Features
»
Configurable NZS 4512:2010 Appendix F sound
patterns when detector active:
»
Switch S1 DOWN: Evacuation signal
»
Switch S1 UP: Alert signal
»
Sounds evacuation signal when SNDR IN activated
»
Configurable to generate an alert signal acceptable
to NZS4512:1997 by giving an evacuation tone
sweep every 15.5 seconds
»
95 dBA maximum sound pressure level
Overview
The Pertronic Sounder Base (PSBAS2220) is an
analogue addressable plug-in detector base with built-in
sounder. The PSBAS2220 generates a tone when the
detector is in alarm, or when directly activated by a bell
circuit.
The PSBAS2220 communicates with any Pertronic
analogue addressable fire alarm control panel via the AA
loop. The base connections connect the sounder base to
the analogue addressable loop, and internally to the LED
drive output of the analogue addressable detector.
When the detector is in the alarm state, the sounder base
generates NZS 4512:2010 Appendix F evacuation or alert
signals, depending on the position of switch S1. (Switch
S1 is accessible only when the unit is removed from its
mounting base.)
The unit may also be powered from a supervised bell
or sounder circuit via the SNDR IN terminals. If the
bell circuit is activated, the evacuation signal will be
generated, irrespective of the detector status.
The PSBAS2220 is normally mounted by recessing it
into the ceiling. A mounting ring is available for surface
mounted applications.
PERTRONIC INDUSTRIES LTD
DATASHEET
Pertronic Sounder Base (PSBAS2220)
Pertronic Analogue Addressable
Sounder Base (PSBAS2220)
Specification
Sound Pressure
Level at 1 m (± 3 dB)
Alert
87 dBA
Evacuation
95 dBA
Analogue
Addressable Loop
connection only
Operating Voltage
15 to 30 V dc
Quiescent Current (non-alarm)
0.4 mA (24 V)
Operating Current (alarm state)
(see note)
8 mA average, 12 mA peak, 15 V
14 mA average, 22 mA peak, 24 V
Bell Driver
connected
with Analogue
Addressable Loop
Quiescent Current (non-alarm)
0.2 mA @ 24 V (Analogue addressable loop)
0.2 µA @ 24 V (Bell driver)
Operating Current (alarm state)
8 mA average, 12 mA peak, 15 V
14 mA average, 22 mA peak, 24 V
Height
Below Ceiling (when recessed)
31 mm (including B501 base)
Above Ceiling (when recessed)
35 mm
With Surface Mounted Extension Cover
66 mm
Surface Mounted Extension Cover
35 mm
Mounting Flange Diameter
122 mm
Colour
Ivory
Note: Operating current sourced from the power supply with the greater voltage (usually bell driver).