Commissioning

Scene control and scene setting

Decommissioning the switch

Battery replacement and service

Battery LED Indication

Use the Philips Field App to add a switch to an EasySense group. An App User Manual 
can be found at www.philips.com/easysense. Follow the flow of either “Create group” or 
“Add to group” until the “Adding wireless switch” screen shows up. Simultaneously press 
the “On” and “Off” buttons for at least 4 seconds to move the switch into commissioning 
mode.

Upon entering commissioning mode the LED indicator flashes at a 500msec duty cycle 
for 30 seconds (500 msec on/500 msec off). The luminaire with Easysense will blink 
twice when the zigbee channel is matched. Finish the work flow on the App for creating  
or adding to the group. 

A 30 second time-out is used during commissioning mode.  If no reaction is received from 
the EasySense for 30 seconds, the device will move back to the decommissioned state.

When the device is commissioned, it can only enter commissioning mode again after 
being properly decommissioned.

When the device is commissioned, all commission data is stored in the switch memory.  
This memory is held even in the event of a battery changeout. 

Decommissioning is achieved pressing the decommission 
button and holding for at least 1 second. See diagram below 
for location of the button, which can be accessed with a  
paper clip. After decommissioning, the switch is out of the  
network and can be re-added to a group by following the 
commissioning procedure. 

To replace the battery, disassemble the switch from the wall to access the Switch  
Assembly. Locate the “Button Cover Access Slot” at the bottom of the Button Cover  
Assembly (see drawing). Gently pry with a screwdriver to separate the cover. The battery 
will be visible pressed against the switch circuit board by the battery clip. Carefully  
remove the old battery. Replace only with lithium button cell battery CR2032. Be sure  
the battery “+” is facing the battery clip. Snap the cover back onto the Button Cover  
Assembly with the battery at the lower end of the switch. Re-assemble the switch  
to the wall.

Other than battery replacement, this switch is non-serviceable. A damaged or  
non-functioning switch should be completely replaced and should not be repaired.

Decommission button

Button Cover Access Slot  
(also location of battery insulator strip on new switch)

Pressing a Scene button on the switch will instruct the sensors and lighting in the group 
to go to their programmed setting. Scenes can be custom configured through the Philips 
Field Apps. See the EasySense App User Manual on www.Philips.com/easysense. The 
default settings are: Scene 1-- 60% light output; Scene 2 – 20% light output.  

Button state

Battery level – Normal ( > 2.5V)

Battery level – Low
( 2.3 < Low < 2.5V)

Battery level – Dead
( < 2.3V)

Any button in 

pressed state

RED LED blink

6 cycles, 50ms On –  

100ms Off

RED LED flash once

50ms On

RED LED Off

All buttons in 

released state

RED LED Off

RED LED Off

RED LED Off

This product contains a lithium button/coin cell battery. If a new or used lithium 
button/coin cell battery is swallowed or enters the body, it can cause severe internal 
burns and can lead to death in as little as 2 hours. Always completely secure the battery 
compartment. If the battery compartment does not close securely, stop using the 
product, remove the batteries, and keep it away from children. If you think batteries 
might have been swallowed or placed inside any part of the body, seek immediate 
medical attention.

The cells shall be disposed of properly, including keeping them away from children; and 
Even used cells may cause injury.