Perlick US10KP Installation And Operation Instructions Manual Download Page 7

7

Form No. Z2026

Rev 01.28.09

General Information

Electrical Requirements 

The package unit must be installed so that the wir-
ing conforms to, and is in accordance with National 
and Local Electrical Codes. (See Condensing Unit 
Data Plate for Electrical Specifications.

CAUTION:

 Do not attempt to operate the condens-

ing unit on any other power source than that listed 
on the unit data plate. See appropriate wiring dia-
gram on pages 9, 10 or 11.

Starting The Cooler   

Allow the empty utility cooler to operate 24 hours 
for a settling-out period before use.

Temperature Control   

The temperature control is located on the evapo-
rator housing. It is factory adjusted to maintain a 
temperature of approximately 34° F. cut out and 
40° F. cut in. Cut out temperatures lower than 34°F. 
are not advisable as excessive frost may accumu-
late on the evaporator.

If excessive frost does accumulate, the unit is 
operating at too cold a temperature. To defrost the 
evaporator, turn off the electrical power to the con-
densing unit or turn the control to a warmer posi-
tion to allow the fan motor to defrost it. The control 
should then be reset to a temperature that will not 
ice up the evaporator. A plastic drain hose should 
be attached to the drain pan of the evaporator and 
routed through the wall panel. A receptacle should 
be provided for accumulated condensing water or 
connect to a building drain facility.

Ventilation Requirements 

Air-cooled units must be furnished with sufficent 
ventilation to maintain their efficiency. The table  
at right indicates the minimum room size/cubic 
footage, only the space above the condensing  
unit can be used. When the room size is below 
minimum, some type of forced ventilation must  
be provided.

There should be nothing on or around the machin-
ery compartment area which will restrict the flow of 
room temperature air to the condenser or over the 
compressor.

Compressor H.P.

Natural 

Circulation Cu. 

Ft. Room Volume 

Needed

Forced Air  

Circulation C.F.M. 

Fresh Air Entering 

Room

1/3 to 1/2

600

220

Cleaning the Condensing Unit 

Inspect the machinery compartment every 60 days. 
A heavy accumulation of dirt and/or grease on 
the front of the condensing unit (radiator) must be 
cleaned off with a stiff brush or vacuum cleaner. be 
careful not to bend the aluminum fins on the con-
densing unit.

Warranty 

 

This Utility Cooler is fully warranted against defects 
in both material and workmanship for a period 
of one (1) year from date of sale. Defective parts 
must be returned to Perlick freight prepaid. All 
parts found to be defective upon inspection will be 
replaced on a no-charge basis, F.O.b. our factory. 
Perlick is not responsible for parts damaged by 
alteration, unauthorized service, accident or abuse. 
All costs incident to replacement, including labor, 
refrigerant, and/or loss of sales are incidental to 
this warranty and must be borne by the user.

Perlick is committed to continuous improvement. Therefore, we reserve the right to change specifications without prior notice.

Summary of Contents for US10KP

Page 1: ...558 5592 E Mail Perlick Perlick com www Perlick com IMPORTANT INFORMATION This manual has been prepared to assist you in the installation of your Utility Cooler and to acquaint you with its operation and maintenance We dedicate considerable time to ensure that our products provide the highest level of customer satisfaction If service is required your dealer can provide you with a list of qualified...

Page 2: ...ains through access hole in wall 20 x 1 2 I D drain line provided refrigeration R134a refrigerant insulation 4 UL Class 1 urethane foam Flame Spreading Rate 25 or less Smoke Develop Rating 450 or less DOORS Flush mounted with cam lift chrome hinges automatic door closer magnetic gaskets chrome pull handle Standard right hinged Door size 30 W x 55 H features Light ON indicator in door Light switch ...

Page 3: ...rance is required between the top of the utility cooler and the ceiling of the building in which it is being installed Self contained Units Sufficient clearance above the cooler must be allowed for ceiling panel and condensing unit installation For ventilation requirements see page 7 The Cam Lock Fastening Method This utility cooler utilizes the cam lock fastening method See illustration on below ...

Page 4: ...mbly 1 Place do not slide all sections into position 2 Each panel is numbered on the edge For a four keg cooler follow the assembly order on page 5 For a ten keg cooler the assembly order appears on page 6 Note If ceiling height in building is restricted panel s can be carried through the door open ing and placed into position from inside the cooler 3 Install cap plugs in all cam lock holes 4 Seal...

Page 5: ... the right to change specifications without prior notice Four Keg Cooler Assembly Assemble panels as follows Section 1 Floor Section 2 Left Wall Section 3 Left Back Wall Section 4 Right Back Wall Section 6 Front with Door Section 5 Right Wall Section 7 Ceiling FRONT VIEW FLOOR 3 PANEL NO S UNIT COOLER 4 6 1 5 7 2 ...

Page 6: ...ooler Assembly Assemble panels as follows Section 1 2 Floor Section Section 3 Left Wall Section 4 Left Back Wall Section 5 Right Back Wall Section 3A Right Wall Section 6 Right Front Wall Section 7 Door Section Section 8 Left Front Panel Section 9 Celing Panel with Evaporator Housiing Section 10 Celing Panel FRONT VIEW COOLER UNIT COOLER PANEL NO S 4 5 3 3A 9 2 1 6 8 10 10 7 9 ...

Page 7: ...Ventilation Requirements Air cooled units must be furnished with sufficent ventilation to maintain their efficiency The table at right indicates the minimum room size cubic footage only the space above the condensing unit can be used When the room size is below minimum some type of forced ventilation must be provided There should be nothing on or around the machin ery compartment area which will r...

Page 8: ...Compressor Only 57499 Compressor Only 57860 Condensing Unit Fan Motor 57513 Condensing Unit Fan Motor C15250A2 Condensing Unit Fan Blade C3150 3 Condensing Unit Fan Blade C15250A3 Evaporator Coil Assembly 57861 Evaporator Coil Assembly 57872 E xpansion Valve 57877 E xpansion Valve 57877 Temp Control two wired 57891 Temp Control two wired 57891 all model UTILITY COOLERS Description Part Number Desc...

Page 9: ...ions without prior notice Wiring Diagram Four Keg Self Contained Cooler OVERLOAD RELAY FAN GREEN BROWN WHITE WHITE WHITE WHITE WHITE BROWN BROWN LIGHT SWITCH BLACK BLACK BLACK EVAPORATOR FAN MOTORS ELECTRONIC THERMOSTAT 4 MIN ON DELAY ALTERNATE THERMOSTAT STANDARD BLACK GREEN GREEN COMPRESSOR TERMINALS CAPACITOR L1 1 2 C R S L2 ...

Page 10: ...rior notice Wiring Diagram Ten Keg Self Contained Cooler OVERLOAD RELAY 1 L 3 1 C R S 5 M 2 GREEN BROWN GREEN WHITE EVAPORATOR FAN MOTORS BLACK WHITE WHITE BLACK LIGHT SWITCH BLACK WHITE FAN CONDENSER COMPRESSOR TERMINALS BROWN GREEN WHITE RED YELLOW BLUE CAPACITOR ELECTRONIC THERMOSTAT 4 MIN ON DELAY ALTERNATE THERMOSTAT STANDARD BLACK BROWN ...

Page 11: ...11 Form No Z2026 Rev 01 28 09 Perlick is committed to continuous improvement Therefore we reserve the right to change specifications without prior notice ...

Page 12: ...8300 West Good Hope Road Milwaukee WI 53223 Phone 414 353 7060 Fax 414 353 7069 Toll Free 800 558 5592 E Mail Perlick Perlick com www Perlick com Form No Z2026 Rev 01 28 09 ...

Reviews: