Connecting Source Power
Table 11
–
Input Wiring
Wire size recommendations based on 600 VAC copper wire, rated either 60°C or 75°C.
Assuming 86°F (30°C) ambient and no more than 3 current carrying conductors in raceway
or earth (directly buried). If phase converter will be in warmer environments, consult NEC
Handbook for temperature correction factor.
Input Wiring Recommendations
Min. Wire
Gauge (60°C)
Min. Wire
Gauge (75°C)
PT007/PTE007
4 AWG
6 AWG
PT010/PTE010
3 AWG
4 AWG
PTE015
1/0 AWG
1 AWG
PT020/PTE020
-
1/0 AWG
PT030
300 kcmil
4/0 AWG
PT040
-
350 kcmil
PT050
2 x 250 kcmil
2 x 3/0 AWG
PT060
2 x 300 kcmil
2 x 250 kcmil
PT075
2 x 500 kcmil
2 x 350 kcmil
PT407/PTE407
10 AWG
10 AWG
PT410/PTE410
8 AWG
8 AWG
PT415/PTE415
4 AWG
6 AWG
PT420/PTE420
4 AWG
4 AWG
PT430
1 AWG
3 AWG
PT440
-
1/0 AWG
PT450
-
2/0 AWG
PT460
250 kcmil
3/0 AWG
PT475
350 kcmil
250 kcmil
PT4100
2 x 250 kcmil
2 x 3/0 AWG