happens all devices stored in the respective association group will receive a common wireless command.
Association Groups:
1 Relay 1 and 2 together (max. nodes in group: 1)
2 Relay 1 (max. nodes in group: 1)
3 Relay 2 (max. nodes in group: 1)
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however certain configuration can
adapt the function better to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow to configure signed values. In order to set values in the range 128
… 255 the value sent in the application shall be the desired value minus 256. For example: to set a
parameter to 200? it may be needed to set a value of 200 minus 256 = minus 56. In case of two byte value
the same logic applies: Values greater than 32768 may needed to be given as negative values too.
W meter report period (Parameter Number 1, Parameter Size 2) If the setting is configured for 1hour (set
value =720), the device will report its instant power consumption every 1 hour to Z-Wave Controller. Unit: 5
seconds
Value
Description
1 — 32000 seconds (Default 720)
KWH meter report period (Parameter Number 2, Parameter Size 2) If the setting is configured for 1hour (set
value =720), the device will report its power consumption in KWh every 1 hour to Z-Wave Controller. Unit: 5
seconds
Value
Description
1 — 32000 seconds (Default 6)
Selected end point (Parameter Number 3, Parameter Size 1) defines the relays selected
Value
Description
1
Relay 1 and Relay 2 (Default)
2 — 3 Relay 1
3 — 4 Relay 2
5