“Warn” or “Fault” (middle and right, respectively) LED indicator is on or flickers: inverter is powered on, but system 
fault occurred. Refer to section 7.3 to check the fault code in LCD display, stop the inverter as per section 6.3, and rule 
out faults according to chapter 9. After all the faults are removed, repeat the operations in chapter 6. 

 

Stopping Operation 

When it is necessary to carry out power-off maintenance, inspection and fault elimination on the inverter, stop the 
inverter according to the following steps: 

1.

 

Disconnect the breaker on inverter public grid AC side. 

2.

 

Disconnect the integrated DC switch of the inverter. 

3.

 

Disconnect the breaker switch on PV string DC input side. 

4.

 

Wait for at least 5 minutes until the internal components of the inverter are fully discharged. The inverter has 
now stopped operation. 

 

Maintenance 

In a solar PV grid-connected power generation system, PSW-G series grid-connected solar inverters can realize grid-
connected power generation and stop/start operations automatically day and night in all seasons. In order to 
safeguard and prolong the service life of the inverter, it is necessary to carry out maintenance and inspection on the 
inverter besides using the inverter strictly according to this manual. 
 

Regular Maintenance 

Task 

Method 

Maintenance Cycle 

Store the 
operation 
data 

Use real-time monitoring software to read inverter running data, regularly 
back up all inverter running data and stats. Check the monitoring software 
and inverter LCD screen to make sure the parameters are set correctly.   

Once each quarter 

Check 
inverter 
operation 
status 

Check to make sure the inverter installation is solid, no damage or 
deformation. When inverter running, check to make sure the sound and 
variables are normal. When inverter running, use thermal imager to check 
whether the case cooling is normal. 

Every six months 

Clean the 
inverter 

Check the ambient humidity and dust around inverter, clean the inverter 
when necessary. See Section “6.4 Maintenance” 

 “Cleaning”. 

Every six months 

Check 
electrical 
connection 

Check whether system cable connection and inverter terminal block are 
loosened, if yes, secure them again in the manner specified in section 4. 
Check whether the cable is damaged, and whether the cable skin touched by 
the metal surface is cut. 

Every six months 

Check the 
security 
features 

Check the inverter LCD and stop function of the system. Simulate stop 
operation and check the stop signal communication. Check the warning 
marks and replace them if necessary. 

Every six months 

 

Cleaning 

The cleaning procedure is as follows: 

1.

 

Disconnect the input and output switches. 

2.

 

Wait ten minutes. 

3.

 

Use a soft brush or a vacuum cleaner to clean the surface and the inlet and outlet of the inverter. 

4.

 

Repeat Section “6.1 Inspection before Operation”. 

5.

 

Restart the inverter. 

 

 

Summary of Contents for Any-Grid Series

Page 1: ...Pure Sine Wave Grid Inverter with MPPT Solar Charge Controller PSW G 1KW 1P PSW G 2KW 1P PSW G 3KW 1P PSW G 4KW 1P PSW G 5KW 1P User and Installation Manual English www phocos com...

Page 2: ...tion 8 Before Installation 9 Mechanical Installation 11 Electrical Installation 13 6 0 Operation 16 Inspection before Operation 16 Grid Tied Operation 16 Stopping Operation 17 Maintenance 17 7 0 Displ...

Page 3: ...ng installation operation and maintenance Incorrect use or misuse may result in Injury to the life and personal safety of the operator or other people Damage to the inverter or other property belongin...

Page 4: ...nical personnel who can perform installation wiring commissioning maintenance troubleshooting and replacement of the PSW G series grid tied solar inverters must meet the following requirements Operato...

Page 5: ...ant personnel from entering the maintenance area during maintenance temporary warning labels must be placed to warn non professionals to enter or use fence for isolation Firstly disconnect all power s...

Page 6: ...soidal AC energy which has the same frequency and phase with the public grid by grid tied solar inverters and then be fed to the grid PSW G series grid tied solar inverters are only applied in solar g...

Page 7: ...DC switch On Off of the DC input 4 DC input port For the connection of solar modules 5 AC terminal For the connection of AC output 6 Communication port RS485 and EXT communication port 7 Cooling chamb...

Page 8: ...SW G 2KW 1P 2000 Single phase grid tied solar inverter PSW G 3KW 1P 3000 Single phase grid tied solar inverter PSW G 4KW 1P 4000 Single phase grid tied solar inverter PSW G 5KW 1P 5000 Note For techni...

Page 9: ...chemically corrosive substances that may corrode the inverter Periodic inspections are required If damages are found by worms and rats or packages are found to be damaged the packaging materials must...

Page 10: ...7 Inverter packing list No Name Quantity 1 Inverter 1 pc 2 Installation bracket 1 pc 3 User and installation manual 1 pc 4 Assembling bolt M5x20 2 pcs 5 Expansion bolts M6x60 3 kW inverter nominal pow...

