Phason 

Natural Ventilation Control 

33440000  

15 

If  you are installing a Phason Rain Sensor, you must enable the sensor input. By default, the input is 

not enabled

.  

 

To enable the sensor 

1.

 

Press 

Up 

or 

Down

 until the display shows 

s e n s

 and the

 Sensor 

LED is lit. 

2.

 

Press 

Select

The current setting (on or off) displays and the

 Sensor 

LED flashes. 

3.

 

Press 

Up

 or 

Down

 to adjust the setting and then press 

Select

The change is saved and the display shows 

s e n s

4.

 

Press 

Back 

to return to the main display. 

 

Testing and maintaining the NVC 

Using temperature test mode 

Temperature test mode allows you to test your equipment and settings by simulating the 
temperature. In temperature test mode, you adjust the “test temperature”.  

As you increase or decrease the test temperature, the relays operate according to their settings and 
the test temperature. This gives you an idea of  how your system performs over a full range of  
temperatures. The relays remain operating according to the test temperature until you exit test mode. 

 

 

 

When the NVC is in temperature test mode, it operates the equipment according 
to the test temperature, not according to the measured temperature.  

 

The NVC does not exit test mode automatically. When you are finished testing, 

press

 Back

 or 

Select

 to exit test mode. 

 

To use temperature test mode 

1.

 

Press 

Up 

or 

Down

 until the display shows 

t e s t

2.

 

Press 

Select

The display shows 

t e n p

3.

 

Press 

Select

The 

Test

 LED flashes and the display shows the test temperature. The NVC is now in 

temperature test mode. 

4.

 

Press 

Up 

or 

Down

 to adjust the test temperature. 

The NVC operates the equipment according to the test temperature. 

5.

 

When finished, press 

Back

 to return the control to automatic mode. Press 

Back 

again to return 

to the main display. 

Summary of Contents for NVC-2-12

Page 1: ...tion the NV or closes the temperature ature is below er on ature is abov er off e s 21 7 iew 13 11 ion 11 5 3 nnection 6 10 rview 9 18 Contro NVC is a fu our curtain o ature in a roo grammed sett ered...

Page 2: ...is w temperature one close odel NVC 2 1 odel NVC 2 24 A at 30 VDC A at 120 23 2 HP at 120 4 A at 125 VA 2 A at 125 VA any equipme s For more e A F F P M P T 5 R R w L 2 12 VDC 4 24 VDC C 30 VAC resis...

Page 3: ...nd Close LEDs will blink three times and then stay off for one second For the heater if the heater is ON the Heat LED will blink three times and then stay ON for one second if the heater is OFF the LE...

Page 4: ...oma Select automa Switch the ala Adjust the tes Restore the fa Display the fir Update the firm Adjust the cur Adjust the cur Adjust the ope Adjust the clo Adjust the clo Adjust the Idle Adjust the hea...

Page 5: ...t a curta n page 6 heater or furna ater on page 6 battery cable to on read Connec nnect the tempe e ribbon cable f n external alarm page 7 nal Rain Sensor memory stick to age 19 5 6 4 ain machine to t...

Page 6: ...s the cu a being more s fired fur s shown in th es using hot on their name urnace man Gas fired fu Make sure y ol front cover a using the fo rner of the b hine equipment c times referre urtain to let...

Page 7: ...rm system An alarm system can be a siren an alarm panel or an auto dialer See your alarm siren s installation guide for installation instructions and information about the type of system The descripti...

Page 8: ...ON the power until you have finished all wiring and verified all equipment is properly connected and free of obstructions Finishing the installation 1 Make sure all wires are properly connected to the...

Page 9: ...olds its position during the close cycle Curtains hold their position while the temperature is within the Idle band of the Set point For example if the Set point is 80 F and the Idle band is 4 F 2 the...

Page 10: ...t The current setting in seconds displays and the On duration LED flashes 3 Press Up or Down to adjust the setting and then press Select The change is saved and the display shows 0 on 4 Press Down to...

Page 11: ...nge is saved and the display shows C on 4 Press Down to move to the Close off duration or Back to cancel and return to the main display To program the Close off duration Default 120 seconds range 1 to...

Page 12: ...own to move to the High alarm or Back to cancel and return to the main display How hysteresis works Hysteresis is the number of degrees above the set point that a heating stage or relay switches off F...

Page 13: ...open When there is a probe damage or probe short condition the control switches all relays off Alarm messages Message and description Possible cause Possible solution Hi High temperature alarm The am...

Page 14: ...LoaL 4 Press Down to move to the Hysteresis or Back to cancel and return to the main display Changing the temperature units The NVC can display temperatures in Fahrenheit or Celsius The default is Fa...

Page 15: ...lays operate according to their settings and the test temperature This gives you an idea of how your system performs over a full range of temperatures The relays remain operating according to the test...

Page 16: ...n override mode For the curtain the Open and Close LEDs will blink three times and then stay off for one second For the heater if the heater is ON the Heat LED will blink three times and then stay ON...

Page 17: ...4 Press Select The display shows Curt or heat depending which item you chose in step 1 5 Press Up or Down to select a different menu item or press Back to return the main display To override the heate...

Page 18: ...lts If for some reason the power on method does not work use the power off method To restore the factory defaults using the POWER ON method 1 Press Up or Down until the display shows test 2 Press Sele...

Page 19: ...need is a USB memory stick and a firmware update file You can update the firmware using one of two methods the power on method or the power off method The power on method is the easiest way to update...

Page 20: ...d then the main temperature display 10 When finished remove the USB drive verify the ribbon cable is properly connected and then fasten the cover to the base To update the firmware using the POWER OFF...

Page 21: ...wiring The display shows unusually high or low temperature The probe is not a Phason probe Remove the probe and then install a Phason probe The extension cable connected to the temperature probe is p...

Page 22: ...includes power contactor relay and mounting hardware for easy mounting in an enclosure Power contactor kit model 122 1 includes power contactor relay on off auto switch and label snubber filter reduce...

Page 23: ...a display kit After replacing the display you will need to program the control If the bottom circuit board fails you can replace it with a control kit Model NVC 2 12 Display kit model K331003 Control...

Page 24: ...he product must not have been involved in an accident misused abused or operated or installed contrary to the instructions in our user and or installation manuals Phason s opinion about these items is...

Reviews: