Pewatron Mean Well RCB-1600 Series User Manual Download Page 10

8

Figure 3-2

Note The RCP-1600 will trigger OLP to shut down itself if the output stays on constant current level condition for more than 5 seconds.

:

3.5 3

.

Output current adjustment

function

(Output current trimming

)

Constant current level(RCP-1600)/output current (RCB-1600) can be adjusted within a range of 20-100% of the rated current via an external DC

source, the wiring is show as below.

V

V

5

5

External voltage

(DC)

External voltage

(DC)

4.7

4.7

Non-Linear

Non-Linear

1

1

RCB-1600-12

RCP-1600-12

0.4

0.4

9

7.2

12

12

15

15

RCB-1600-24

RCP-1600-24

0

0

18

9.6

36

19.2

24

24

48

48

30

30

60

60

RCB-1600-48

RCP-1600-48

0

0

0

0

OUTPUT

  VOL

T

A

GE(V)

OUTPUT

  VOL

T

A

GE(V)

Connection bS & +V, -S & -V on CN1 is required (RCP-1600system

)

Relationship between the output current and the external DC source is shown as below.

System

RCP-1600

System

RCB-1600

+V

-S

CN2 +S

-V

RHP-1U System

LOAD

PC

CN1 -V Signal

EXTERNAL
VOLTAGE

25

24

1

2

Iout

V

0.4 1

4.7 5

20

100

External voltage

(VDC)

OUT

PUT

CU

RRE

N

T

(%

)

Non-Linear

110

Iout

V

0.4

4.7

20

100

External voltage

(VDC)

OUTPUT

CUR

R

EN

T

(%

)

Non-Linear

5

1

3.5.2

Voltage adjustment of whole rack system by an external 0 -5 Vdc source (output voltage trimming function)

PV

26

0~5V

(1) Connect output of the external DC source to PV(PIN 26) and –V(PIN 24) on CN1, as shown in Figure3-1.
(2) Relationship between the output voltage and the external DC

is shown in Figure3-2.

source

(3) When increase the output to a higher voltage level, please reduce the load current accordingly. Output wattage of each unit should not

exceed the rated value under any circumstance.

Figure 3-1 Connection of external  DC voltage source

24

-V

10

RCB-1600-RHP-1U_1610-21407-0001-E-0420

Summary of Contents for Mean Well RCB-1600 Series

Page 1: ...RCP 00 RHP 1U 16 RCB 1600 U s e r s M a n u a l 1 RCB 1600 RHP 1U_1610 21407 0001 E 0420...

Page 2: ...5 Output Voltage Current Adjustment 3 6 Fan Speed Control 3 7 Short Circuit and Over Current Protection 3 8 Over Voltage Protection 3 9 Over Temperature protection and Alarm 3 10 AC OK Signal 3 11 DC...

Page 3: ...lications Universal AC input Full range Built in active PFC function PF 0 98 Protections short circuit overload over voltage over temperature Active current sharing up to 8000W 5 units in one 19 rack...

Page 4: ...48V OUTPUT 24V OUTPUT 12V OUTPUT 48V OUTPUT 24V OUTPUT 12V OUTPUT 48V OUTPUT 24V OUTPUT 12V 20 1A 40 5A 75A 23 5A 47A 87 5A 33 5A 67A 125A 14 0A 14 0A 13 0A 10 5A 10 5A 10 0A 50 60Hz 50 60Hz 50 60Hz R...

Page 5: ...HUMIDITY TEMP COEFFICIENT VIBRATION UL60950 1 TUV EN60950 1 EAC TP TC 004 approved 30 70 Refer to Derating Curve 20 90 RH non condensing 40 85 10 95 RH non condensing 0 03 0 50 10 500Hz 2G 10min 1cyc...

Page 6: ...a 12 twisted pair wire terminated with a 0 1uf 47uf parallel capacitor Under parallel operation of more than one rack connecting together ripple of the output voltage may be higher than the SPEC at li...

Page 7: ...STATUS STATUS STATUS STATUS STATUS 7 10 2 35 SVR SVR SVR SVR SVR 29 5 7 4 Air flow direction 44 14 max 8 4 24 24 7 65 7 65 306 365 E E D D C C B B A A ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS ADDRESS A...

