10.
Hookup AC service to the unit as follows: Caution: Do not connect AC until battery is installed.
OPERATING INSTRUCTIONS
Energize AC power to the unit. The unit will initiate normal power-up sequence (See Normal Power Up
Sequence).
Figure 3
Self-Diagnostic System Operation – Emergency Light or EXIT Sign Products
Normal Power Up Sequence
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute
a “Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up
Quick Test” these will be evident by a flashing red LED indicator. If the audible diagnostic option has been ordered, the
flashing red LED will be accompanied by a simultaneous beeping tone. (Note: A continuous rapid alternating Red/Green
flash with rapid beeping tone indicates 277V applied to 120V input lead. TURN OFF POWER IMMEDIATELY!)
120 V
AC
OPERATION
277 V
AC
OPERATION
White Wire
- Common
White Wire
- Common
Black Wire
- 120V Line
Black Wire
- Cap Wire
Blue Wire
- Cap Wire
Blue Wire
- 277V Line
Green Wire
- Ground
Green Wire
- Ground