Philips EasyAir SNS210 MC Design-In Manual Download Page 1

Design-in Guide

Single, compact, 

cost-effective 

luminaire control

Philips EasyAir SNS210 MC

, SNS410 MC

August

 202

1

Sensors

EasyAir

SNS210 MC

, SNS410 MC

Summary of Contents for EasyAir SNS210 MC

Page 1: ...Design in Guide Single compact cost effective luminaire control Philips EasyAir SNS210 MC SNS410 MC August 2021 Sensors EasyAir SNS210 MC SNS410 MC ...

Page 2: ...t calibration Daylight regulation with calibration Mechanical design in Wire strip length Wire insertion Wire separation from the connector Wiring Information Wire distance for remote mounting Luminaire to luminaire distance Recommendations to design in around EasyAir SNSx10 MC with good RF signal Mounting to a luminaire Mounting EasyAir SNS410 MC inside of a luminaire Mounting in a bracket SMB 50...

Page 3: ...sensor functionality mechanical mounting wiring details configuration and commissioning grouping method application notes and frequently asked questions For sensor specifications please see the datasheet available at www lighting philips co uk oem emea products connected lighting More information or support For further information or support please consult your local Philips sales representative o...

Page 4: ...tion of qualified wireless switches obstructions in viewing angle will result in incorrect functioning of occupancy detection Faulty settings of the sensor might result in undefined startup Make sure the sensor especially the occupancy detection lens is protected from damage during shipment and handling The application area of EasyAir SNS210 MC is designed for a typical indoor environment open pri...

Page 5: ...ution ideal for energy savings An intuitive MasterConnect app makes commissioning and configuration during and after installation fast and easy EasyAir SNS210 MC enables grouping allows scene setting on a wireless switch e g presentation mode for a conference room as well as occupancy sharing i e luminaires within a group can be programmed to remain at prescribed light levels so long as occupancy ...

Page 6: ... LED indicator EasyAir SNS210 MC is designed for a typical indoor environment open private offices conference rooms classrooms corridors etc in normally heated and ventilated areas The sensor is normally mounted to a luminaire and is optimized for a sensor mounting height of 2 5 m to 3 m Zigbee and Bluetooth Low Energy BLE The Zigbee BLE antenna should not be covered by metal and should be exposed...

Page 7: ...wn to a few centimeters at the task area of a desk and is sensitive to major movements within a range of X2 by Y2 The directions X1 X2 are parallel to direction X likewise for Y1 Y2 being parallel to Y The maximum recommended height to place the sensor in the ceiling is 3 m to assure movement coverage and detection The PIR sensor reacts on movement by means of a temperature difference such as the ...

Page 8: ...ulled out flipped and inserted back in the sensor and then rotated so the correct area is shielded off from the detection area If such shield is not needed in the application it can be easily pulled out from the sensor or left as in the original position To prevent false triggers the EasyAir SNS210 MC must be mounted more than 2 m away from air vents in all directions see figures below 2m 2m Lumin...

Page 9: ...ounted too close to the window it will look partly outside Sun reflection from cars or snow can reflect directly into the sensor The sensor will then measure such high illumination levels that it will drive the artificial light to its minimal level or even switch off the artificial lights The optimum distance Y from the window to EasyAir SNS210 MC can be obtained from Figure 4 This graph shows the...

Page 10: ...for the required lux value in the working area It is recommended to measure the value with a lux meter Daylight regulation with calibration Any time after configuration a calibration routine can be initiated When the calibration routine is run the light level adjusts to the full light output given by the operating current of the luminaire times the percentage value set for the Eco on level In a da...

Page 11: ... Conductor size fine stranded 0 25 0 34 mm2 with insulated formule AWG 24 18 Strip length 7 9 mm 0 28 0 35 in Note Stranded wires without ferrule should be soldered Strip length 8 0 0 5 mm Conductor Conductor Bare Copper Strand wire Insulation 5 7 Angle Max Insertion Inserting solid conductors via push in terminal 2 Pull out 1 Push Wire strip length Wire insertion Wire separation from the connecto...

