2

   DLE1210GL Installation Manual Rev H.docx 

features 

 

 

Multiple Supply Options 

Three phase and neutral supply at 25A per 
phase, or single phase and neutral supply at 
75A. 
 

 

12 Dimmed Outputs 

Each 10A output is independently regulated, 
protecting  loads  from  voltage  surges  and 
spikes. 
 

 

MCB Protection 

Each  output  is  protected  by  a  single  pole 
thermal - magnetic circuit breaker. 

 

 

Convection Cooled 

This  device  is  naturally  aspirated,  requiring 
no  mechanical  cooling  system,  when 
installed 

in 

accordance 

with 

these 

instructions. 
 

 

Many Control Options 

Control  of  this  device  can  be  from  a 
combination of available methods, eg. serial 
control port, relay contacts, push button wall 
stations,  infrared  receivers  and  timeclocks. 
Easy high level interface to other popular AV 
control  systems  and  Building  Management 
Systems  (BMS)  is  also  available.  This 
device  is  DMX512  compatible.    Dual  serial 
control  ports  for  applications  such  as 
network  backup  and  DMX512  compatibility 
are available as an option. 
 

 

Simple Installation 

Wall  mount  enclosure  with  mounting  lugs 
facilitate  installation.  Cable  knockouts  are 
provided,  at  the  top  of  the  enclosure  for 
supply  and  load  cables,  with  low  voltage 
(LV) control at the bottom.

  

 
 

important safeguards 

 

Warning

 

–  This  is  a  class  A  product.    In  a  domestic 

environment this product may cause radio interference, in 
which  case  the  user  may  be  required  to  take  adequate 
measures. 

Read  the  Instructions

 

– We  recommend  that  you  read 

this  instruction  manual  prior  to  commencement  of 
installation.    Retain  instructions  and  give  the  end  user 

Troubleshooting

 

–  If  problems  are  encountered,  read 

the troubleshooting section on page 8. 

Special Programming

 

– This device will only operate in 

basic  modes  unless  programmed  via  a  computer.    If 
programming  is  required,  contact  your  local  agent  for 
details.  Once the data cable is connected to the devices, 
the factory default settings will allow any control panel to 
control all channels in all dimmers. 

Check  Connections

 

–  Treat  this  device  as  a 

switchboard  that  has  been  shipped.    Tighten  all  load 
carrying  screw  connections,  as  vibrations  from  transport 
can  cause  MCB  and  terminal  block  screws  to  become 
loose. 

Power

 

Sources

 

–  This  device  should  only  be  operated 

from the type of supply specified on the front panel. This 
device 

must

 be earthed. 

Output  Circuits

 

–  The  load  on  a  circuit  should  not 

exceed  the  specified  capacity  of  10A.  Loads  should  be 
calculated to ensure that the overall maximum capacity of 
75A is not exceeded.  Some types of load will need to be 
de rated.  Check the Dimmable Lamps Chart on page 7 
for more information. 

Megger  Testing

 

–  Do  not  megger  test  any  circuitry 

connected  to  the  dimming  system,  as  damage  to  the 
electronics may result. 

Mounting Location

 

– This device must be mounted right 

way  up,  on  a  vertical  surface  (refer  to  page  4  for 
mounting instructions).  The specified minimum clearance 
of  200mm  for  all  sides  must  be  adhered  to.  Install  in  a 
dry,  well-ventilated  location.  Controllers  may  emit  some 
mechanical  noise.  Take  this into  account  when  deciding 
the mounting location. 

Data Cable

 

– The recommended cable for connections to 

the  serial  port  is  screened,  stranded  RS485  data  cable 
with  three  twisted  pairs.  Part  numbers  for  various 
manufacturers are listed on page 6. This cable should be 
segregated from mains cables by a minimum distance of 
300mm. If anticipated cable runs are over 600 metres for 
serial cables, consult your dealer for advice. Do not cut or 
terminate live data cables. 

Load  Type

 

–  The  factory  default  settings  are  for  all 

channels  to  be  dimmable.    Do  not  terminate  any  non-
dimmable  loads  until  the  relevant  channel  has  been 
programmed  as  switching  only.    See  the  Dimmable 
Lamps Chart on page 7.  If it is necessary to energise a 
switched  load  before  programming  has  occurred, 
temporarily  connect  the  load  to  the  emergency  lighting 
terminal, instead of the dimmed output terminal, see page 
5.  Some types of load will need to be de rated, check for 
details in the Dimmable Lamps Chart on page 7. 

 

 

Warning 

 

TO  REDUCE  THE  RISK  OF  FIRE  OR 
ELECTRIC  SHOCK,  DO  NOT  EXPOSE 
THIS DEVICE TO RAIN OR MOISTURE.  

 

DO  NOT  ENERGISE  UNLESS  THE 
FRONT COVER IS IN PLACE.  

 

THIS DEVICE MUST BE EARTHED.  

 

INSTALLATION,  PROGRAMMING  AND 
MAINTENANCE MUST BE CARRIED OUT 
BY QUALIFIED PERSONNEL 

Summary of Contents for dynalite DLE1210GL

Page 1: ...10A Leading Edge Dimmer Installation Manual contents Warning 2 Dimmable Lamps Chart 7 Features 2 Preset Programming Using The Program Key 8 Important Safeguards 2 Hold Down Programming Of Presets 9 Internal View 3 One Touch Button Operation 9 Mounting 4 Troubleshooting 10 Supply Load Cable Connections 5 Specification 10 Connecting Serial Control Cables 6 Useful DyNet Op Codes 11 Hardware Controls ...

Page 2: ...Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specified capacity of 10A Loads should be calculated to ensure that the overall ...

Page 3: ...internal view DLE1210GL Installation Manual Rev H docx 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DLE1210GL ...

Page 4: ... DLE1210GL has integral mounting brackets attached to the enclosure The brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DLE1210GL can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the co...

Page 5: ...individual channel which is 10A To ensure compliance with interference standards the load neutral cables must be individually connected to the neutral link terminals inside the cabinet Never use a common neutral at a remote location Emergency Lighting Connections Connect emergency lighting circuit active to the load side on the circuit breaker for the relevant channel as indicated by the labels ne...

Page 6: ...r GND one pair paralleled for 12V and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The re...

Page 7: ...etter performance an electronic HF dimming transformer is recommended The power factor capacitors need to be wired to the supply side of the dimmer Some Dynalite controllers include a supplementary relay contact for control of power factor capacitors If electronic ballasts are not used cabling and controllers should be de rated by approx 60 to allow for reactive current Contact your Dynalite deale...

Page 8: ...ufacturer s diagram specification Supply 230V 14 50 60Hz Single Phase at 75A or 230 400V 14 50 60Hz 3 Phase Y at 25A per phase Outputs 12 x dimmed outputs leading edge phase control at 10A total device load 75A Protection 12 x 10A 6kA single pole thermal magnetic circuit breakers Regulating Device Triac 600V 40A nom 400A surge Power Conditioning Regulated outputs Over voltage protection Surge prot...