To reduce the risk of fire or electric shock, do not expose this device to rain or moisture. Installation, programming and maintenance must be 

carried out by qualified personnel. All local wiring and electrical regulations must be followed when installing device.

Overview

360º motion detection (PIR) – 

Detects presence or absence of

motion and adjusts lights accordingly.

Low profile

  recessed flush mount

Segmented click-up bezel – 

Masks unused detection areas

Ambient light level detection (PE) –

 Allows accurate lighting

control and daylight harvesting.

Infrared Rx sensor – 

device enables system control via any RC5

IR remote.

Ceiling Mount Universal Sensor

Read Instructions

 – We recommend that you read these 

instructions prior to commencement of installation.

 

Check Connections

 – Ensure that all wiring terminals are securely 

connected.

Mounting Location

 – For indoor use only. Select sensor locations 

as per user requirements. Note that the optimal locations for PIR 

and PE use may be different, requiring multiple sensors in the 

same area.

Data Cable

 – Use screened, stranded RS485 data cable with three 

twisted pairs. Segregate from mains cables by at least 300mm.  

Connect devices in a ‘daisy chain’ configuration. A data cable that 

is connected to an energized device is live. Do not cut or terminate 

live data cables.

Installation

 – Installation must be done in accordance to the local 

wiring code (or wiring rules). Installation of home and building 

automation and control systems shall comply with HD60364-4-41.

Lens Pattern

8m

6m

0

1

2

3

4

1

2

3

4

0

1

1

2

2

3

3

72mm

2.8in

63mm

2.5in

41mm

1.6in

39mm

1.5in

Dimensions

Hardware

Light level 

sensor

Network sign-

on button and 

IR window

Masking bezel

PIR sensor

DRAFT