DRC810DT 

SPDT Dry Contact Relay Controller  
Installation Manual 

 

 

contents 

 

Warning…………………………………………….. 2  Hardware Controls.……………………………………..8 
Features…………………………………………….. 2  Troubleshooting…………………………………………9 
Important Safeguards……………………………..  2  Specification..……………………………………………9 
Internal View……………………………………….. 3   
Mounting…………………………………….……… 4   
Supply & Load Cable Connections.……………… 5   
Connecting 

Serial Control Cables……………….. 6   

Summary of Contents for Dynalite DRC810DT

Page 1: ... 61 2 8338 9333 dynalite info philips com dynalite online com DRC810DT SPDT Dry Contact Relay Controller Installation Manual contents Warning 2 Hardware Controls 8 Features 2 Troubleshooting 9 Important Safeguards 2 Specification 9 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 ...

Page 2: ...n cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specified capacity of 10A Loads should be calculated to ensure that the overall maximum capacity of 80A is not exceeded Functional isolation only exists be...

Page 3: ... Mounting Point Network Socket Service Switch Depth 75mm Transformer SHLD GND D D 12V AUX Alternative Mounting Point to Enable Easy Cable Access Relay SPDT Dry Contact Outputs EARTH LINK 8 C NO NC 7 C NO NC 6 C NO NC Dry Contact Control Inputs Accessory Socket Supply 230V AC 0 5A LINE IN NEUTRAL For spare parts or service please call your local Philips Dynalite Dealer and specify DRC810DT ...

Page 4: ... brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DRC810DT can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load ...

Page 5: ...uit is not overloaded Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 10A resistive Derate for reactive loads When connecting ELV or SELV cables to the relay terminals ensure that proper segregation is maintained between them and mains cables Control Input Cables There are 8 control inputs that terminate on a 10 way terminal strip They...

Page 6: ...leled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting ...

Page 7: ...tion Go Stop Motor 1 Motor 2 Motor 3 Motor 4 Example of load wiring for 12V DC bi directional curtain motors Direction Movement Motor 1 Channel 1 2 Motor 2 Channel 3 4 Motor 3 Channel 5 6 Motor 4 Channel 7 8 12V Motor 12V Motor 12V Motor 12V Motor 12V DC Power Supply C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC 8 7 6 5 4 3 2 1 Direction Movement Motor 1 Channel 1 Channel 5 Motor...

Page 8: ...l strip is no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for o...

Page 9: ...stant tripping short circuit on load Delayed tripping Load Controller overloaded Check load wiring for short circuits Verify Load Controller loading with current tester don t forget to de rate for low power factor loads and transformer losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Control cable from DRC810DT to bal...

Page 10: ...3 097 246 921 All rights reserved Dynalite Dimtek DyNet and DLight and associated logos are the registered trademarks of Dynalite Intelligent Light Pty Ltd Not to be reproduced without permission Unit 6 691 Gardeners Road Mascot NSW 2020 Australia Tel 61 2 8338 9899 Fax 61 2 8338 9333 E mail dynalite info philips com Web Philips com dynalite ...