9
Electrical ratings
Control power
85 to 264 VAC, 50/60 Hz
Actuator Module
15 A at 120/230 VAC, general-purpose (resistive)
1/2 HP at 120 VAC, 1 HP at 230 VAC
RM-2 Relay Module
20 A at 120/230 VAC, general-purpose (resistive)
1 HP at 120 VAC, 2 HP at 230 VAC
RM-4 Relay Module
15 A at 120/230 VAC, general-purpose (resistive)
1/2 HP at 120 VAC, 1 HP at 230 VAC
Variable AC Module
7 A at 120/230 VAC, general-purpose (resistive)
4.9 FLA at 120/230 VAC, PSC motor
1/2 HP at 120 VAC, 1 HP at 230 VAC
800 W @ 120 VAC, 1600 W @ 230 VAC
Variable DC Module /
0 to 10 VDC, 2K Ω load
Variable Chimney Module (DC)
Alarm relay
0.4 A at 125 VAC; 2 A at 30 VDC, resistive load
0.2 A at 125 VAC; 1 A at 30 VDC, inductive load
Using power contactors to increase the capacity of relays
Phason’s 240-volt power contactors are heavy-duty relays that allow you to increase the load
handling capability of control relays. Power contactors are ideal for secondary ventilation fans and
electric heaters.
Phason’s power contactor relays have the following electrical ratings.
Coil
10.2 mA at 240 VAC
Contact
25 A at 240 VAC; resistive
2 HP at 240 VAC, 1 HP at 120 VAC; motor, power factor 0.4
1300 W at 120 VAC; tungsten
For more information about power contactors, visit
Enclosure dimensions and mounting guidelines
Mount the control on a sheltered, vertical surface.
Mount the control with the electrical knockouts facing down.
Mount the control away from sources of moisture and heat.
Summary of Contents for AutoFlex Connect