Page 12: ...ance will minimize a sensor from seeing the light variation of neighbouring luminaires and reacting Recommendations to design in around EasyAir SNSx10 MC with good RF signal It is recommended to have one side metal wall distance from EasyAir SNS210 MC SNS410 MC antenna side wall greater than 100mm assuming other metal walls are further away see figure 6 below 0 0 1 2 3 4 5 6 20 40 signal loss dB v...

Page 13: ...in the same cavity Without the shield some light can tunnel through the white housing and impact daylight sensing Mounting EasyAir SNS410 MC inside of a luminaire Easy Air SNS410 MC can also be placed inside of a sealed luminaire with plastic housing because plastic materials do not block the RF signal and it has no sensor functionality The sensor must not be enclosed by metal parts In addition th...

Page 14: ...ir SNS210 MC SNS410 MC can be mounted in a bracket SMB 50 Refer the figures for details on mounting and design in into luminaire All dimensions are in mm 65 Max 26 Max 64 Max 24 Max 8 Max 22 0 2 60 0 2 Press springs inwards on both sides before the bracket can slide in the luminaire hole ...

Page 15: ...any pre mounted sensor or cable The luminaire manufacturer needs to mount the sensor in the CMP bracket and attach cable to it The cable and screws are available with the accessory Caution The cable length from the EasyAir sensor to SR driver should be kept 2m For cut out in the ceiling and mounting refer to the figures below All dimensions are in mm 74 46 86 Ø 63 Ø 74 Radius min 5 mm ...

Page 16: ...ain the assigned ZigBee MAC Address For a typical application the top two labels can be removed and discarded For a network application using a gateway the labels can be used to identify a luminaire and where it is installed in the building Label 1 Apply to the luminaire Label 2 Apply to the floor plan Label 3 Remains on the sensor ...

Page 17: ...bilities to address individual drivers The light commands are sent as a broadcast command so occupancy daylight based lighting control and task tuning operate the same on all connected drivers The readout of energy information from the connected drivers will not function The energy readout of multiple drivers is foreseen in our roadmap Warning Please note the DALI power supply can only be turned o...

Page 18: ...Xitanium SR driver is correct a visible check can be made The luminaire on power up dims up to 30 of maximum light output in the 1st second followed by dimming up to 100 in the next second This behaviour is only visible in non commissioned devices i e once grouped using Philips MasterConnect app this behaviour will cease to exist Luminaire Production Test ...

Page 19: ...ith energy reporting and works with Philips Xitanium SR LED drivers to eliminate the cost and complexity of a separate power pack Is EasyAir SNS210 MC a DALI sensor EasyAir SNS210 MC works with Philips Xitanium SR LED drivers which have inbuilt power supply It cannot be used with DALI drivers and therefore EasyAir SNS210 MC is not a DALI sensor Can I use EasyAir SNS210 MC outside a luminaire An ac...

Page 20: ... SR LED drivers as on off is done relay free within the driver Devices with mechanical relays should be designed so that relay failure results in lights on If an SR driver does not see a digital signal from a device for a long period of time e g loose connection sensor failure the driver goes to full programmed output Does EasyAir SNS210 MC work on 0 10v drivers No EasyAir SNS210 MC works on Phili...

Page 21: ...SNS210 MC August 2021 Philips EasyAir SNS210 MC SNS410 MC Product information www lighting philips co uk oem emea products easy to integrate wireless sensors html Or contact your local Philips sales representative Contact details ...

Page 22: ...ity content and or quality of any recommendations and other advice contained in this document whether express or implied including without limitation any warranties of satisfactory quality fitness for a particular purpose or non infringement Signify has not investigated and is under no obligation or duty to investigate whether the recommendations and other advice contained in this document are or ...

Page 23: ...ot be liable for any action in reliance thereon The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N V All other trademarks are owned by Signify Holding or their respective owners 08 2021 Data subject to change www lighting phili...