10
Design-in Guide - Philips EasySense luminaire-mount sensors
May 2016
Lighting control overview
EasySense controls the light output based on the
occupancy, daylight regulation and field task level.
When both occupancy- and daylight-based lighting
control are enabled, the light level is determined by
the lowest light level of the following:
• Occupancy-based set point (either the switch-on
level, background level or off)
• Daylight regulation set point (The daylight
regulation set point is the amount of light needed
on top of the available daylight.)
• Field task level
In case occupancy-based lighting control is disabled,
the occupancy-based set point is not used for
determination of the light level. In case daylight-
based lighting control is disabled, the daylight
regulation set point is not used for determination of
the light level. When both occupancy-based light
control and daylight-based light control are
disabled, the light output will continuously be on
field task level.
Switch On sequence
Switch On level (fixed)
T1
T3
T2
T4
T5
T7
T6
Background level
(configurable)
LIGHT
LEVEL
Fade
to s
wit
ch on
(fix
ed)
Fade
to s
wit
ch on
(fix
ed)
G
rac
e
fading
(configur
abl
e)
G
rac
e
fading
(configur
abl
e)
Fade
to s
wit
ch o
ff
(fix
ed)
Fade
to s
wit
ch o
ff
(fix
ed)
Hold time
(configurable)
Prolong time
(configurable)
Switch Off sequence
Occupancy-based lighting control