DLE220-S Instruction Manual Rev F.doc   

5

 

 

 

 

Supply Cables 

The supply input terminals are located toward 
the  top  left  of  the  enclosure  and  consists  of 
Neutral, Line, and an Earth link located on the 
chassis, all of which will accept up to 10mm

2

 

cables.    The  supply  cables  should  have  a 
capacity of at least 40A. 

 

 
 
 

Load Cables 

Load cables can be terminated on the 2 way 
Load  terminal  strip.  These  connectors  will 
accept  up  to  10mm

2

  cables.  Calculate  the 

intended load, and ensure that it is below the 
maximum  capacity  of  an  individual  channel, 
which is 20A. Derate for reactive loads.   
 
 

 
 

Energising the Device 

If it is necessary to energise load circuits 
before any control cables are connected, it is 
acceptable to replace the cover and energise 
the device immediately, as the default factory 
programming is to have all channels set to 
100% output.  If there is no output on any or 
all channels, see the Troubleshooting section 
(page 7).  The device should be de-energised 
before terminating the control and data 
cables.   

 

 

 

 

 

 

 

 

  

supply and load cable connections 

 

Summary of Contents for Dynalite DLE220-S

Page 1: ...alite info philips com ABN 33 097 246 921 philips com dynalite DLE220 S 2 x 20A Leading Edge Dimmer Installation Manual Contents Features 2 Troubleshooting 7 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Hardware Controls Analogue Inputs 7 ...

Page 2: ...will allow any control panel to control all channels in all dimmers Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earth...

Page 3: ...DLE220 S Instruction Manual Rev F doc 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE220 S internal view ...

Page 4: ...re designed to accommodate 4 fixing screws up to 8mm diameter The DLE220 S can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load control cab...

Page 5: ... 10mm2 cables Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 20A Derate for reactive loads Energising the Device If it is necessary to energise load circuits before any control cables are connected it is acceptable to replace the cover and energise the device immediately as the default factory programming is to have all channels set t...

Page 6: ... VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting method is...

Page 7: ...no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for optional fea...

Page 8: ...allast incorrectly wired Control cable from DRC810DT to ballasts not installed Check ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI cable and settings Supply 230V 14 50 60Hz Single Phase at 40A Outputs 2 x dimmed outputs leading edge phase control at 20A total box load is 40A max Power Conditioning Regulated outputs Over voltage protection Surge protection ...