INSTALLATION

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT 

LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN  

INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO 

THE EMERGENCY BALLAST.

NOTE:  Make sure the necessary branch circuit wiring is available. An unswitched source of 

power is required. The emergency ballast must be fed from the same branch circuit 
as the AC ballast.

STEP #1

INSTALLING THE EMERGENCY BALLAST

>  Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast  

either in the ballast channel or on top of the fixture.* 

Remote mounting distance must be less than half the 

maximum remote mounting distance for the AC ballast. Consult AC ballast manufacturer before remote 

installation.

>  Depending on the type of fixture in use install emergency ballast using one of the methods illustrated below.

STEP #2

INSTALLING THE TEST SWITCH

>  Refer to the illustrations above and install the test switch 

through the ballast channel cover of a troffer or through the 
side of a strip fixture.

>  Drill a 1/2" hole and install the switch as shown.  

>  Refer to the diagrams on page 4 and wire the test switch so 

that it removes AC power from the unswitched hot line to the 
emergency ballast.

*  For  installation  on  top  of  the  fixture,  wire  bundle  covers  (RMC-60)  may  be  required  by  state  or  local  codes.  These  covers  are 

 

  available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete 

 

 information.

Inside Ballast Channel

Inside Strip Fixture

On Top of Fixture

INSIDE BALLAST CHANNEL

INSIDE STRIP FIXTURE

ON TOP OF FIXTURE

Fixture

Test Button

Hex Nut

Hex Nut

Test Switch

Leads

Push to Test

STEP #3

INSTALLING THE CHARGING INDICATOR LIGHT

>  Install the CHARGING INDICATOR LIGHT as shown in the illustration on the next page so that it will be visible 

after the fixture is installed.

2

NOTE:  After installing the charging indicator light and test switch, mark each with the appropriate label.

TROFFER STYLE FIXTURE 

STRIP STYLE FIXTURE

Charging

Indicator

Light

1/2" White

Bushing

Violet (+)

 

Brown (–)

Violet (+)

 

Brown (–)

1/2" White

Bushing

5/8" Black

Bushing

5/8" Black

Bushing

1/2" Punch

Fixture

Fixture

Charging

Indicator

Light

* If violet and brown leads are detached, connect to 

unit by matching wire colors.

Summary of Contents for B50

Page 1: ...s are in accordance with the National Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture 6 This product is suitable for use in damp loca...

Page 2: ... the side of a strip fixture Drill a 1 2 hole and install the switch as shown Refer to the diagrams on page 4 and wire the test switch so that it removes AC power from the unswitched hot line to the emergency ballast For installation on top of the fixture wire bundle covers RMC 60 may be required by state or local codes These covers are available from the manufacturer as an accessory kit and must ...

Page 3: ...nnect the emergency ballast to the AC ballast and lamp s Make sure all connections are in accordance with the National Electrical Code and any local regulations After installation is complete supply AC power to the emergency ballast and join the inverter connector At this point power should be connected to both the AC ballast and the emergency ballast and the Charging Indicator Light should illumi...

Page 4: ...E 1 LAMP COMPACT RAPID START BALLAST E M E R G E N C Y B A L L A S T WALL SWITCH WHT RED RED WHITE VIOLET BROWN WHITE WHT BLK COMMON TEST SWITCH INVERTER CONNECTOR CHARGING INDICATOR B L K B L K HOT BLACK LAMP 1 EMERGENCY LAMP 2 LAMP 3 LAMP 4 4 LAMP RAPID START BALLAST RED RED BLACK WHITE RED YELLOW YEL BLK BLU WHT BLUE BLU WHT BLU WHT YELLOW BRN BRN BLUE BLUE YELLOW WARNING Refer to Table 1 befor...

Page 5: ...TANT START BALLAST WARNING Do NOT connect brown connector BLUE RED YELLOW YEL BLK BLU WHT BLUE BLUE YELLOW RED YELLOW RED BLACK WHITE EMERGENCY EMERGENCY LAMP 1 LAMP 2 LAMP 3 LAMP 4 BROWN BROWN E M E R G E N C Y B A L L A S T WALL SWITCH WHT RED RED WHITE VIOLET BROWN WHITE WHT BLK COMMON TEST SWITCH INVERTER CONNECTOR CHARGING INDICATOR B L K B L K HOT BLACK 2 LAMP RAPID START BALLAST BLUE BLUE B...

Reviews: