© Pertronic Industries Ltd
8
FAAST LT Loop-Based Installation & Maintenance Guide Iss 1.0, 201701
2
3
1
3
4
5
6
2
1
IO
N
Front Panel Buttons
The front panel has three (3) user buttons:
TEST
,
RESET
and
DISABLE
These buttons are used to enter the pass-code which then
allows
simple test functions to be performed.
Note: In Remote Maintenance and Service Mode these
buttons
are disabled.
Table 5: Front Panel Buttons
BUTTON
NORMAL Mode
MAINTENANCE Mode
RESET
Press for 2s to start PASSWORD
PROCEDURE to enter
MAINTENANCE
mode
Press for 2s to Reset latched Alarms, Faults
and
sounders (relays).
Alarm controlled by panel: if the
Alarm
persists, set again immediately after the Reset
In DISABLE Mode, press for 2s to exit from
DISABLE Mode (but remains in
MAINTENANCE Mode)
DISABLE
Use to increment Password digits in
PASSWORD PROCEDURE
Press for 2s to enter DISABLE Mode for
60
minutes (default).
Alarms, Alerts and Faults not reported
(To exit DISABLE Mode see RESET)
TEST
Use to confirm password in
PASSWORD
PROCEDURE.
Default Password = 3111
Press for 2s then release - both detectors will
simulate Alarm
Press for 4s then release
– Detector #1 will
simulate Alarm
Press for 6s then release
– Detector #2 will
simulate Alarm
COMBINATIONS
RESET + DISABLE
Press for 2s to show Fan Speed
(on
Smoke Level scales) for a preset time
Press for 2s to show Fan Speed
(on Smoke
Level scales) for a preset time
RESET + TEST
No action
Press for 2s to turn Sounders OFF
RESET + TEST + DISABLE No action
Press for 2s to exit MAINTENANCE mode
Password Sequence to Enter MAINTENANCE mode
a) press and hold
RESET
; Left Flow indicator turns yellow, then green
b) release
RESET
and
FAULT
indicator turns ON (green). The
left Flow indicator blinks green indicating the
device is ready for
the first digit
c) press
DISABLE
to increment the LEDs 1…9; press
TEST
to select a digit
The flashing airflow segment turns ON (green) and the next segment begins to flash indicating set the next digit.
When the 4th digit is selected, all 4 airflow segments turn OFF.
- if the password is accepted the
FAULT
indicator remains green and
the unit enters
MAINTENANCE
mode.
- if the password is incorrect, the
FAULT
indicator flashes yellow and the unit remains in
NORMAL
mode.
The default Password is
3111
If no button is pressed for 10s during the password sequence, the
unit returns to
NORMAL
mode.
If there is no activity in
MAINTENANCE
mode for 5 minutes (default), the
FAULT
indicator blinks green for
15secs and then the unit returns to the
NORMAL
state.
TESTING:
Note that the Laser detector LEDs, which are controlled by the Fire Panel, must be turned ON to activate the front
panel Alarm
indicators
Magnet Test:
The alarm signalling can be tested for functionality by placing a
test magnet in the position shown in Figure 10
(refer Page 4). This method does not test the air flow in the pipe-work
Smoke Testing:
The system alarm response can be tested for functionality
using smoke. The choice of smoke source is
dependent on the
installation but Pertronic industries recommends the use of a Smoke Pen (PN: SMOKEPEN)
In all cases the smoke must be present for the
duration of the test.
Smoke pellets or matches can be used close
to the sampling point to introduce smoke particulates into the
system. It is recommended that smoke with a particulate life cycle
of greater than 120 seconds should be used
–
standard aerosol sprays for
point detector testing do not work well on aspirated systems and therefore a re not
recommended.
Fault Testing:
Simulate a fault on the detector (for example, block the outlet pipe)
and check that a fault is signalled on both the
front panel of the unit
and at the Fire Panel.