2 LEDs amarelos ligados 1 LED amarelo ligado 1 LED amarelo piscando Percentagem correspondente energia dispon vel em rela o bateria completamente carregada at chegar ao est...

Page 86: ...ada Isto sinalizado da seguinte forma Opera o normal Desconex o baixa tens o Sobrecarga ou curto circuito terminal carga LED vermelho desligado LED vermelho ligado LED vermelho piscando Fun o Desconex...

Page 87: ...do diretamente bateria O controlador est pr ajustado de f brica no modo 1 Para alterar esta configura o vide descri o abaixo Configura es O controlador de cargas pode tamb m ser configurado para condi...

Page 88: ...o bateria Eletr lito liquido Progresso de carga Ligado Estado de carga GEL bateria VRLA Fun es de seguran a Terminais painel solar Terminais bateria Terminais consuidor Polaridade inversa Prote o ati...

Page 89: ...entemente danificado por curto circuito 4 Corrente nominal 200 desconecta com 3 s de retardo Cuidado Uma combina o de diferentes falhas poder danificar o controlador Elimine sempre qualquer condi o de...

Page 90: ...hocos Um conector modular tipo 6p4c est dispon vel para controlar qualquer inversor da s rie Phocos SI 350 SI 700 ou SI 1500 na fun o desconex o por baixa tens o LVD do controlador de carga O inversor...

Page 91: ...nte com bateria A fun o SOC Estado de carga n o devera ser utilizada neste caso pois o CMLsolid30 n o mede o n vel de corrente demandada pelo inversor Sinaliza es de falha Sinaliza o LED Causa Solu o...

Page 92: ...nectar imediatamente caso contrario controlador est danificado Condutores ou fus veis da bateria est o danificados bateria com resist ncia interna elevada Verifique os condutores e fus veis da bateria...

Page 93: ...de carga Painel solar defeituoso ou polaridade invertida LED verde desligado Remova a conex o invertida inverta a polaridade Polaridade incorreta da bateria Bateria est conectada com polaridade invers...

Page 94: ...3 8 27 6 V 25 C N vel de tens o carga principal 14 4 28 8 V 25 C 0 5 h diariamente N vel de tens o carga r pida 14 4 28 8 V 25 C 2 h N vel de tens o conex o do consumidor Tens o da bateria 12 3 24 6 V...

Page 95: ...ns o m xima de bateria 50 V Compensa o de temperatura Tens o de carga 4 2 mV K por c lula da bateria Autoconsumo repouso 10 mA Condutor terra Positivo aterrado Baixa de temperatura armazenagem 40 50 C...

Page 96: ...Vide gr fico da SOA rea de prote o segura 94 Corrente nominal consumidor PO...

Page 97: ...das recomenda es feitas pelo fabricante da bateria O fabricante n o se responsabiliza pelos servi os ou reparos efetuados por pessoas n o autorizadas uso indevido instala o incorreta ou mal desempenh...

Page 98: ...CMLsolid 30 USB MP3 16 CMLsolid 30 0 5m GEL AGM 12 24 V 96 CH...

Page 99: ...1 5 CE CE 97 CH...

Page 100: ...12 V 24 V 1 2 3 10 mm2 98 CH...

Page 101: ...99 USB CH...

Page 102: ...CMLsolid 30 1 5 45A 12 V 24 V 18 V 24 V 100 CH...

Page 103: ...5 LED 101 CH...

Page 104: ...LED LED 75 25 75 25 10 3 LED 2 LED 1 LED 1 LED 102 CH...

Page 105: ...25 1 LED LED LED 103 CH...

Page 106: ...CML 1 SOC 11 4 22 8 V 11 9 23 8 V 2 LVD 11 0 22 0 V 1 104 CH...

Page 107: ...DIP BUZ LVD GEL LED 1 1 2 3 4 50 V 50 V 15 5 31 0V 105 CH...

Page 108: ...1 2 400 A 3 4 200 3 s USB USB 5 V 800 mA USB RJ11 6p4c SI 106 CH...

Page 109: ...CMLsolid 30 1 1 SOC LVD 107 CH...

Page 110: ...LED LED 15 5 31 0 V 108 CH...

Page 111: ...LED LED LED 109 CH...

Page 112: ...12V 24 V CMLsolid 30 12 24 V 30 A 30 A 13 8 27 6 V 25 C 14 4 28 8 V 25 C 0 5 h 14 4 28 8 V 25 C 2 h 12 3 24 6 V 14 8 29 6 V 25 C 2 h 12 1 24 2 V 30 15 5 31 0 V 11 4 11 9 22 8 23 8 V 11 0 22 0 V 110 CH...

Page 113: ...12 8 25 6 V 10 5 21 0 V 50 V 50 V 4 2 mV K per cell 10 mA 40 50 C 4 000 AGM WXHXD 140 x 90 x 40 mm 420 g 16 mm IP20 111 CH...

Page 114: ...112 CH...

Page 115: ...20130624 Phocos AG Germany www phocos com 113 ISO9001 RoHS CH...

Reviews: