38 |
P a g e
Table 14
- Operating Parameters
DISPLAY MESSAGE
DESCRIPTION
DEFAULT/MIN
/MAX VALUE
MIN FREQUENCY
Minimum output frequency allowed except during startup ramp.
When
SUBMERSIBLE PUMP
parameter is enabled, frequency
will ramp from stop to minimum frequency in one second.
Important in protecting thrust bearing in submersible pumps.
30/5/120
MAX FREQUENCY
Maximum frequency allowed, or target frequency at start-up
ramp. This parameter value cannot be set lower than
MINIMUM FREQ
.
60/5/300
START UP RAMP
Time in seconds from
MIN FREQUENCY
to
MAX
FREQUENCY
. Ramp speed is linear
12/1/120
OVERCURRENT
LIMIT
Setting for motor overload protection, Trip Class 10 curve.
SD002: 9/3/11
SD003: 11/3/13
SD005/SDE005: 18/3/22
SD007/SDE007: 27/3/32
SD010/SDE010: 37/3/38
SDE015: 46/3/48
SD405/SDE405: 10/3/11
SD407/SDE407: 13/3/13
SD410/SDE410: 18/3/22
SDE415: 24/3/26
2XD205: 10/3/11
2XD207: 14/3/15
2XD210: 18/3/22
DRY WELL CURRENT
Drive faults when output current goes below the set value (dry
well protection).
To use this function for dry well protection, make certain the
parameter
DRY WELL KW
is set at zero.
Note: Fluctuating voltage can change motor currents without
any change in power consumption. It may be more accurate to
use the parameter
DRY WELL KW
for drywell protection.
SD002: 0/0/9
SD003: 0/0/11
SD005/SDE005: 0/0/19
SD007/SDE007: 0/0/28
SD010/SDE010: 0/0/33
SDE015: 0/0/46
SD405/SDE405: 0/0/13
SD407/SDE407: 0/0/16
SD410/SDE410: 0/0/21
SDE415: 0/0/24
2XD205: 0/0/13
2XD207: 0/0/16
2XD210: 0/0/21
Summary of Contents for 2XD Series
Page 10: ...4 P a g e 2 3 Dimensional Drawings Figure 5 SD Series Line Drawing...
Page 11: ...5 P a g e Figure 6 SD Series Line Drawing if selected with optional breaker see Figure 9...
Page 12: ...6 P a g e Figure 7 SD Series Line Drawing if selected with optional breaker see Figure 9...
Page 14: ...8 P a g e Figure 9 SD Series Line Drawing...
Page 15: ...9 P a g e Figure 10 SD Series Line Drawing...
Page 16: ...10 P a g e Figure 11 2XD Series Line Drawing...