10
Connecting alarm and time signal inputs
The alarm and time signal switches are connected across poles 4 and 5 of the 5-pole DIN con-
nectors. The alarm signal will be activated by opening or closing the switch (depending on the
normally closed/normally open setting described in section 1.3). Refer to fig. 1.14. The DIN
connectors are shown in fig. 1.12, fig. 1.13 and fig. 1.14.
1.3
Configuring the ARM
The following table lists the DIL switches used to configure the ARM.
3
3
= 'On'
7
7
= 'Off'
DIL
Switches
Description
Setting
S300
1 2 3 4
Time signal priority
7 7 7 7
Priority 1
3 7 7 7
Priority 2
7 3 7 7
Priority 3
7 7 3 7
Priority 4
7 7 7 3
Priority 5
S300
5 6 7
Time
signal
selection
7 7 7
1.2 kHz for 1s
3 7 7
554 Hz for 4 s
7 3 7
440 Hz for 4 s
3 3 7
554 Hz for 4 s
7 7 3
1 kHz for 4 s
3 7 3
1 kHz for 4 s
7 3 3
1 kHz for 4 s
3 3 3
1 kHz for 4 s
S300
8
Time signal activation/
3
Pulse on/Pulse off
deactivation properties
7
ON/OFF
S301
1 2 3 4
Alarm
priority
7 7 7 7
Priority 1
3 7 7 7
Priority 2
7 3 7 7
Priority 3
7 7 3 7
Priority 4
7 7 7 3
Priority 5
S301
5
Alarm signal activation/
3
Pulse on/Pulse off
deactivation properties
7
ON/OFF
S301
6
Normally open/closed
3
Normally closed
7
Normally open
S301
7
Interruption/deactivation
3
Deactivation
7
Interruption
S301
8
Zone selection
3
Alarm - All call, Time - pre-select
7
Time - All call, Alarm - pre-select
S302
1 2 3 4 5 6 7 8 Zone selection (1to 8)
Select any combination of zones 1 to 8
using DIP switches 1 to 8 respectively
S303
1 2 3 4
Zone selection (9 to 12)
Select any combination of zones 9 to 12
using DIP switches 1 to 4 respectively
S303
5 6 7 8
Alarm
signal
selection
7 7 7 7
Slow Whoop 60 s; 500 to 1200 Hz sweep (in 1s, pause 1 s)
3 7 7 7
Slow Whoop key-release; 500 to 1200 Hz sweep (in 1 s, pause 1 s)
7 3 7 7
DIN Alarm 60 s; 1200 to 500 Hz sweep (1 s repeating)
3 3 7 7
DIN alarm key-release; 1200 to 500 Hz sweep (1 s, repeating)
7 7 3 7
Evacuation key-release; 554 Hz (100 ms), 440 Hz (400 ms)
3 7 3 7
Immediate danger key-release; 600 Hz (200 ms), pause (200 ms)
7 3 3 7
Not defined
3 3 3 7
Not defined
7 7 7 3
Fire alarm 60 s; 440 Hz (12 s on, 12 s off)
3 7 7 3
Slow Whoop key-release; 500 to 1200 Hz (in 3.5 s, pause 0.5 s)
7 3 7 3
Two-tone alarm 60 s; 440 Hz (1s), 554 Hz (1s)
3 3 7 3
Base tone key-release; 440 Hz continuous
7 7 3 3
Pulse alarm 60s; 1000 Hz (300ms), pause (200ms)
3 7 3 3
Morse A (di-dah), repeating, 1200 Hz signal, 12 WPM (dit=100 ms)
7 3 3 3
Morse F (di-di-dah-dit), repeating, 1200 Hz signal, 12 WPM (dit=100 ms)
3 3 3 3
Not defined