Phason
Natural Ventilation Control
33440000
15
If you are installing a Phason Rain Sensor, you must enable the sensor input. By default, the input is
not enabled
.
To enable the sensor
1.
Press
Up
or
Down
until the display shows
s e n s
and the
Sensor
LED is lit.
2.
Press
Select
.
The current setting (on or off) displays and the
Sensor
LED flashes.
3.
Press
Up
or
Down
to adjust the setting and then press
Select
.
The change is saved and the display shows
s e n s
.
4.
Press
Back
to return to the main display.
Testing and maintaining the NVC
Using temperature test mode
Temperature test mode allows you to test your equipment and settings by simulating the
temperature. In temperature test mode, you adjust the “test temperature”.
As you increase or decrease the test temperature, the relays operate according to their settings and
the test temperature. This gives you an idea of how your system performs over a full range of
temperatures. The relays remain operating according to the test temperature until you exit test mode.
When the NVC is in temperature test mode, it operates the equipment according
to the test temperature, not according to the measured temperature.
The NVC does not exit test mode automatically. When you are finished testing,
press
Back
or
Select
to exit test mode.
To use temperature test mode
1.
Press
Up
or
Down
until the display shows
t e s t
.
2.
Press
Select
.
The display shows
t e n p
.
3.
Press
Select
.
The
Test
LED flashes and the display shows the test temperature. The NVC is now in
temperature test mode.
4.
Press
Up
or
Down
to adjust the test temperature.
The NVC operates the equipment according to the test temperature.
5.
When finished, press
Back
to return the control to automatic mode. Press
Back
again to return
to the main display.