background image

4

Product Guide - LRM1070, LRM1080

Mounting

Fixing

The OccuSwitch can be mounted in two ways; 
recessed in the ceiling or surface-mounted using  
the ceiling box.
The ceiling box (LRH1070) has breakout ports for 
cable ducts and a breakout centrepiece.

When selecting a location for the OccuSwitch, avoid 
obvious cold spots so that condensation does not 
occur.

Fixing the OccuSwitch in a ceiling (recessed)

Fixing the OccuSwitch on a ceiling  
(surface-mounted)

 80-82 mm

> 50 mm

 30 mm

1

1

2

max. 185 mm

No. 8 (Ø 4 mm)

35

Ø 95 mm (3.74 in)

5

1.5 mm

(2.

0

3 in

)

56 .. 66 mm

(2.2

0 .. 2.

6

0 in

)

3

1

2

4

5

22 x 10 mm
25 x 13 mm
25 x 16 mm
16 x 16 mm 

LRH1070 

LRM1070
LRM1080

3

1

2

4

5

22 x 10 mm
25 x 13 mm
25 x 16 mm
16 x 16 mm 

LRH1070 

LRM1070
LRM1080

Summary of Contents for OccuSwitch LRM1070/00

Page 1: ...światło w pomieszczeniu lubna otwartej przestrzeni po opuszczeniu jej przez ostatnią osobę obniżając w ten sposób zużycie prądu nawet o 30 Przełącznik OccuSwitch może włączać instalacje pracujące na prądzie do 6 A oraz kontrolować pomieszczenia o powierzchni od 20 do 25 m2Złączka sieci zasilającej zapewnia łatwy montaż przełącznika OccuSwitch na suficieDostępny jest osobny przewód Wieland umożliwi...

Page 2: ...MOV DET ST OccuSwitch 2018 Philips Lighting Holding B V Wszelkie prawa zastrzeżone Dane mogą ulec zmianie bez uprzedniego powiadomienia Znak towarowy jest własnością Philips Lighting Holding B V lub odpowiednich podmiotów www lighting philips com 2018 Maj 18 Dane wkrótce ulegną zmianie ...

Page 3: ...Product guide OccuSwitch movement detector LRM1070 LRM1080 ...

Page 4: ...tch in the ceiling A separate Wieland cable is available for easy fast and trouble free installation The OccuSwitch family exists of LRM1070 Basic OccuSwitch LRM1080 Advanced OccuSwitch LCC1070 Wieland cable LRH1070 Ceiling mounting box Dimensional drawing LRM1070 Basic OccuSwitch LRM1080 Advanced OccuSwitch LCC1070 Wieland cable LCC1070 Wieland cable LRH1070 Ceiling mounting box LRH1070 Ceiling m...

Page 5: ...ow the required level Functions advanced version Parallel operation It is possible to connect up to 10 OccuSwitches in parallel via a separate bus signal When one of the OccuSwitches detects movement all units will switch the lights on The bus signal is fully isolated so each OccuSwitch can be used on any mains group or phase allowing the use of several mains groups in an area and easy wiring Loca...

Page 6: ...ecting a location for the OccuSwitch avoid obvious cold spots so that condensation does not occur Fixing the OccuSwitch in a ceiling recessed Fixing the OccuSwitch on a ceiling surface mounted 80 82 mm 50 mm 30 mm 1 1 2 max 185 mm No 8 Ø 4 mm 35 Ø 95 mm 3 74 in 51 5 mm 2 03 in 56 66 mm 2 20 2 60 in 3 1 2 22 x 10 mm 25 x 13 mm 25 x 16 mm 16 x 16 mm LRH1070 LRM1070 LRM1080 3 1 2 4 5 22 x 10 mm 25 x ...

Page 7: ...the OccuSwitch of being pushed out of the ceiling due to the weight of these ridged cables Parallel operation Parallel operation is used to enlarge the covering area of the OccuSwitch This can be done in two ways either by parallel installation or by using the parallel connection of the advanced OccuSwitch LRM1080 Parallel installation limits the total load to 6A and restricts the application to o...

Page 8: ... 500 Lux required with 1000 Lux installed This will prevent the lights from switching on and off in a 15 minute cycle The OccuSwitch can switch off once or twice with a 15 minute delay for reference purposes This cycle will repeat every time the OccuSwitch is reconnected to the mains power Calibration Turn the dial to raise or lower the required light level Calibration Local control LRM1080 The Oc...

Page 9: ... the power on and IR group settings together if changed To erase previous settings press reset followed by send on the IRT9090 B Warnings The OccuSwitch should not be used in the following situations In applications outside the specification range most notable heights above 3 5 meter Environmental conditions other than in a normal office environment temperature humidity In applications with heat s...

Page 10: ...rew terminal CPF5 08 2VE or MSTB2 5 2 ST 5 08 Maximum wire range 1 5 to 2 5mm2 Maximum length 100m Settings LED indicator Red on movement detection Switch off delay 1 to 30 minutes Light levels 250 to 1000 Lux 30 reflection Detection range see diagram The remote control and light sensor work in a similar range Compliances and approvals Standards EN IEC 60669 2 1 Electronic switches Classification ...

Page 11: ... 0 07 LRH1070 Outer box 400 x 300 x 300 42 cardboard 1 8 2 4 LCC1070 Unit box 90 x 90 x 90 1 plastic bag 0 13 0 17 LCC1070 Outer box 289 x 214 x 178 18 cardboard 2 4 2 7 Type MOQ Ordering number EAN code level 1 EAN code level 3 EOC LRM1070 00 OccuSwitch basic 1 9137 003 27803 8711559 731384 8711559 731391 731384 99 LRM1080 00 OccuSwitch advanced 1 9137 003 27903 8711559 731407 8711559 731414 7314...

Page 12: ...g Holding B V all rights reserved Specifications are subject to change without notice Trademarks are the property of Philips Lighting Holding B V or their respective owners 3222 636 33176 6 October 2016 www philips com controls ...