Page 11: ...ion and removal from the mounting surface and air convection Refer to Figure 8 4 The ambient temperature of installation should be 25 C 60 C 5 The installation site should be away from electronic devi...

Page 12: ...rs or fuses on the DC input side and AC output side of the inverter Nominal Inverter Power DC Input AC Output Recommended DC breaker Recommended AC breaker 1 kW DC500V C10A 2P AC240V C10A 2P 2 kW DC50...

Page 13: ...position on the wall Mark the punching position according to the fixing hole Drill holes 70 mm deep and install the expansion screw Fix the bracket on the expansion bolt according to Figure 12 Ensure...

Page 14: ...ion may cause damage to the device physical injuries or even death during system operation All the electrical installation must conform to the national and local electrical safety regulations Ensure a...

Page 15: ...propriate position of the connector crimp the MC4 DC terminal of the inverter and tighten the nut with a torque of 2 5 3 Nm The wiring of negative pole is the same as that of the positive pole Ensure...

Page 16: ...6 AC connection of single phase inverter AC connection steps 1 Before connecting the single phase AC grid cable to the inverter take lightning and short circuit protection measures in accordance with...

Page 17: ...he installation site In order to ensure a safe normal and stable operation of the PV power generation system all the newly installed renovated and repaired PV grid connected power generation system an...

Page 18: ...nce Cycle Store the operation data Use real time monitoring software to read inverter running data regularly back up all inverter running data and stats Check the monitoring software and inverter LCD...

Page 19: ...ion Run Warn Fault Green indicator blinks in every 0 25 s others off Power on and ready for self inspection Power generation Run Warn Fault Green indicator on others off Grid tied power generation Run...

Page 20: ...n the LCD screen The background illumination of LCD screen will go out to save power if there is not button operation within 15 seconds But it can be activated by pressing any button Press ENTER to en...

Page 21: ...grid connected power generation alarm fault OFF state 4 Dynamic fault code and menu entrance When the state display area displays alarm or fault the dynamic fault code area will display corresponding...

Page 22: ...atistical menu Menu Entry Details Lifetime Total operation time total power produced total power saved total CO2 reduction in lifetime Time statistics Total power produced total power saved peak power...

Page 23: ...www phocos com 22 P a g e LCD Menus...

Page 24: ...ess ENT to save the edition and press ESC to exit User Password Enter into the interface and edit the data through UP or DOWN And then press ENTER again to go to the next digit After editing the four...

Page 25: ...ENTER to save and press ESC to exit Setup Mode The DC input mode includes independent and parallel independent mode means the MPPTs A and B track independently of each other if there are two MPPTs pa...

Page 26: ...y LmtPower this function is only valid when the P Lmt Mode is manual the percentage is that of the rated power and the setting range is from 10 to 100 Power factor includes normal model default value...

Page 27: ...ER to confirm Run Param There are 2 protections under G83 G59 UK and PEA Thailand standards and there is only one protection under other grid tied standards Set ACUV Volt ACUV time and others under th...

Page 28: ...www phocos com 27 P a g e System Information Press UP and DOWN in the main interface to select System Information and then press ENTER to view the parameters which is shown in Figure 24...

Page 29: ...25 Figure 25 System version Faults Press UP and DOWN in the main interface to review the fault history and then press ENTER to view the sub menu which is shown in Figure 26 Figure 26 Fault informatio...

Page 30: ...ore to the factory setting and save all history operation records Restore to factory Restore to factory to clear all setting parameters and history operation records through the panel and restore to t...

Page 31: ...CD screen MENU Main Menu Setup Setup Menu Country Country Figure 29 Changing country setting The grid certification which has been set can be queried as follows LCD screen MENU Main Menu System Info S...

Page 32: ...485 S ports The RS485 M ports can communicate with private computers smart phones and so on The system monitoring solution is shown in Figure 31 Figure 31 Monitoring system of inverter Standard Commun...

Page 33: ...lude Ethernet WiFi GPRS and ENET which also need corresponding communication parts and components as shown in the table below sold separately All operation parameters of the inverter are output from p...

Page 34: ...ult Voltage boost fault of the inverter E005 Grid OC AC overcurrent Internal AC overcurrent E006 OTP Over temperature Internal over temperature E007 Riso Low Low isolation impedance Low isolation impe...

Page 35: ...t be resolved please contact your supplier and provide following information Model of the inverter Serial number of the inverter System version o Version 1 o Version 2 MCU software version Fault code...

Page 36: ...purpose Repair and replacement are your sole remedies and the company shall not be liable for damages whether direct incidental and special or consequential even if caused by negligence Further detail...

Reviews: