INSTALLATION
During normal operation AC power is applied, the charging indicator light is illuminated, indicating that the battery is
being charged. When power fails, the emergency ballast automatically switches to emergency power (internal battery),
operating either one or two lamps for a minimum of 90 minutes. When AC power is restored, the emergency ballast returns
to the charging mode and delays AC ballast operation for three seconds to prevent false-tripping of AC ballast (end-of-lamp-
life) shutdown circuits.
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to
ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. One or two
lamps should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. One or two lamps should operate at reduced
illumination for at least 90 minutes.
! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL !
OPERATION
STEP #4
WIRING THE EMERGENCY BALLAST
> Determine the type of AC ballast installed in the fixture.
> Select the appropriate wiring diagram on back to connect the emergency ballast to the AC ballast and lamp(s).
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency ballast and join the inverter connector.
> At this point, power should be connected to both the AC ballast and the emergency ballast, and the Charging
Indicator Light should illuminate indicating the battery is charging.
> A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge
for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label
"CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
MAINTENANCE
WIRING DIAGRAMS
The following diagrams are typical schematics only.
May be used with other ballasts. Consult the factory
for other wiring diagrams. Emergency Ballast and AC
Ballast must be fed from the SAME BRANCH CIRCUIT.
IMPORTANT TEXT: REFER TO TABLE 1
REGARDING BROWN CONNECTOR
Table 1
LAMP
(DIAMETER)
BASE
TYPE
WATTAGE
(Length)
NO. of LAMPS
(EMERGENCY-
MODE)
BROWN
CONNECTOR
T8,T9,T10,T12
(1”, 1¼”, 1½”)
Single
or
Bipin
17 - 40 W
(2'-4')
1
CLOSED
2
OPEN
40 - 215 W
(5' -8')
1
OPEN
LONG COMPACT
4-PIN (2G11)
18 - 39 W
1
CLOSED
2
OPEN
40 - 55 W
1
CLOSED
3
BROWN
BROWN
BROWN CONNECTOR CLOSED
BROWN
BROWN
BROWN CONNECTOR OPEN
JUMPER
WIRE