background image

Features

 

»

Configurable NZS 4512:2010 Appendix F sound 

patterns when detector active:

 

»

Switch S1 DOWN: Evacuation signal

 

»

Switch S1 UP: Alert signal

 

»

Sounds evacuation signal when SNDR IN activated

 

»

Configurable to generate an alert signal acceptable 

to NZS4512:1997 by giving an evacuation tone 

sweep every 15.5 seconds

 

»

95 dBA maximum sound pressure level

Overview

The Pertronic Sounder  Base (PSBAS2220) is an 
analogue addressable plug-in detector base with built-in 
sounder. The PSBAS2220 generates a tone when the 
detector is in alarm, or when directly activated by a bell 
circuit.
The PSBAS2220 communicates with any Pertronic 
analogue addressable fire alarm control panel via the AA 
loop. The base connections connect the sounder base to 
the analogue addressable loop, and internally to the LED 
drive output of the analogue addressable detector.
When the detector is in the alarm state, the sounder base 
generates NZS 4512:2010 Appendix F evacuation or alert 
signals, depending on the position of switch S1. (Switch 
S1 is accessible only when the unit is removed from its 
mounting base.)
The unit may also be powered from a supervised bell 
or sounder circuit via the SNDR IN terminals. If the 
bell circuit is activated, the evacuation signal will be 
generated, irrespective of the detector status.

The PSBAS2220 is normally mounted by recessing it 
into the ceiling. A mounting ring is available for surface 
mounted applications.

PERTRONIC INDUSTRIES LTD

DATASHEET
Pertronic Sounder Base (PSBAS2220)

Pertronic Analogue Addressable 

Sounder Base (PSBAS2220)

Specification

Sound Pressure 

Level at 1 m (± 3 dB)

Alert

87 dBA

Evacuation 

95 dBA

Analogue 

Addressable Loop 

connection only

Operating Voltage

15 to 30 V dc

Quiescent Current (non-alarm)

0.4 mA (24 V)

Operating Current (alarm state)

(see note)

8 mA average, 12 mA peak, 15 V

14 mA average, 22 mA peak, 24 V

Bell Driver

connected 

with Analogue 

Addressable Loop

Quiescent Current (non-alarm)

0.2 mA @ 24 V (Analogue addressable loop)

0.2 µA @ 24 V (Bell driver)

Operating Current (alarm state)

8 mA average, 12 mA peak, 15 V

14 mA average, 22 mA peak, 24 V

Height 

Below Ceiling (when recessed)

31 mm (including B501 base)

Above Ceiling (when recessed)

35 mm

With Surface Mounted Extension Cover

66 mm

Surface Mounted Extension Cover

35 mm

Mounting Flange Diameter

122 mm

Colour

Ivory

Note: Operating current sourced from the power supply with the greater voltage (usually bell driver).