Philips Dynalite DUS360CR Installation Manual Download Page 2

DUS360CR Installation Instructions Rev A Specifications subject to change without notice

Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921)  Unit 6, 691 Gardeners Road  Mascot  NSW  2020  Australia  Tel: +61 2 8338 9899 Fax: +61 2 8338 9333

E-Mail: 

[email protected]

      Web: 

http://philips.com/dynalite

DyNet Terminal

 

5-way pluggable screw terminal

 

1 x 2.5mm

2

 conductor size

DyNet Network Supply

  RS485 12-24 VDC, 20mA max

PIR sensor: 

Quad element pyroelectric

Max detection range

5 m

Detection area: 

7.4 m x 5.6 m (at 2.4m mounting height)

Detection speed: 

1 m/s

Detection object: 

700 mm x 250 mm

Detection zones: 

64

Activation indicator: 

LED

PE cell: 

<5 to >5000 lux (reflected)

 

Automatic daylight harvesting mode

Infrared Rx: 

RC5

Controls:

 

Walk test / LED indicator

 

Network sign-on button

Compliance: 

CE, RCM

Operating Conditions: 

Temperature: 0 to 45° C ambient

 

Humidity: 0 to 90% non-condensing

Storage & Transport: 

Temperature: -25 to 60° C ambient

 

Humidity: 0 to 90% non-condensing

Construction: 

ABS plastic enclosure

Dimensions: 

72 mm dia. x 41 mm (2.8” dia. x 1.6”)

Packed Weight: 

TBA kg

Installation Steps

1.  Fix the sensor to a 64 mm diameter circular hole in a firm section of the ceiling. The mounting position should adhere to the following 

guidelines:

• 

Ceiling height should be between 2.1 m and 4.0 m. Optimum height is 2.4 m.

• 

Position the sensor at least 1 m away from electrical lighting such as neon and fluorescent lights.

• 

Avoid exposure to direct sunlight and heating/cooling sources.

• 

Position the sensor where pedestrian traffic is likely to move through the detection zone.

• 

Note that the sensor coverage area is rectangular, approximately 7.6 m x 5.4 m (at 2.4 m installation height).

• 

The detection range above is specified for an ambient temperature of 25ºC. This range is reduced at higher temperatures.

2.  If needed, pull out and rotate the masking bezel to block a 120

º

 viewing angle.

3.  Terminate the DyNet cable as indicated below. If terminated and powered correctly, the red indicator LED turns on for 5 seconds.

Recommended Cable Type

Dynalite DYNET-STP-CABLE or equivalent 

shielded three twisted-pair cable.

See datasheet for more information.

Recommended Cable Color Coding

Green/White Pair

 

Paralleled for GND

Orange/White Pair

 

Paralleled for +12VDC

Blue/White Pair

 

Blue for DATA+

 

White for DATA-

Brown/White Pair

 

Spare, use for SHIELD on unshielded cables

RS485 DyNet network

Product Specifications

Daisy chained 

device

first or last device

DRAFT