shield and place it over the backbox and EXIT sign assembly.  Place sheetmetal trim ring over the clear 
plastic shield and secure both to the backbox using the supplied tamperproof Torx screws. 
 
 

 

 
 

OPERATING INSTRUCTIONS 

 

(NON-DIAGNOSTICS EQUIPPED UNITS) 

(FOR SELF-DIAGNOSTICS EQUIPPED UNITS, SEE NEXT 

PAGE) 

1.

 

Energize AC power to the equipment and check that the test switch/pilot lamp illuminates and 
EXIT is illuminated. 

2.

 

Press the test switch/pilot lamp and verify that the pilot lamp turns off and EXIT remains 
illuminated. 

3.

 

Leave AC connected for a minimum of 24 hours before performing any extended testing.  Full 
recharge of batteries may require one full week. 

Notes: 

1.

 

This equipment is provided with a lockout feature whereby connecting battery leads prior to 
energizing AC power will not turn on the EXIT.  After AC power is energized, the EXIT will 
illuminate upon AC power failure. 

2.

 

This equipment is provided with a low battery disconnect feature which prevents full discharge 
of the batteries.  If the building is to be unoccupied for an extended period of time and AC power 
is shut off, the batteries should be disconnected from the charger to prevent damage. 

3.

 

The batteries provided in this equipment are sealed and require no maintenance 

 

Summary of Contents for SC Series

Page 1: ...d be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters Use caution when servicin...

Page 2: ...P 2 for Wall Mounting Remove keyhole knockouts for securing the backplate to the mounting surface as necessary Keyhole knockout patterns are provided for 3 1 2 and 4 octagonal boxes single gang boxes and widely spaced keyhole knockouts are provided for use with wall anchors not provided A large central knockout is provided for AC service entry or the conduit entry knockout in the upper surface of ...

Page 3: ...emove one of the two knockouts that are found in the side or top of the backplate or extra stencil face use the extra stencil face for double sided EXIT installations single face installation using a blank backplate is shown above Place the resulting opening in the backplate or stencil over the threaded nipple on the canopy and thread on the jamb nut A four pole connector assembly is provided on t...

Page 4: ... the canopy bracket Thread the jamb nut onto the end of the pendant stem followed by the pendant adapter Remove the center knockout that is found in the top of the backplate or extra stencil face use the extra stencil face for double sided EXIT installations single face installation using the backplate is shown above Place the resulting opening in the backplate or stencil over the threaded nipple ...

Page 5: ...maining four Torx screws thru the corners of the stencil electronics assembly to finish the installation if vandal resistant shield option has been ordered use the Torx screws to also attach the clear shield to each stencil face Recessed Mounting Option Make a 13 7 8 x 9 1 2 cutout in the mounting surface Secure the backbox with nails or screws to the stud structure Route flex conduit into the upp...

Page 6: ...lluminates and EXIT is illuminated 2 Press the test switch pilot lamp and verify that the pilot lamp turns off and EXIT remains illuminated 3 Leave AC connected for a minimum of 24 hours before performing any extended testing Full recharge of batteries may require one full week Notes 1 This equipment is provided with a lockout feature whereby connecting battery leads prior to energizing AC power w...

Page 7: ...manually initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec t...

Page 8: ...ion 200 Franklin Square Drive Somerset NJ 08873 USA Phone 855 486 2216 www philips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053550 February 2016 ...

Reviews: