Voltage Limitations:
According to CEI EN 60204-1, Pfannenberg standard Chiller operation is guaranteed within these ranges:
•
Nominal voltage ±10 % [V]
•
Nominal frequency ±1 % [Hz]
Please refer to the type label to see which are the operating nominal conditions of the unit.
Nominal conditions
V min
[V]
V max
[V]
f min
[Hz]
f max
[Hz]
230 V / 1 ~ / 50 Hz
207
253
49.5
50.5
230 V / 1 ~ / 60 Hz
207
253
59.4
60.6
For units with special voltages please refer to the type label.
7. Process Water / Fluids
PFANNENBERG chillers should be filled to the proper level with an
inhibited glycol
designed for Industrial chillers systems.
Do
not use automotive antifreeze!
The inhibitors used in automotive antifreeze can break down quickly and accelerate the
degradation of the coolant base (glycol); as well as promote corrosion in a system. Silicates used in automotive antifreeze coat
heat exchangers, resulting in reduced heat transfer. Also, silicates can gel causing fouling and plugging of a system.
The ratio of inhibited glycol to water should be adequate to prevent freezing at the lowest ambient temperature. Check the level
with all lines filled.
The glycol mixture should be checked periodically (3 to 6 months) for proper concentrations
. When
filling the system, always use a pre-mixed solution in the proper ratio to maintain freeze and corrosion protection. Distilled water
is
recommended
because many municipal water supplies contain large amounts of chlorine, which can react unfavorably with
glycol.
NOTE: If
user’s circuit is at least 500mm over the hydraulic connection of the chiller, the fluid in the piping may drain
back and overflow the chiller reservoir if the chiller is shut down. This can be prevented by using a check valve in the
supply line, and either a solenoid valve on the return line.
Corrosion protection:
PFANNENBERG recommends that Pfannenberg Protect Glycol is also used as a rust inhibitor.
The percentages of glycol into the mixture is related to the minimum working temperature of the mixture (that must be in line
with the minimum working set point of the unit, please see the technical data of the unit):
Propylene glycol
dilution
Working range temperature
Freezing point
%
Min [°C]
Max [°C]
PP20P
20
+13
+101
-8
PP30P
30
0
+103
-14
PP50P
54
-25
+104
-38
Ethylene glycol
dilution
Working range temperature
Freezing point
%
Min [°C]
Max [°C]
PP20E
20
+13
+102
-8
PP30E
30
0
+103
-15
PP50E
50
-25
+108
-38
CAUTION:
The higher the concentration of glycol the lower the amount of heat rejection you will be
able to get out of the fluid.
Summary of Contents for PC2500 WT CE STD
Page 17: ...English 70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 17 APPENDIX A1...
Page 40: ...Deutsch 70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 40 ANLAGE A1...
Page 63: ...Italiano 70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 63 ALLEGATO A1...
Page 109: ...Fran ais 70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 109 ANNEXE A1...
Page 119: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 119 n 517 2014 16 2014 I n 517 2014...
Page 123: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 123 PFANNENBERG 30 4 6 1 4...
Page 124: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 124 5 6 7 Pfannenberg TN Zpe...
Page 128: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 128 9 10 11...
Page 130: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 130 KLIXON Klixon 1...
Page 131: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 131...
Page 132: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 132 A1...
Page 134: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 134 B1 0 n 517 2014 2 4 2 15 16...
Page 135: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 135 17 18 19 20 21...
Page 137: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 137 B2...
Page 138: ...70040 122_01 _ PC2500_Op _Manual_IT EN DE FR ES RU docx 138 N 16 11 2017 01 _ ACi...