background image

INSTALLATION

STEP #5

WIRING THE AUXILIARY RELAY CONNECTIONS (OPTIONAL)

This product also provides 2 additional isolated, auxiliary output relays to allow additional or alternate dimming  

operation from other dimming sources, or to provide a means of control or signaling to alternate equipment. See 

Illustration 1 for the location of these auxiliary contacts on the product.

STEP #6

BATTERY INSTALLATION

ILLUSTRATION 6a

BATTERY MECHANICAL INSTALLATION

4

This product is provided with two lead-acid batteries, which must be mechanically secured inside the enclosure using the provided 

battery bracket. They must then be wired using the provided battery connection wires. Refer to Illustration 6a and 6b for installation.

 

To replace the batteries, disconnect both switched and unswitched AC power to the Emergency Lighting Inverter. Remove 

the two screws securing the lid to the enclosure base and remove the lid. Open the inverter connector wires and then 

unplug and remove the old batteries. Reverse this process to install the new batteries. Remember to join the inverter 

connector prior to reinstalling the lid. The charging indicator light should be illuminated once unswitched AC power is 

restored.  Use only Philips Bodine part number PRT00133 as replacement batteries.

ILLUSTRATION 5  

AUXILIARY RELAY CONTACT WIRING

ILLUSTRATION 6b

BATTERY WIRING CONNECTIONS

YELLOW

RED

BLACK

TO PCB BOARD J8

Attach the battery wires as 

shown in the illustration.

Refer to Illustration 5 for connections to these auxiliary relay contacts. Ensure the ratings of the contacts are not exceeded. 

The relay contacts are rated for 1 A at 30 VDC or 1 A at 120 VAC.

Install the batteries as shown. With the unit secured to the mounting surface, place the batteries into the enclosure as  

illustrated in Illustration 6a. Insert the battery bracket on the battery bracket stud, ensuring the bracket is placed against the 

batteries. Slide the ring terminal of the grounding wire over the battery bracket stud. Securely fasten the grounding wire and 

battery bracket against the batteries using the external toothed washer and nut. Once the batteries are secure, attach the 

battery harnesses as shown in Illustration 6b.

•  The batteries should be installed and charged within 8 months of manufacture’s date code.

•  The battery date code is made up of 5 characters which represent the month, day and year of manufacture (MM/DD/Y). For example,

08023  means the battery was made August 2, 2013. There may be additional alpha-numeric characters at the end of the date code.

The date code  is located on the battery carton and additionally engraved into the battery.

•  DO NOT CONNECT the battery cable connector to the Circuit Board connector J8 until the unit is ready for use as the batteries may

be discharged after long periods of unit inactivity.

BATTERY REPLACEMENT

CAUTION:

BATTERIES

BATTERY BRACKET

RING TERMINAL FROM GROUNDING 

WIRE, EXTERNAL TOOTH WASHER 

AND NUT

Summary of Contents for Bodine ELI Series

Page 1: ...s are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both the normal and emergency power supplies and the inverter connector of the emergency lighting inverter before servicing 5 Do not install near gas or electric heaters 6 An unswitched AC power source is required The AC voltage rating of thi...

Page 2: ...stalled Remove the knockouts to install input and output wiring conduit fittings Extend AC supply output load wiring and optional control wiring into the equipment enclosure using appropriate wiring hardware and methods Illustration 1 details the locations of the various wiring terminals and switch locations needed for the remainder of the installation Reference Illustration 1 for steps through 2 ...

Page 3: ...n 1 See Step 4 for switch settings STEP 4 SETTING THE OUTPUT DIMMING LEVEL OPTIONAL Upon loss of normal AC power the Emergency Lighting Inverter s internal 0 10 VDC circuit will output a dimming voltage to the luminaires PCB Switches S701 and S702 are used to set the 0 10 VDC dimming level See Illustration 4 which details the switch positions for the desired level of dimming Refer to Illustration ...

Page 4: ...YELLOW RED BLACK TO PCB BOARD J8 Attach the battery wires as shown in the illustration Refer to Illustration 5 for connections to these auxiliary relay contacts Ensure the ratings of the contacts are not exceeded The relay contacts are rated for 1 A at 30 VDC or 1 A at 120 VAC Install the batteries as shown With the unit secured to the mounting surface place the batteries into the enclosure as ill...

Page 5: ...placed whenever it will no longer operate the connected fixtures for the duration of a 90 minute test The battery supplied has a life expectancy of 4 years when used in normal ambient temperature of 72 degrees F Fuse The fuses contained within this product are field replaceable For fuse locations see illustration 1 To replace fuses remove AC Power from the product and disconnect the inverter conne...