background image

DDBC1200

Overview

• 

Single-phase supply – 

100 - 240 VAC at 0.5A

• 

12 individually controlled lighting driver channels –

 each 

Broadcast

• 

High output capacity – 

each of the 12 channels is capable of 

driving the following: 

 

 

DALI:

 max 80 drivers per channel or 300 total

 

 

DSI: 

max 100 drivers per channel or 375 total

 

 

0-10V: 

50mA sink or source per channel

• 

LED status indicators and override switches – 

for each of the 

12 outputs

• 

Powerful internal PLC –

 allows custom scripts to enable process 

control based on conditional logic

• 

Dry contact interface – 

factory settings enable this interface to 

• 

Many control options – 

device is controllable via a combination of 

methods, including a serial control port, relay contacts, push-button 

wall stations, infrared receivers and timeclocks

Signal Dimmer Controller

Read Instructions

 – We recommend that you read this guide prior 

to commencement of installation. 

Special Programming

 – Once powered and terminated correctly 

this device will only operate in basic mode. If network terminations 

are correct, a new Dynalite user interface turns all lighting channels 

on from button 1 and off from button 4. Commissioning can only 

begin once the full network has been tested. Advanced functions 

are commissioned via Envision software. If commissioning services 

are required, contact your local distributor.

Check Connections

 – Tighten all load-bearing screw connections, 

as vibrations from transport can cause the terminal block screws to 

loosen.

Power Sources

 – This device must only be powered by the supply 

Output Circuits

 – The load on each circuit must not exceed the 

or 50mA sink or source for 1-10V.

Mounting Location

 – Install in a dry, well-ventilated location.  

Controllers may emit some mechanical noise. Take this into 

account when deciding the mounting location.

Data Cable

 – Use screened, stranded RS485 data cable with three 

twisted pairs. Segregate from mains cables by at least 300mm.  

is connected to an energized device is live. Do not cut or terminate 

live data cables.

Electrical Diagram

Supply:

100 – 240 VAC

0.5A

E

µP

N L

DA+

CH2

CH3

CH4

CH5

CH6

CH7

CH8

CH9

CH10

CH11

CH12

DA-

+V

E

D

 +

D

 -

G

N

D

S

h

ie

ld

A

U

X

DyNet

RS485

2 x RJ12

CH1

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

DA+

DA-

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

D

A

LI

 1

-1

0V

 D

S

I

Supplied by:

Reviews: