28
ROUTINE MAINTENANCE
Cleaning of filter
The filter is located in the right inside the unit cover. Clean the filter once a month to keep the
refrigerating performance and condition of refrigerating unit.
To clean the filter, follow the procedure below.
WARNING
Do not touch a condenser behind the filter when removing the filter for cleaning.
The condenser
is hot and may cause injury.
1.
As shown in Fig. 1, remove 2 hand screws on the
bottom of the unit cover and remove the unit cover.
2.
Pull the filter to the left (to the front of the evaporating
tray) by taking the finger grip (black) on the left edge as
shown in Fig. 2.
3.
Tilt the filter slightly to the back and take out the filter.
4.
Wash the filter with clean water and dry it naturally.
5.
Set the filter in the front of the evaporating tray and slide
the filter to the right (to the front of the condenser).
6.
Replace the unit cover and fix it with 2 hand screws.
Unit cover
Fig. 1
Filter
Condenser
Fig. 2