8.4.2.11 P3(Current protection of compressor) error diagnosis and solution.
Error Code
P3
Malfunction decision
conditions
If the outdoor current exceeds the current limit value, the LED
will display the failure.
Supposed causes
●
Wiring mistake
●
Over load protector faulty
●
System block
●
Outdoor PCB faulty
Trouble shooting:
Current protection of compressor
Current protection of compressor
Judge 1: Check whether the input
current of the power supply wire
is more than 12.5A(18K) (For
27K, it is 17.For 30K, it is 18.5.For
36K, it is 23A)
Judge 1: Check whether the input
current of the power supply wire
is more than 12.5A(18K) (For
27K, it is 17.For 30K, it is 18.5.For
36K, it is 23A)
Yes
Replace the electric control box
Replace the electric control box
Check whether the
refrigerant system
is ok
Check whether the
refrigerant system
is ok
Judge 2: Check whether the
outdoor ambient temperature
is higher than 50
℃
Judge 2: Check whether the
outdoor ambient temperature
is higher than 50
℃
No
Stop the unit
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant pipe is
blocked
Judge 5: The refrigerant pipe is
blocked
No
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize
and charge the refrigerant again
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize
and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether the
system can run normally
Replace outdoor main
board,and check whether the
system can run normally
No
Yes
Trouble is solved
Trouble is solved
Replace outdoor main board
Replace outdoor main board
No
Summary of Contents for 1PAMSH18-MZO2-16
Page 3: ... Model 1PAMSH27 MZO3 16 W210 metal plate 113 Model 1PAMSH36 MZO4 16 W520 metal plate 128 ...
Page 6: ...2 Suggested Indoor Unit Model Numbers ...
Page 7: ......
Page 9: ......
Page 23: ...7 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor 1PAMSH18 MZO2 16 ...
Page 24: ...PCB board of 1PAMSH18 MZ O2 16 ...
Page 25: ...IPM board of 1PAMSH18 MZO2 16 ...
Page 26: ......
Page 27: ...8 2 Wiring diagram of 1 drive 3 outdoor 1PAMSH27 MZO3 16 ...
Page 28: ......
Page 29: ......
Page 30: ...PCB board of 1PAMSH27 MZO3 16 ...
Page 31: ...IPM board of 1PAMSH27 MZO3 16 ...
Page 32: ...8 3 Wiring diagram of 1 drive 4 outdoor 1PAMSH36 MZO4 16 ...
Page 33: ...PCB board of 1PAMSH36 MZO4 16 ...
Page 34: ...IPM board of 1PAMSH36 MZO4 16 ...
Page 35: ...PFC board of 1PAMSH36 MZO4 16 ...
Page 36: ...8 4 Wiring diagram of 1 drive 5 outdoor ...
Page 37: ......
Page 71: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone ...
Page 72: ...P N for qua zone ...
Page 73: ...bridge rectifier for dual tri zone bridge rectifier for qua zone ...
Page 74: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V ...
Page 76: ...Two ports of the inductance Inductance ...
Page 77: ......
Page 80: ...Vsp FG ...
Page 82: ......
Page 85: ......
Page 88: ......
Page 90: ......
Page 103: ...6 EXV check Disconnect the connectors ...
Page 105: ...Red Blue Red Yellow ...
Page 106: ...Brown Orange Brown White ...
Page 121: ...Screws of front panel Screws of right rear panel Screws of top cover ...
Page 136: ...Screws of front panel Screws of big handle Screws of right rear panel ...