WIRING DIAGRAM

Maintenance

Operation

During normal operation, AC power is supplied to the AC ballast/driver through the ELI-S-100 and the batteries charge. 

Connecting the inverter connector wires (red and white) enables the emergency circuit and supplies power to the control

/monitor circuit. When AC power fails, the ELI-S-100 automatically switches to emergency mode, keeping the load 

illuminated for a minimum of 90 minutes. When AC power is restored, the ELI-S-100 returns to charging mode. The unit 

can also detect an abnormal load condition (open or shorted load) during emergency mode operation and will protect the 

inverter from damage.

Always turn off AC power to the equipment and open the inverter connector inside the case before servicing. Servicing should 
be performed only by qualified service technicians. Use only manufacturer supplied replacement parts.

Although no routine maintenance is required to keep the emergency Lighting Inverter functional, it should be checked 

periodically to ensure that it is working.

Figure 7 shows an example of a branch circuit containing 5 luminaires, 3 of which are powered through an Emergency 

Lighting Inverter. During normal AC run mode, the power from the switched hot and dimmer voltage is passed through to 

the three “Emergency” fixtures. The unswitched hot charges the battery. During a power failure, the Emergency Lighting 

Inverter powers the “Emergency” fixtures for a minimum of 90 minutes, at a power level set by the Emergency Lighting 

Inverter’s dimming output level. In this example, each luminaire can draw a maximum of 33 Watts, to total no more than 

100 Watts.

Battery: The Battery supplied with this equipment requires no maintenance. However, it should be tested periodically 

and replaced whenever it will no longer operate the connected fixtures for the duration of a 90-minute test. The battery 

supplied has a life expectancy of 4 years when used in normal ambient temperature of 72 degrees F.

Fuse: The fuses contained within this product are field replaceable. For fuse locations see illustration 1. To replace fuses, 

remove AC Power from the product and disconnect the inverter connector. Ensure fuse F201 is replaced by Little Fuse 

0314015.MXP or equivalent 15 A, 125 VDC. Ensure fuse F101 is replaced by Little Fuse 0209005.MXP or equivalent 5 A,  

350 VAC.

>

After installation is complete, apply AC power and join the inverter connector inside the case then screw the front

cover to the case.

>

At this point, power should be connected to both the AC ballast and the ELI-S-100, and the Charging Indicator

Light on the test switch should illuminate indicating the battery is charging.

>

A short-term discharge test may be conducted after the Emergency Lighting Inverter has been charging for 1 hour.

Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.

STEP #7

JOIN THE INVERTER CONNECTOR & APPLY POWER

! REFER ANY SERVICING TO QUALIFIED PERSONNEL !

Note: 

Mark each designated emergency fixture with provided warning labels, 10 provided.

Testing:

  The following schedule is recommended

1.

Visually inspect the charging indicator light monthly. It should be illuminated.

2.

Test the emergency operation at 30-day intervals for a minimum of 30 seconds by pushing the illuminated

test switch located at the top of the unit.

3.

Conduct a 90-minute discharge test once a year.

CAUTION:

WALL SWITCH

ELI

UNSWITCHED HOT

SWITCHED HOT

COMMON

120/277 

AC POWER

0-10 V

DIMMING

NORMAL/ 

EMERGENCY

FIXTURE

INVERTER

CONNECTOR

RED

WHT

AC DRIVER

120 OR 277 V

AC OUT

NEUTRAL

DIM

OUT

DIM

OUT

 DIM (+) IN

DIM (-) IN

GND

INPUT FROM 0-10V

DIMMER

{

NORMAL ONLY

FIXTURE

NORMAL/ 

EMERGENCY

FIXTURE

NORMAL/ 

EMERGENCY

FIXTURE

NORMAL ONLY

FIXTURE

Figure 7

Summary of Contents for Bodine ELI Series

Page 1: ...s are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both the normal and emergency power supplies and the inverter connector of the emergency lighting inverter before servicing 5 Do not install near gas or electric heaters 6 An unswitched AC power source is required The AC voltage rating of thi...

Page 2: ...stalled Remove the knockouts to install input and output wiring conduit fittings Extend AC supply output load wiring and optional control wiring into the equipment enclosure using appropriate wiring hardware and methods Illustration 1 details the locations of the various wiring terminals and switch locations needed for the remainder of the installation Reference Illustration 1 for steps through 2 ...

Page 3: ...n 1 See Step 4 for switch settings STEP 4 SETTING THE OUTPUT DIMMING LEVEL OPTIONAL Upon loss of normal AC power the Emergency Lighting Inverter s internal 0 10 VDC circuit will output a dimming voltage to the luminaires PCB Switches S701 and S702 are used to set the 0 10 VDC dimming level See Illustration 4 which details the switch positions for the desired level of dimming Refer to Illustration ...

Page 4: ...YELLOW RED BLACK TO PCB BOARD J8 Attach the battery wires as shown in the illustration Refer to Illustration 5 for connections to these auxiliary relay contacts Ensure the ratings of the contacts are not exceeded The relay contacts are rated for 1 A at 30 VDC or 1 A at 120 VAC Install the batteries as shown With the unit secured to the mounting surface place the batteries into the enclosure as ill...

Page 5: ...placed whenever it will no longer operate the connected fixtures for the duration of a 90 minute test The battery supplied has a life expectancy of 4 years when used in normal ambient temperature of 72 degrees F Fuse The fuses contained within this product are field replaceable For fuse locations see illustration 1 To replace fuses remove AC Power from the product and disconnect the inverter conne...

Reviews: