Self Diagnostic System Operation – Emergency Light or EXIT Sign Products 

 

Normal Power Up Sequence 
 
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute 
a “Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up 
Quick Test” these will be evident by a flashing red LED indicator.  If the audible diagnostic option has been ordered, the 
flashing red LED will be accompanied by a simultaneous beeping tone. 

(Note: A continuous rapid alternating Red/Green 

flash with rapid beeping tone indicates incorrect voltage applied to input lead. TURN OFF POWER IMMEDIATELY!) 

 
Emergency Operation 
Emergency operation occurs when AC power fails. The product remains in emergency operation until AC power is 
restored or battery capacity is depleted. During emergency operation both red and green LED indicators are disabled. 
 
User Interface 
 

Green LED indicator

 

 

Slow Flash/Continuous ON = AC power present; normal operating condition 

 

Rapid Flash = product performing an automatic or manually initiated diagnostic test 

Red LED indicator 

 

Single Flash = battery fault 

 

Two Flashes = lamp failure (light bar failure – EXIT signs) 

 

Three Flashes = charger fault 

 

Four Flashes = transfer fault 

(If more than one fault condition is present simultaneously, the red LED will flash the indication pattern for each 
fault independently then repeat the cycle.) 
 

Pushbutton Test Switch

 

 

Long Press (longer than 0.5sec) transfers product to emergency operation during time the button is 
pressed. 

 

Short Press initiates self diagnostic activities as follows: 

 

One Press cancels diagnostic test presently running. 

 

Two Presses starts a one minute diagnostic test. 

 

Three Presses starts a 90 minute diagnostic test. 

 

Four Presses conducts a lamp load calibration (emergency light products only). 

 

Seven Presses initiates a system reset. 

(Note: the microprocessor will allow up to seven, one minute diagnostic tests within the first 24 hours of 
operation. Allow 24 hours of charging before performing any long duration testing.) 
 

Buzzer

 (optional)– Sounds in unison with the flashing red LED if a fault condition is present. Buzzer may be 

silenced for up to 196 hours by a short press of either the test switch or the optional IR remote control device 
“silence” button. Correcting fault condition will cancel fault notification. Lamp failure indication requires a 
manually activated diagnostic test after lamp replacement to cancel notification. 
 

IR Remote Control 

(optional)- is a hand held device that allows remote activation of diagnostic testing and 

silencing of the optional buzzer during fault conditions. 

Summary of Contents for SC Series

Page 1: ...d be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters Use caution when servicin...

Page 2: ...P 2 for Wall Mounting Remove keyhole knockouts for securing the backplate to the mounting surface as necessary Keyhole knockout patterns are provided for 3 1 2 and 4 octagonal boxes single gang boxes and widely spaced keyhole knockouts are provided for use with wall anchors not provided A large central knockout is provided for AC service entry or the conduit entry knockout in the upper surface of ...

Page 3: ...emove one of the two knockouts that are found in the side or top of the backplate or extra stencil face use the extra stencil face for double sided EXIT installations single face installation using a blank backplate is shown above Place the resulting opening in the backplate or stencil over the threaded nipple on the canopy and thread on the jamb nut A four pole connector assembly is provided on t...

Page 4: ... the canopy bracket Thread the jamb nut onto the end of the pendant stem followed by the pendant adapter Remove the center knockout that is found in the top of the backplate or extra stencil face use the extra stencil face for double sided EXIT installations single face installation using the backplate is shown above Place the resulting opening in the backplate or stencil over the threaded nipple ...

Page 5: ...maining four Torx screws thru the corners of the stencil electronics assembly to finish the installation if vandal resistant shield option has been ordered use the Torx screws to also attach the clear shield to each stencil face Recessed Mounting Option Make a 13 7 8 x 9 1 2 cutout in the mounting surface Secure the backbox with nails or screws to the stud structure Route flex conduit into the upp...

Page 6: ...lluminates and EXIT is illuminated 2 Press the test switch pilot lamp and verify that the pilot lamp turns off and EXIT remains illuminated 3 Leave AC connected for a minimum of 24 hours before performing any extended testing Full recharge of batteries may require one full week Notes 1 This equipment is provided with a lockout feature whereby connecting battery leads prior to energizing AC power w...

Page 7: ...manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec t...

Page 8: ...ion 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053550 February 2016 ...

Reviews: