3. Z-Wave’s Configuration
Configuration
Parameter
Function
Size
(Byte)
Value
Unit
Default
Description
1
Watt Meter
Report Period
2
0x00
-
0x7FFF
5s
720
0: Disable Report W
1~0x7FFF :
720*5s=3600s=1 hour
2
KWH Meter
Report Period
2
0x00
-
0x7FFF
10min
6
0: Disable Report KWh
1~0x7FFF :
6*10min=1 hour
3
Threshold of
current for Load
caution
2
10-1100
0.01A
1100
1100*0.01A = 11A
4
Threshold of
KWh for Load
caution
2
1-10000
1KWh
10000
5
Restore switch
state mode
1
0-2
1
0 : Switch off
1 : Last switch state
2 : Switch on
6
Manual On/Off
mode
1
0-1
1
0
:
Disable
manual On/Off
1
:
Enable
manual On/Off
7
LED indication
mode
1
1-3
1
1 : Show switch state
2 : Show night mode
3 : One flash mode
8
Auto off timer
2
0-0x7FFF
1s
0
0 : Disable auto off
function
1-0x7FFF : 1s ~
32767s
9
RF off com-
1
0-3
0
0 : Switch off
1 : Ignore
mand mode
2 : Switch toggle
3 : Switch on
11
Manual Switch
Report mode
1
0-1
1
0 : Disable
1 : Enable
14
Watt differential
report mode
1
0-4
1
0 : Disable
1 : 5%
2 : 10%
3 : 15%
4 : 20%
3-1
Watt
Meter Report Period:
If the setting is configured for 1hour (set value =720), the PAN10 will report its
instant power consumption every 1 hour to Group1 node. The maximum interval
to report its instant power consumption is 45 hours (5s*32767/3600=45hr).
If the
setting value is 0, the auto report function of meter Watt will be disabled.
3-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), the PAN10 will report its
Accumulated Power Consumption (KWh) every 1 hour to Group1 node. The
maximum interval to report its Accumulated Power Consumption (KWh) is 227.55
days (10min*32767/1440=227.55 days).
If the setting value is 0, the auto report
function of meter KWh will be disabled.
3-3 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if the
setting value is 1100, when the load current of Relay1 over this value, PAN10 will
send current meter report to warn the Group1 node, the Range of the setting
value is from 10 to 1100, and the default value is 1100.
3-4 Threshold of KWh for Load Caution
9