CM-22200
CTX6 Series Compac
®
Thermoplastic Emergency Unit with
Xtest
dimensions
5-11/16"
(128.3mm)
5-1/4"
(133.6mm)
11-1/16"
(280.9mm)
photometry
Meets Life Safety Code standard minimum illuminance of 0.1 FC and average
illuminance of 1.0 FC. Assumes open space with no obstructions, mounting
height: 8', ceiling height: 9', and reflectances: 80/50/20. Analysis based on
independently tested photometrics.
3'
Xtest
testing specifications
• Automatic Test: The system charger and lamps are continually being
controlled via pre-determined parameters specific to each model
configuration, automatically. The battery is controlled via a true open circuit
test each hour after initial installation. One each month the
Xtest
System
illuminates lamps under load for 30 minutes, simulating a power outage
with a true charger off condition, without affecting long term battery life.
This is above and beyond the requirements of the National Fire Protection
Association. This gives you unequaled control and confidence, knowing you
are meeting self-test code requirements each and every month.
• Manual Test: A manual test switch allows for the
Xtest
system to perform
the following tests at any time:
Press
Button
Once–5
second test, charger off, no load
Twice–60
second test, charger off, lamps on
Three–90
minute test, charger off, lamps on
6-Second
Hold–Fully reinitializes micro-processor.
Pressing
once during any test will cancel/abort testing.
Location of sensor for laser activation
of manual test via handheld remote laser
tester (this is an optional feature, specify
“LX” option)
SELF-TEST / DIAGNOSTIC
CHARGER
BATTERY
LAMPS
CHG-TEST
Xtest
Status Indicator Panel
AC/Green Charger/Red
Batt/Red
Lamp/Red
Status/Fault
Action
On
AC power is on/OK
None
F
Performing Test
None
On
F
F
F
Lamp/Battery Disconnected or Charger Fault
Check connections; if ok, replace circuit board
On
F
Charger fault
Replace circuit board
On
F
Battery disconnected/fault
Check connection or replace battery
On
F
Lamp disconnected/bad or remote disconnected
Check connection then press manual test once to
determine bad lamp/replace lamp or check remote lamp.*
Fault Indications:
Four LED indicators provide visible indication of system status:
*If unit has remote capacity and remote cable is connected to charger board but not connected to
a remote load, then either connect remote load or disconnect cable from charger board.
On=Steady F=Flashing Blank=Off
lamp
spacing avg. fc. max. fc.
min. fc.
CTX6
5.4W tungsten
24ft.
1.0
2.00
0.1
CTX618 9W tungsten
39ft.
1.4
2.70
0.1
Test Numbers:
CTX6 - CSWA
CTX618 - CSWC
© 2016 Philips Lighting Holding B.V. All rights reserved.
Philips reserves the right-make changes in specifications
and/or-discontinue any product at any time without notice
or obligation and will not be liable for any consequences
resulting from the use of this publication.