TROUBLESHOOTING 

 

Whether it is operating as a 275AP/APF high-side float (Figure 5) or as a 275AF low-side float (Figure 6), the valve opens when the 
liquid  level  drops.  The  operation  of  the  275AF  will  be  covered  first,  because  understanding  its  possible  malfunctions  serve  as  a 
foundation for troubleshooting the 275AP/APF pilot float valve.  

 
Float Valve Only (275AF)

 

 

Problem: 

Valve does not close fully at high liquid level. 

Causes/Solutions:  

Float rod bent or interference with float movement: If the valve 
was  supplied  without  a  chamber  (299A),  the  float  rod  (343A, 
not  on  275APF  valves)  may  have  been  bent  in  shipping.  It  is 
also  possible  that  the  valve  was  installed  in  a  non-standard 
chamber that does not allow full float movement. CAREFULLY 
bending the float rod a small amount may correct this problem. 
Jammed  or  worn  linkage  parts:  Examine  float  and  needle 
movement. Verify that parts move freely and without excessive 
play.  Check  for  excessive  float  block  (230Z)  and/or  lever  pin 
(411)  wear.  Remove  any  debris,  replace  worn  or  damaged 
parts. 
Needle/seat damage or debris present: Remove lever pin and 
float  assembly.  Be  careful  not  to  disturb  the  setting  of  the 
needle  and  the  adjusting  nuts.  Examine  needle  and  seat 
bushing for damage

 and debris. 

A worn or damaged needle/seat 

should always be replaced with a matched set from the factory. 
Hole  in  float  ball:    Liquid  refrigerant  leaking  into  the  float  will 
prevent  it  from  rising  properly  with  changes  in  liquid  level. 
Warming  the  float  will  cause  any  refrigerant  inside  it  to 
vaporize. Observe any vapor leakage from the float to confirm 
a  leak.  To  replace  a  defective  float,  unscrew  the  float.  (Be 
careful  not  to  disturb  the  positions  of  the  nuts  (322,  324).) 
Install  new  float  snugly,  again  without  disturbing  the  nut 
positions.   

 
Problem: 

Valve does not open at low liquid level. 

Cause/Solution:  

Jammed  needle  or  worn  linkage  parts:  Inspect  valve  as 
described above. Repair or replace parts as needed. 
 

 

 
Pilot Float Valve with 700H Valve (275AP/APF)  

 

Figure  9  shows  schematically  how  the  275AP/APF  and  700H 
valves operate together. This is very similar to the arrangement 
shown in Figure 6.  
 
As the liquid level rises in the chamber, the float rises and the 
needle  shuts  off  flow  to  the  700H.  The  pressure  above  the 
700H  piston  drops  and  the  piston  rises  due  to  pressure 
underneath,  opening  the  valve  port  and  allowing  flow. 
Conversely,  as  the  liquid  level  drops,  the  275AP  opens  and 
pressure  above  the  piston  rises,  closing  the  700H  port  with 
spring-assist. 
 
Match  the  condenser  condition  (liquid  high  or  low)  with 
pressure gauge reading (condensing or downstream pressure) 
and note the possible causes given in Table 2. 

 
Figure 9: Schematic of 275AP/700H Operation 

 

Table 2: Troubleshooting The 275AP & 700H 

 

(2) Pressure Gauge reads: 

Approximately Downstream Pressure 

Approximately Condensing Pressure 

(1) 

C

o

n

d

e

n

s

e

L

iqu

id 

L

e

v

e

is

T
o
o

 

h

i

g

The pressure indicates that the 275AP is closed (as it 
should be). Therefore the 700H may be closed due to a 
malfunction. Check if the 700H is stuck partially or 
completely closed by dirt/debris, or if the strainer is blocked. 
Other possibilities: Operating conditions may have changed 
so that (1) The 700H cannot open fully due to too strong 
spring, or (2) the 700H metering plug does not have 
sufficient capacity. Contact Phillips to resolve these issues. 

The pressure indicates the 275AP is open (it is supposed to 
be closed). Therefore the 700H is being signaled to close. 
Check if 275AP float is stuck in low position, or if dirt/debris 
is keeping the needle from seating. 
 

T
o
o

 

l

o

The pressure indicates the 275AP is closed (it is supposed 
to be open). Therefore the 700H is being signaled to open. 
Check if the 275AP is stuck in the closed position. See 
“Float Valve Only: valve does not open” Troubleshooting 
Tips, above, to resolve the problem.  

The pressure level indicates the 275AP is open (as it should 
be). Therefore the 700H is open due to malfunction. Check if 
the 700H is stuck partially or completely open by dirt/debris, 
or the spring may have broken. 
Other possibilities: (1) The 700H piston or body may have 
worn, permitting blow-by that prevents the pressure above 
piston from rising sufficiently to close the valve. (2) 
Operating conditions may have changed so that the 275AP 
does not have sufficient capacity to close the 700H. Contact 
Phillips to resolve these issues. 

 

H. A. Phillips & Co. 

      

            

 

770 Enterprise Avenue 
DeKalb, 

IL 

60115 U.S.A. 

Phone: (630) 377-0050 
Fax: (630) 377-2706 

Condensing 
Pressure 

Downstream 
Pressure 

The 275AP opens 
when the liquid level 
drops. 
The pressure above the 
piston increases when 
the 275AP opens.  
This closes the 700H. 

275AP  

700H  

Liquid 

from 

Condenser 

Liquid  
Out 

Strainer 

Spring 

Summary of Contents for 275AP series

Page 1: ...F AP APF valves are available without a chamber Figure 1 with a cast iron chamber Figure 2 or with a welded steel chamber Figure 3 An optional mounting flange is available for mounting the valve without a chamber Figure 4 The valve should always be oriented such that the 1 2 FPT connection is toward the top of the valve and the front face is vertical This will ensure that the float moves appropria...

Page 2: ...e pin out with pliers or carefully drive it out with a punch Retain the spacers 11S for re assembly After re assembly peen the lever pin to retain in place and check for free movement of valve components Needle and seat replacement The needle and seat bushing are lapped in the factory to create a matched set If either the needle or seat bushing show signs of wear or damage both parts must be repla...

Page 3: ...nto the adjusting nut so the float is slightly above horizontal when the needle is seated in the bushing Figure 8 Tighten the lock nut to secure needle position 7 Remove the lever pin and pull the needle from the bushing Reassemble the float block to the valve body using the lever pin and spacers 11S to ensure the float block 230Z is centered on the link 431 8 Peen the lever pin to retain in place...

Page 4: ...The pressure above the 700H piston drops and the piston rises due to pressure underneath opening the valve port and allowing flow Conversely as the liquid level drops the 275AP opens and pressure above the piston rises closing the 700H port with spring assist Match the condenser condition liquid high or low with pressure gauge reading condensing or downstream pressure and note the possible causes ...

Reviews: