background image

Skyway

SKS2GPK2FT

Page 2 of 2

2' x 2' Recessed Fluorescent, Tri-Lens Frame

Static or Air Supply/Return, 2 Lamp Twin Tube T5

Ordering Information

Explanation of Catalog Number. Example: SKS2GPK2FTUNVIB

Options/Accessories

Fusing:

Internal fast blow fusing: SUFFIX:

A

.

Internal slow blow fusing: SUFFIX:

C

.

Drywall Kit:

Order Catalog Number:

FK92X2

.

Electrical Wiring Options:

Consult factory.

For motion or light sensor:

See Folio OA20-10 and OA20-30.

Specifications

Performance:

In an installation of 2 lamp 40W luminaires in a room cavity ratio of 1,

with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .81.
To reduce glare the average brightness at 65° shall not exceed 3418 candelas per
square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall
not be less than 68.5%.

Air Handling: (SKA only)

side air passages for air supply or air return. Supply air is

discharged vertically. Optional side closure strips. Air return is also provided through the
lamp compartment through fixture body ends.

Materials

:

Chassis parts

are die-formed code gauge cold rolled steel. Housing has side rails

hemmed over and housing ends turned-in for safe handling.

Specifications (continuned)

Finish

:

Chassis exterior

–black baked polyester enamel.

Cavity

–white baked polyester

enamel minimum 86% reflectance. Rust preventative undercoating.

Reflectors-

95%

reflective white powder coated.

Lens:

Proprietary high quailty frost white acrylic and clear conical prism lens assembly.

Electrical:

Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is

within 3" of ballast, use wire suitable for at least 90°.

Labels:

UL Listed for damp locations. I.B.E.W./UL and ULc Listed.

This product may have a mercury containing lamp. Manage in accord with Disposal
Laws. See: www.lamprecycle.org

Options:

Add appropriate
suffix to catalog

no., ie: (A)

Skyway

Recessed

Fluorescent

Body Style:

S

= Static

A

= Air

2

Fixture

Width

Ceiling Type:

G

= Standard

Grid

T

= Slot Grid

P

Side Lens:

P

= Frost White

Acrylic Lens

FT

Lamp:

(By Others)

FT

= Twin Tube T5

K

Center Lens:
K

= Pattern 19

.156 Virgin

Acyrlic Lens

2

Lamp

Quantity

2

=2 Lamp

Ballast Type:

<

20THD

<

10THD

2 Lamp Elec. TT5 (40 Watt)

SB*

I

B*

*

2 Lamp Elec. TT5 (40 Watt)

PR†

2 Lamp Elec. TT5 (50 Watt)

BE

*

2 Lamp Elec. TT5 (55 Watt)

BF

*

LOL Dimming TT5

PB

*Instant Start Standard.
Other dimming options. Consult factory.

NOTE:

For TT5 40W

UNV

, you must use PR Ballast Code.

†Program Rapid Start

Voltage:

120, 277 or

UNV

=120-277

0.0

45.0

90.0

FLUX

0

2055

2055

2055

5

2040

2040

2043

194

15

1937

1957

1986

554

25

1747

1826

1932

846

35

1482

1672

1859

1041

45

1131

1248

1276

956

55

736

808

772

703

65

420

459

435

454

75

218

222

207

240

85

48

66

40

65

90

0

0

0

Model No. SKS2GPK2FTUNVIB (40 watt lamp)

LER = FP - 64.3

IW - 69.1

BF - 0.88

Comparative yearly lighting energy cost per

1000 lumens = $3.73

Report Number: G2008206
Catalog Number: SKS2GPK2FTUNVIB
Lamps: (2) PL-L40/835/RS/IS
Luminaire: Skyway Recessed 2' x 2' fixture

prismatic acrylic lens assembly

.

Ballast: ICN-2TTP40-SC
Report is based on 3300 Lumens per lamp.

Efficiency: 76.5%

CIE Type-Direct-Indirect
Plane:

0-Deg

90-Deg

Spacing Criteria:

1.2

1.4

Shielding Angles:

90

90

Plane:

0-Deg

90-Deg

Luminous Length:

21.600

21.600

CANDELA DISTRIBUTION

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG.

45-DEG.

90-DEG.

45

5312.

5861.

5993.

55

4261.

4678.

4470.

65

3300.

3607.

3418.

75

2797.

2849.

2656.

85

1829.

2515.

1524.

LUMINANCE DATA IN CANDELA/SQ. METER

COEFFICIENTS OF UTILIZATION –

ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20

0

RC

80

50

30

RW 70 50 30 50 30 10 50 30 10

0

1 84 81 78 76 74 72 73 71 69

0

2 77 71 66 67 63 60 65 62 59

0

3 71 63 57 60 55 51 58 54 51

0

4 65 56 50 54 48 44 52 47 44

0

5 60 51 44 48 43 39 47 42 38

0

6 56 46 39 44 38 34 43 38 34

0

7 52 42 35 40 35 31 39 34 30

0

8 48 38 32 37 31 27 36 31 27

0

9 45 35 29 34 29 25 33 28 25

10 42 33 27 31 26 23 31 26 22

ZONE

LUMENS % LAMP

% FIXT

0

0-

0

30

1593

24.1

31.5

0

0-

0

40

2635

39.9

52.2

0

0-

0

60

4294

65.1

85.0

0

0-

0

90

5052

76.5

100.0

90-180

000

0

0.0

00

0.0

0

0-180

5052

76.5

100.0

ZONAL LUMEN SUMMARY

SK

Standard Skyway

SY

For NYC Code – I.B.E.W. Manufactured

Job Information

Type:

For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595

08/10

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group

Section 5/Folio MA12-10 Rev. B

Reviews: