19
PMBus command
OPERATION
CURVE_VBST
(Note.3)
CURVE_VFLOAT
(Note.3)
IOUT_OC_FAULT_LIMIT
CURVE_ICHG
CURVE_ITAPER
CURVE_CC_TIMEOUT
CURVE_CV_TIMEOUT
CURVE_FLOAT_TIMEOUT
VOUT_COMMAND
(Note.2)
VOUT_TRIM
(Note.2)
Adjustable
r
ange
00h(OFF) / 80h(ON)
9 ~ 15V
9 ~ VBST
20 ~ 100A
5 ~ 30A
18 ~ 30V
18 ~ VBST
11 ~ 55A
2.75 ~ 16.5A
60 ~ 64800 Minute
36 ~ 60V
36 ~ VBST
5.5 ~ 27.5A
1.5 ~ 8.25A
-3 ~ 3V
-6 ~ 6V
-12 ~ 12V
Tolerance
Default
N/A
N/A
N/A
N/A
80h(ON)
±
0.18V
±
0.18V
±
2.5A
±
2.5A
±
0.36V
±
0.36V
±
1.34A
±
1.34A
±
5 Minute
±
0.48V
±
0.48V
±
0.67A
±
0.67A
14.4V
13.8V
100A
10A
28.8V
27.6V
55A
5.5A
600 Minute
57.6V
55.2V
27.5A
2.8A
±
0.18V
±
0.36V
±
0.48V
0V
0V
0V
Model
ALL
12V
12V
12V
12V
12V
12V
12V
12V
24V
24V
24V
24V
24V
24V
24V
24V
ALL
48V
48V
48V
48V
48V
48V
48V
48V
Tabel 3-11
◎
Control parameter
Minimum readable current
Model
12V
5A 1A
±
24V
2.7A 1A
±
48V
1.3A 1A
±
Tabel 3-12
Note:
1.
READ_IOUT will display ZERO amp when output current is less than values in the table below.
3.20.5
PMBus Data Range and Tolerance
◎
Display parameters
PMBus command
READ_VIN
READ_TEMPERATURE_1
READ_FAN_SPEED_1
READ_FAN_SPEED_2
READ_VOUT
READ_IOUT
(Note.1)
Range
80 ~ 264V
-40 ~ 100
℃
0 ~ 26500RPM
0 ~ 26500RPM
0 ~ 15V
0 ~ 150A
0 ~ 30V
0 ~ 80A
0 ~ 60V
0 ~ 40A
Tolerance
±
10V
± ℃
5
±
2000RPM
±
2000RPM
±
0.18V
±
2.5A
±
0.36V
±
1.34A
±
0.48V
±
0.67A
Mode
ALL
ALL
ALL
ALL
12V
12V
24V
24V
48V
48V
Tabel 3-10
21
RCB-1600-RHP-1U_1610-21407-0001-E-0420