Page 8: ...output terminals V V Auxiliary voltage output 10 8 13 2V referenced to GND AUX pin 22 The maximum load current is 0 8A This output has the built in Oring diodes and is not controlled by the remote ON...

Page 9: ...ion or even damaging the unit in worst scenario s The efficiency will be lower and the to a predetermined safe value if the units are applied with a lower output current will be automatically limited...

Page 10: ...hip between the output current and the external DC source is shown as below System RCP 1600 System RCB 1600 V S CN2 S V RHP 1U System LOAD PC CN1 V Signal EXTERNAL VOLTAGE 25 24 1 2 Iout V 0 4 1 4 7 5...

Page 11: ...ack system ON OFF Single unit ON OFF Figure 3 3 Connection of Remote Control Between CN1 ON OFF and 5V AUX SW Open SW Short Output OFF ON 3 11 DC OK signal 5V AUX 5V AUX ON OFF A CN1 CN1 ON OFF A ON O...

Page 12: ...the connectors both shelf on the rear of the units and inside the rack Figure 3 7 Illustration of how to remove the RCP RCB 1600 from a rack Press down Figure 3 6 Illustration of how to insert the RC...

Page 13: ...ition It is suggested that reduce the total output current by 10 For example RCP 1600 24x15 connected in parallel in 3 rack shelves the total output current should be to 67Ax15unitx0 9 reduced 904 5A...

Page 14: ...1 2 3 4 ON Module No Module No 1 1 A0 A0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 2 A1 A1 3 3 A2 A2 4 4 A3 A3 ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON OFF OFF OF...

Page 15: ...STATUS_WORD STATUS_VOUT STATUS_IOUT STATUS_INPUT STATUS_TEMPERATURE R Byte R Word R Byte R Byte R Byte R Byte 81h 80h 88h 7Eh 8Bh 8Ch 1 1 2 1 2 2 Fan1 and 2 status reporting Manufacture specific statu...

Page 16: ...V 7 2 15V 5A 1A 24V 24V 9 6 30V 2 7A 1A 48V 48V 19 2 60V 1 3A 1A Table 3 6 Table 3 5 Note 2 When using PMBus to adjust output voltage VOUT_COMMAND only can be used to display the rated voltage of the...

Page 17: ...evice address to communicate over the PMbus 7 bit address setting pins are used to assign a device address for a RCB 1600 unit as shown in the below description A0 A2 allow users to designate the addr...

Page 18: ..._OC_FAULT_LIMIT R W Word 81h 80h 88h 8Bh 8Ch 1 1 2 2 2 Fan1 and 2 status reporting Manufacture specific status reporting AC input voltage reading value format Linear N 1 Output voltage reading value f...

Page 19: ...oating timeout setting value of charging curve format Linear N 0 Constant current setting value of charging curve format Linear N 2 Constant voltage setting value of charging curve format Linear N 9 C...

Page 20: ..._STATUS Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 High byte FVTOF CVTOF CCTOF BTNC NTCER EEPER Low byte FVM CVM CCM FULLM Note EEPER When EEPROM Charge Parameter Error occurs the charger stops charging...

Page 21: ...2 8A 0 18V 0 36V 0 48V 0V 0V 0V Model ALL 12V 12V 12V 12V 12V 12V 12V 12V 24V 24V 24V 24V 24V 24V 24V 24V ALL 48V 48V 48V 48V 48V 48V 48V 48V Tabel 3 11 Control parameter Minimum readable current Mod...

Page 22: ...range Model 12V 9 15V 24V 18 30V 48V 36 60V Tabel 3 13 2 When using PMBus to adjust output voltage VOUT_COMMAND only can be used to display the rated voltage of the unit and cannot be It is VOUT_TRIM...

Page 23: ...wn as Figure 4 2 A five is year global warranty provided under normal operation Please do not change ny component or modify the unit by a yourself or MEANWELL may reserve the right not to provide the...

Page 24: ...87 65 osman coban pewatron com Pressure Sensors Load Cells Philipp Kistler Phone 41 44 877 35 03 philipp kistler pewatron com Power supplies Sebastiano Leggio Phone 41 44 877 35 06 sebastiano leggio p...

Reviews: