Important-Safety
Before carrying out any servicing on this luminaire, ensure that the mains supply is fully isolated.
Disconnect luminaire before insulation testing of the installation.
Installation Method
Philip Payne Ltd
A SUBSIDIARY OF F.W. THORPE PLC
Thornhill Road, Solihull, B91 2HB, England.
Tel:
0121 705 2384
Fax:
0121 711 2469
e-mail:
Website:
http://www.philippayne.co.uk
Philip Payne Ltd registered in England No. 1361523
ISO9001
FM55077
21LFT054_7
Cleaning Instructions
3
4
6 x LID SCREWS -
TORQUE SETTING -
100Ncm
Operation and Maintenance
Continual operation at mains voltages in excess of the rated voltage will reduce LED and expected gear life.
This luminaire uses plastic components in its construction and when installed in environments containing chemicals, degradation may occur.
Please contact our Technical Department for advice.
Modifications
Philip Payne products should not be modified.
Any modification may render the product unsafe and will invalidate any Safety/Approval marks.
Philip Payne will not accept any responsibility for any modified products or for any damage caused as a result of their modification.
Monthly and Annual Tests
Monthly and Annual tests should be carried out in accordance with BS EN 50172:2004, 7.2.
Testing can be carried out by using a sub circuit isolator or by switching off the lighting circuit at the circuit breaker (not for AutoTest or DALI versions).
Battery pack shall be replaced if the specified 3 hour duration is not met.
For replacement battery pack contact Philip Payne Ltd.
The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.