Page 3 of 7
Philips Lighting Company
200 Franklin Square Drive
Somerset, NJ 08873
Phone: 855-486-2216
Philips Lighting Company
281 Hillmount Road
Markham ON, Canada L6C 2S3
Phone: 800-668-9008
INSTALLATION INSTRUCTIONS
The B200G is intended for surface mounting only and is suitable for 120VAC or 277VAC, 60 Hz operation.
1.
Remove keyway knockouts (2) if cabinet is to be mounted to the wall.
2.
Remove hole plugs as needed for installing the lamp heads. (Figure 1)
Figure 1
3.
Install lamp heads to cover per instructions provided with lamp heads.
4.
Connect lamp head leads, one grey lead to one terminal on the lamp head, a white lead to the other
terminal. (Figure 4)
5.
Remove appropriate knockout located on sides of cabinet to accept AC service.
6.
Mount cabinet directly to wall or use optional mounting plate MBB. (Figure 2)
Figure 2
7.
Max Mounting Height: 12W Halogen=7.5 ft., 7W/MR16/LED=30 ft., 15W LED AR111=31ft.
8.
Install batteries in battery chamber. DO NOT LIFT BATTERY BY TERMINALS. (Figure 3)
9.
Connect Battery leads to the batteries. (Figure 4). Warning: The unit will be damaged if the batteries
are connected improperly.